Fire Alarm and Suppression System Maintenance

Closed
FA568226QA001Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 561621
New
Centennial Fire Alarm & CO Detection Upgrade and Maintenance Services
Solicitation # centennial-fire-alarm-co-detection-upgrade-maintenance-services
Management & Training Corporation (MTC) is soliciting bids for a fixed-price, single lump sum contract to provide fire alarm and carbon monoxide (CO) detection upgrade and maintenance services at the Centennial Job Corps Center in Nampa, Idaho. The primary objective is to restore the central Simplex 4020 Fire Alarm Control Center Panel and connected systems across nine campus facilities to full operational status. The scope of work includes diagnosing and clearing system trouble statuses, upgrading the control panel motherboard or firmware if necessary, and integrating CO detection into the men's and women's dormitories by installing intelligent multi-criteria detectors and sounder bases. All work must adhere to NFPA 101 (2024), NFPA 72 (2025), IFC (2024), and local building and fire codes. Bids are due by December 1, 2026, and must be submitted following a mandatory physical site visit. Evaluation is based on overall best value, and bidders must provide a detailed cost breakout and proof of insurance. For bids equal to or exceeding $25,000, a bid bond of 20% of the base bid is required, and the awarded contractor must provide performance and payment bonds from an A-rated surety company. This project is subject to the Davis-Bacon Act and Construction Wage Rate Requirements, necessitating the submission of weekly certified payroll reports for payment processing. The solicitation is set aside for small businesses, including VOSB, SDVOSB, WOSB, and HUBZone certifications, and requires a Unique Entity ID (UEI) for all bidders. Final acceptance is contingent upon a successful on-site inspection and the delivery of operation and maintenance manuals and NFPA 72 certification.
Management & Training Corporation/Centennial Job Corps Center

POSTED

about 2 hours ago

DEADLINE

in about 1 month

General Info

Agency

Department Of Defense → FA5682 31 Cons (unit 6102)

NAICS

561621 - Security Systems Services (except Locksmiths)

Place of Performance

CAMPIA TURZII , AE, 405100, ROU

Set-Aside

NONE

Documents

1

Performance Work Statement for Fire Alarm and Suppression System ITM Services

PDF, High priority: read this firstpws
High

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

PhaseClosed
Posted

Sources Sought

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Start your free trial to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Defense → FA5682 31 Cons (unit 6102)
Contacts2 people available
OfficeAPO, AE, 09604-6102, USA
Organization / Agency
Department Of Defense → FA5682 31 Cons (unit 6102)
Office AddressAPO, AE, 09604-6102, USA
Contacts

Full Description

Show more

1.0 General Information
1.1 Description of Services & Introduction This Performance Work Statement (PWS) requires a contractor to provide all personnel, equipment, tools, materials, supervision, and other non-personnel services necessary to perform comprehensive inspection, testing, and maintenance (ITM) for the existing fire alarm and suppression systems installed at the VM Hangar and SOF facilities, as defined in this PWS. The contractor shall perform all services to the standards specified in this contract.
1.2 Background The facilities are equipped with an Olympia Electronics analogue addressable fire alarm system and associated water-based suppression systems. Proper maintenance and inspection are critical to ensure the safety of all personnel and the protection of government property.
1.3 Objectives The primary objective of this contract is to ensure the fire alarm and suppression systems are maintained in a constant state of readiness and full operational capability, compliant with all applicable standards and manufacturer requirements.
1.4 Scope The contractor shall provide all necessary management, supervision, labor, materials, tools, and equipment to perform comprehensive ITM, smoke detector cleaning, repair services, and technical assistance for the fire alarm and water-based suppression systems. This scope covers the Olympia Electronics BSR-1004 Analogue Addressable Fire Alarm Panel, all connected peripheral devices, and all water-based suppression systems and associated equipment as detailed in Section 2.0.
2.0 Equipment to be Serviced
This PWS requires a contractor to provide services for the existing fire alarm and suppression systems installed at the facility. The contractor shall be responsible for all labor, tools, materials, and supervision necessary to perform maintenance, inspection, and potential repair or replacement services on the equipment detailed below.
2.1 Fire Alarm Control Panel Specifications
The fire alarm system is controlled by an Olympia Electronics analogue addressable panel. All work must be compatible with this specific model and its associated components.
Specification
Details
Equipment Type
Analogue Addressable Fire Alarm Panel
Manufacturer
Olympia Electronics
Model
BSR-1004
Serial Number (S/N)
2938
System Type
Analogue Addressable
System Capacity
4 Loops
Repeater Panel
Compatible with BSR-1000 Repeater Panel
Power Supply
220-240V AC, 50-60Hz, 130VA Max
Enclosure Rating
IP30
Country of Origin
Greece
2.2 WATER BASED SUPPRESSION SYSTEMS
These systems include but, are not limited to all associated equipment such as: tamper switches, pressure switches, flow switches, fire pumps, water reservoir tanks, liners, bladders, and air compressors. The Contractor’s area of service responsibility starts at Main Control Valve (MCV) (e.g., Post Indicator valve) with its tamper switch (if provided) and applies to all water suppression systems downstream of MCV.
2.3 Compliance and Standards
The contractor must ensure that all work performed, and any parts or components replaced, meet or exceed the original equipment manufacturer (OEM) specifications and comply with the following European standards to which the panel is certified, as well as all applicable local and national standards, regulations, and laws for the installation location.
• EN 54-2:1997+A1:2006 (Control and indicating equipment)
• EN 54-4:1997+A1:2002+A2:2006 (Power supply equipment)
• CE Mark (Notified Body: 1293)
• Construction Products Regulation (CPR) No: 1293 - CPR - 0658 Rev.1
• Declaration of Performance (DoP) No: 921100400_59_001
The contractor is responsible for verifying all site conditions and equipment details prior to commencing work.
3.0 Scope of Work
3.1 Required Tasks
Task
Description
3.1.1 Semi-Annual System Inspection & Testing
Conduct a complete functional and visual inspection of 100% of the fire alarm system components on a semi-annual basis. This includes testing every smoke detector, manual call point, and audible/visual notification appliance to ensure proper operation and communication with the main control panel, in line with UNI 11224 requirements for addressable systems.
3.1.2 Smoke Detector Cleaning
As part of the ITM service, clean all addressable smoke detectors that indicate a 49% or higher analog level at the FACP. The contractor must download and provide a status report from the FACP before and after cleaning.
3.1.3 Preventive Maintenance
Clean all system components as needed, check for environmental changes affecting device performance, and perform all manufacturer-recommended preventive maintenance actions during scheduled visits.
3.1.4 Emergency and Extraordinary Maintenance
Provide emergency, on-call repair services to correct any system deficiencies or malfunctions. The contractor must respond and be onsite within 4 normal working hours after receipt of a service call.
3.1.5 Deficiency Correction
Correct all deficiencies identified during inspection or testing. Minor deficiencies shall be corrected during the inspection visit. For major deficiencies requiring parts or extended labor, the contractor shall provide a written quote for repair within 5 business days of discovery.
3.2 Deliverables and Reporting
Deliverable
Description
3.2.1 ITM Service Schedule
No later than ten (10) working days after award of the contract, the contractor shall submit a detailed schedule for all mandatory ITM services for approval. This schedule must be adhered to and updated as necessary.
3.2.2 ITM Service Report
Within two (2) working days of completing any inspection, the contractor shall submit a detailed dual-language report. The report must include a list of all devices tested, their status (pass/fail), a description of any deficiencies found, and the corrective actions taken or recommended.
3.2.3 Certificate of Compliance
Upon completion of the first semi-annual inspection and annually thereafter, the contractor shall provide a formal Certificate of Compliance stating that the fire alarm system is fully operational and meets all relevant EN 54 and local fire code standards.
3.2.4 Emergency / Extraordinary Service Report
A service report shall be provided by the second working day following the completion of any emergency or extraordinary repair, detailing the nature of the fault, cause, description of work completed, hours expended, and materials used.
3.2.5 Weekly Service Submittals
The contractor shall provide a weekly summary including a parts history summary, a work order tracker, and performance metrics.
4.0 Period of Performance
The period of performance for this contract will be for one (1) Base Year of twelve (12) months, with the possibility of four (4) additional one-year Option Periods. The exercise of any Option Period will be at the sole discretion of the Government.
Period
Duration
Start Date
End Date
Base Year
12 Months
[Insert Start Date]
[Insert End Date]
Option Year 1
12 Months
[Insert Date]
[Insert Date]
Option Year 2
12 Months
[Insert Date]
[Insert Date]
Option Year 3
12 Months
[Insert Date]
[Insert Date]
Option Year 4
12 Months
[Insert Date]
[Insert Date]
5.0 Contractor Qualifications
The Contractor must meet the following minimum qualifications to be considered technically acceptable for this contract.
5.1 Corporate Experience The Contractor shall have a minimum of five (5) years of continuous corporate experience in the inspection, testing, maintenance, and repair of commercial-grade, analogue addressable fire alarm systems.
5.2 Technician Certification and Training All technicians must be fully trained and certified to work on analogue addressable fire alarm systems.
5.3 Key Personnel The Contractor shall appoint key personnel, including a primary and alternate point of contact, who are responsible for the performance of the work.
5.4 Language Proficiency All contractor personnel must be proficient in the local language. Key personnel who
interact with the Contracting Officer's Representative (COR) must also be proficient in English.
5.5 Licensing and Insurance The Contractor must possess and maintain all required local, state, and national licenses and permits necessary to legally perform fire alarm system services.
5.6 Emergency Response Capability The Contractor must demonstrate the capability to meet the emergency response time requirements as specified in Section 3.1.4.

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown