Electrical Lab Equipment Upgrade

Active
Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

AI Contract Overview

Show more

This procurement involves the purchase and installation of components to replace an outdated substation and upgrade the power center in the electrical lab at the National Mine Health and Safety Academy. The project aims to provide students with modern training equipment and includes the rebuilding of a complete mine power system ranging from 750 to 1000 kVA and a 15 kV substation simulator. Key technical requirements include high voltage input sections, main and control transformers, neutral ground resistors, and various circuit breakers and relays. The current contract, held by Trey K Mining & Electric, Inc., is valued at 172,770 dollars with a potential end date of August 31, 2026. This opportunity is classified as a likely recompete with medium confidence and was competed under SAP as a firm fixed price agreement. Performance will take place in West Virginia, and the Department of Labor emphasizes that an onsite visit is highly recommended due to the site-specific nature of the installation and the potential need for a new concrete pad.

General Info

Trey K Mining installs substation and power center upgrades in West Virginia for $172,770.

NAICS

335999 - All Other Miscellaneous Electrical Equipment and Component Manufacturing

Place of Performance

WV, 25813, USA

Set-Aside

NONE

Documents

0

No documents available

Documents will appear here when they are available.

AI Contract Breakdown

Uniform Contract Format

No documents to break down

The breakdown needs solicitation documents. None were found from this contract's source.

Timeline

1 update
Posted

pre-forecast

Notice updated

The notice description changed.

Ready to pursue this opportunity?

Get full access to track this contract, build proposals with AI assistance, and manage your pipeline.

Organization & Contact Information

Show more
AgencyDepartment Of Labor → DOL - Cas Division 4 Procurement
Contacts2 people available
OfficeWASHINGTON, DC, 20210, USA
Office AddressWASHINGTON, DC, 20210, USA

Full Description

Show more
Predicted recompete opportunity based on federal award data.
Current Contract: 1605C426P00001 Incumbent: TREY K MINING & ELECTRIC, INC. Contract Value: $172,770 Potential End Date: 2026-08-31T00:00:00.000Z Competition: COMPETED UNDER SAP Pricing: FIRM FIXED PRICE Classification: recompete-likely (Confidence: medium - 65/100)

The objective of this procurement is for the purchase and installation of components to replace
the existing out-of-date substation behind the Mine Simulation Lab located at the National Mine
Health and Safety Academy, and to purchase and install components to upgrade the power center
in the electrical lab. This upgrade is needed to provide students with the most updated equipment
for training. 


The following are the REQUIREMENTS: 
The following products and tasks are required under this Contract:


750 kVA -1000 kVA COMPLETE MINE POWER SYSTEM
The underground coal mine power center is to be rebuilt with all components listed below and
Fully Functional at Completion.


HIGH VOLTAGE INPUT SECTION
 1 Input Coupler, 15kV, 600A. (PLM High Voltage Couplers)
 1 Feedthrough Coupler, 15kV, 600A. (PLM High Voltage Couplers)
 1 Palm E-Stop pushbutton
 6 Top Cover Interlock Switches
 12 Side Cover Interlock Switches
 1 Visible Disconnect Switch, 600A, 5kV. Grounded in the open position, Lockable Handle, With Viewing window for switch position
 3 H.V. Fuses, 3/7.2kV, Properly Sized
 3 Lightning Arrestors, Properly Sized


MAIN TRANSFORMER
 1 Primary kVA / Voltage 750-1000kVA @ 4160V Delta or Equivalent Transformer
 1 Secondary #1 kVA / Voltage 350kVA @ 995Y/575 Volts or Equivalent Transformer
 1 Secondary #2 kVA / Voltage 400kVA @ 480Y/277 Volts or Equivalent Transformer
 Install counter flashing
 Impedance 5% to 7% Z

 Phase: Three
 Frequency: 60 Hz


CONTROL TRANSFORMER
 1 Primary kVA / Voltage Single Phase 480/240/120 volts or Equivalent Transformer


MISCELLANOUS
 1 995 Volt Secondary Neutral Ground Resistor / 575 L-N, 15 Amp, Ground Resistor or Equivalent.
 1 Back-Up Ground Fault Monitor for 995 Volt Circuit
 1 480 Volt Secondary Neutral Ground Resistor / 277 L-N, 15 Amp, Ground Resistor or Equivalent.
 1 Back-Up Ground Fault Monitor for 480 Volt Circuit
 1 Zigzag XFMR to derive the neutral for the Delta Connected Secondary XFMR
 1 Current induced Test Circuit for all circuits without the use of HV, transfer-switch and 120 VAC 20-amp input plug


OUTPUT CIRCUITS
 1 E2L 400A 1000V Circuit Breaker with trip range of 500-2500 With MCI 25593 with Ground Monitor and TJB Receptacle and Plug Install one ply of Optimax mineral in Weather King adhesive (4’ x 4’) 1 completed panel including all devices 1 E2L 400A 600V Circuit Breaker with a trip range of 500-2500 With MCI 25593 With MCI 25593 Ground Monitor and No.64 Receptacle and Plug 1 completed panel including all devices
 1 E2L 400A 600V Circuit Breaker with a trip range of 500-2500 With MCI 25593 Ground Monitor and Joy X8345 Receptacle and Plug 1 completed panel including all devices
 1 E2K 225A 600V Circuit Breaker with a trip range of 200-1500 With GM8000 Wireless Monitor and Ground Relay Figure with No.67 Receptacle and Plug 1 completed panel included all devices
 1 E2K 225A 480V Circuit Breaker with a trip range of 200-1500 With 25593 Wired/Impedance Monitor and Ground Relay Figure with No.67 Receptacle and Plug 1 Complete panel including all devices
 1 Unit to be Shipped Factory Assembled
 (3) Electrical Drawings (complete set of at least 1 in digital format)


ADDITIONAL REQUIREMENTS
 All control wirings shall be 600-volt type SIS stranded copper conductor and shall not be smaller than #14 AWG. Control wiring shall be run in vented plastic wire-ways, where possible. No wiring will be spliced. All copper buss work and brace to withstand short
circuit stresses.
 All high voltage cables will be an adequate type and supported with fiberglass supports and hangers. No high voltage cables are allowed to come in contact with other high voltage cables or ground. A 3” separation is maintained between insulated cables and a 3” clearance phase to ground.
 Wiring labeled according to wiring diagrams and schematics and correspond with appropriate termination point.
 Terminal blocks to be marked and located adjacent to proper termination point.
 Warning and hazard labels to indicate voltage levels present.
 Labels for operating devices.
 Circuit breaker and fuse tags to indicate capacity and circuits protected.
 Existing Equipment in good working conditions recommended to be used such as
Enclosure, Circuit Breakers, Ground Monitors, Test Circuit, ground resistor
 Existing Power Center needs to be sized to fit existing glass lids that are installed on existing power center located in electrical – lab
 Onsite visit highly recommended as this is a site-specific request.
 Finish Paint Required


15 kV SUBSTATION SIMULATOR
The substation simulator is to be rebuilt with components listed below in workman-like manner
and Test Circuits Fully Functional at Completion. Unit Will Only Be Provided with Low Voltage
Control Power Not to Exceed 240 volts.


MAJOR COMPONENTS
 1 High Voltage, 600 Amp Vacuum Circuit Breaker or Equivalent
 1 Strain Clamp In/Out or Equivalent
 1 Visible Disconnect, 15kV, 600 A or Equivalent
 1 Neutral Ground Resistor, 12.47 kVL-L, 7200L-N, 15A or Equivalent
 3 300 5 Phase Current Transformers Properly Sized for Relays
 1 Potential Transformer (PT) with voltage relay for back up ground default
 Lightning arrestors for primary and secondary


TEST CIRCUITS
 1 Switch for Relay Selection
 4 General Electric Electro-mechanical relays or equivalent
 1 Schweitzer – SEL751A Relay or equivalent
 1 Schweitzer – SEL501 Relay or equivalent
 1 General Electric- 735 Multilin Relay or equivalent
 4 Westinghouse CO Relay or equivalent


MISCELLANOUS
 1 Breaker Control & Indication Circuit
 1 Capacitor Trip Circuit
 1 High Voltage Ground Monitor MCI 24286 or equivalent
 3 sets Electrical Drawings (three complete sets, at least one in digital format)
 Isolated Ground Field at least 25 Feet from the substation must be installed to measure 25 NEC requirements
 All Test Circuits to be Selectable
 Guy Wires repaired/installed as needed
 Existing Equipment in good working condition recommended to be used such as Ground resistor, Mechanical Relays, etc.
 If the existing concrete pad is not sufficiently sized for the Enclosure footprint a new pad is required

Similar Contracts

Same NAICS industry code

More opportunities from Department Of Labor → DOL - Cas Division 4 Procurement

Same awarding agency

Earlier notices in this NAICS code

Posted before this notice, open and closed

Ready to Pursue This Opportunity?

Get AI-powered intelligence on this solicitation and the ones like it

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS