Uninterrupted Power Supply Equipment

Awarded
36C24W25Q0238Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

AI Contract Overview

Show more

The Eastern Oklahoma VA Health Care System is seeking a contractor to supply and deliver Uninterruptible Power Supplies (UPS) and Power Distribution Units (PDUs) to support critical communication infrastructure at the new Tulsa VA Medical Center, scheduled to open in September 2025. The scope includes providing rack-mounted UPS systems, vertical PDUs for data and telecommunication rooms, and backup batteries, all compliant with VA standards and the Department of Veterans Affairs Office of Information and Technology guidelines. Delivery must occur between September 4th and 12th, with coordination required with the VA Contracting Officer Representative (COR). The contractor is responsible for offloading, installing, testing, and providing all necessary manuals and warranties, ensuring equipment functions safely and efficiently within the facility’s infrastructure. The contract emphasizes adherence to safety, regulatory, and compliance standards, including OSHA, NFPA-99, and FDA regulations, while also requiring proper waste disposal and coordination for work outside normal business hours. Payment will be processed upon receipt of a proper invoice and successful inspection and acceptance of the equipment. The project involves multiple high-density power distribution units and UPS systems from specified or equivalent brands, with detailed technical specifications to ensure reliable power backup for critical hospital operations. The solicitation is posted with a response deadline of July 14, 2025, and is managed by the Rpo West office, with contact details provided for further inquiries.

General Info

Supply, deliver, install UPS and PDUs for Tulsa VA by September 2025, meeting specs and standards.

Contract Value

$426,827.67

NAICS

335999 - All Other Miscellaneous Electrical Equipment and Component Manufacturing

Place of Performance

Tulsa, OK, 74127, USA

Set-Aside

NONE

Award Issued Date

Documents

1

Solicitation 36C24W25Q0238 - UPS | Tulsa OK VAMC 623

PDF, High priority: read this firstrfq
High

AI Contract Breakdown

Uniform Contract Format

Contract not broken down yet

CLEATUS splits the solicitation into Uniform Contract Format (UCF) sections: scope, pricing, deliverables, and evaluation criteria.

Timeline

PhaseAwarded
Posted

Solicitation

Awarded

Contract was awarded

Submission Closed

Find active opportunities like this

Get full access to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → Rpo West (36C24W)
Contacts1 person available
OfficeMCCLELLAN, CA, 95652, USA
Office AddressMCCLELLAN, CA, 95652, USA

Full Description

Show more
STATEMENT OF WORK (SOW) Eastern Oklahoma VA Health Care System Uninterruptible Power Supplies At the new Tulsa VA Medical Center GENERAL PURPOSE / OBJECTIVE: Eastern Oklahoma VA Health Care System (EOVAHCS) requires a contractor to supply IT Uninterruptible Power Supplies and Power Distribution Units to support Server Racks in the Entrance Rooms (2), Data Center, and Telecommunication Rooms (12) to establish the communication infrastructure at the Tulsa VA Medical Center. The contractor will be required to supply uninterruptible power supplies and power distribution units in accordance with this statement of work and the Department of Veterans Affairs Office of Information and Technology, Infrastructure Standard for Telecommunications Spaces (ISTS), Version 4.0 in a cost-effective, efficient, and safe manner, while in accordance with the VA Mission. BACKGROUND: A facility in Tulsa, Oklahoma, is being renovated to be used as the new Tulsa VA Medical Center (VAMC) in September 2025. The facility will need uninterruptible power supplies for critical electrical loads delivered between September 4th and September 12th of 2025. The facility is currently under the control of VHiT, and the construction contractor is remodeling it. Delivery will not be allowed prior to the VA receiving the building. LOCATION: The new Tulsa VA Medical Center will be located at 440 S. Houston Ave, Tulsa, Oklahoma 74127. PERFORMANCE PERIOD/DELIVERY TIMES: The VA requires delivery of the equipment between September 4th and September 12th, 2025. After the award delivery times will be coordinated with the COR. The Contractor shall furnish all equipment, user manuals, and maintenance manuals for the specified equipment under this contract. SCOPE: EOVAHCS requires a contractor to provide equipment that meets or exceeds the physical, functional, and performance of the listed salient characteristics in the following sections. The equipment features are essential to the technical requirements to meet the department's needs and account for retrofitting an existing structure. For each rack in the server room 2 power distribution. SALIENT CHARACTERISTICS The contractor is required to provide the following products, Brand Name or Equal, at the location outlined in this SOW. Item # Description/Part Number* Qty 1 Power Supply, Uninterruptable, Rack Mounted 55 2 Power Distribution Unit, Data Center, Vertical 40 3 Power Distribution Unit, TR, Vertical 104 4 Back UPS 1500 Compact Tower 4 5 CyberPower M1100XL 5 Equipment: 55 Each Xtreme Power Conversion Rack Mounted UPS Brand Name or Equal Suitable Models: Xtreme Power Conversion M90C-2s Modular Online Three-Phase UPS w/ rail kit, L21-20P line cord and, and optional receptacle panel configured with L21-20R Chatsworth Lead Acid online UPS, 5kVA - 8kVA, 3-Phase Vertiv Liebert ITA2, Three Phase UPS with VRLA Battery Provide components from a single manufacturer. Description: 5kW three-phase 208V 20A rack-mounted UPS with L21-20 input and output connections. Input Connection: Single input NEMA L21-20P plug (twist lock three-phase five wire L+L+L+N+G). Power cord minimum 3 (1m) length. (twist-lock three-phase five-wire L+L+L+N+G). Power cord 10 (3m) length. (twist-lock three-phase five-wire L+L+L+N+G). Power cord 10 (3m) length. (twist-lock three-phase five-wire L+L+L+N+G). Power cord 10 (3m) length. (twist-lock three-phase five-wire L+L+L+N+G). Power cord 10 (3m) length. (twist-lock three-phase five-wire L+L+L+N+G). Power cord 10 (3m) length. Output Connection: Single output NEMA L21-20R receptacle. Power Capacity: 5kW Enclosure: Fully self-contained. Mounting: 19 rack mount. Battery Capacity: Ten minutes at 70% load (3.5kW). Cooling: Fan-cooled, front air entry, rear exhaust. Monitoring: RJ45 Ethernet port allows connection to an external monitoring system. Supports SNMP v3 with SSL Encryption. 40 Each Chatsworth EA-3017-CE Monitored eConnect Data Center Vertical PDU Brand Name or Equal Provide components from a single manufacturer. Description: Metered/monitored three-phase 208V 20A vertical Rack Power Distribution Unit (Rack PDU), 5.7kW, with IEC60320 outlets. Input Connection: Single input NEMA L21-20P plug (twistlock three-phase five wire L+L+L+N+G). Power cord 10 (3m) length. Output Connections. For Computer Room applications: Minimum 30 each C13 and 6 each C19. Outlets are grouped in phase-grouping banks (A-B, B-C, C-A) or alternating to assist with phase balancing. Outlets labeled with the associated phase-grouping bank. Outlets lock to standard power cords and are capable of accepting Z-lock power cords. For Telecommunications Room (TR) and entrance room applications: Minimum 30 each C13, 6 each C19, 2 each NEMA 5-15/20 or L5-20. Outlets are grouped in phase-grouping banks (A-B, B-C, C-A) or alternating to assist with phase balancing. Outlets labeled with the associated phase-grouping bank. Outlets are compatible with Z-lock power cords. Power Capacity: 5.7kW rated. Enclosure: Fully self-contained. Mounting: Toolless mounting, orientation vertical at the rear of the enclosure, taking up zero RU spaces. Up to two Rack PDUs must be able to be installed on each side for high-density (10kW) enclosures. Mounting Hardware: As required to connect to the specific enclosure make/model. Number of RPDUs: 2 for Standard Density (up to 5kW) enclosures, 4 for High Density (10kW) enclosures. Control Module: Field-replaceable, modular control module with metering and monitoring capabilities. For Computer Room applications: A minimum of 12 control modules shall be able to be daisy-chained together to a single IP address output for network monitoring of all metered and monitored data. Metering: Local display provides input line currents (Amperage). Additional metering items (voltage, power, energy, power factor) across the unit or at individual outlets, are acceptable. Monitoring: RJ45 Ethernet port allows connection to an external monitoring system. Supports SNMP v3 with SSL Encryption. 104 Each APC, AP8861 Telecommunication Room Vertical PDU Brand Name or Equal Provide components from a single manufacturer. Description: Metered/monitored three-phase 208V 20A vertical Rack Power Distribution Unit (Rack PDU), 5.7kW, with IEC60320 outlets. Input Connection: Single input NEMA L21-20P plug (twistlock three-phase five wire L+L+L+N+G). Power cord 10 (3m) length. Output Connections. For Telecommunications Room (TR) and entrance room applications: Minimum 30 each C13, 6 each C19, 2 each NEMA 5-15/20 or L5-20. Outlets are grouped in phase-grouping banks (A-B, B-C, C-A) or alternating to assist with phase balancing. Outlets labeled with the associated phase-grouping bank. Outlets are capable of accepting Z-lock power cords. Power Capacity: 5.7kW rated. Enclosure: Fully self-contained. Mounting: Toolless mounting, orientation vertical at the rear of the enclosure, taking up zero RU spaces. Up to two Rack PDUs must be able to be installed on each side for high-density (10kW) enclosures. Mounting Hardware: As required to connect to the specific enclosure make/model. Number of RPDUs: 2 for Standard Density (up to 5kW) enclosures, 4 for High Density (10kW) enclosures. Control Module: Field-replaceable, modular control module with metering and monitoring capabilities. For Computer Room applications: A minimum of 12 control modules shall be able to be daisy-chained together to a single IP address output for network monitoring of all metered and monitored data. Metering: Local display provides input line currents (Amperage). Additional metering items (voltage, power, energy, power factor) across the unit or at individual outlets, is acceptable. Monitoring: RJ45 Ethernet port allows connection to an external monitoring system. Supports SNMP v3 with SSL Encryption. 4 Each APC, BX1500M Back UPS 1500 Compact Tower Brand Name or Equal Main Input Voltage 120V Main Output Voltages 120V Power Rating: 1500VA/ 900W Form Factor Standalone Battery back-up & Surge protection Battery life 3-5 years Lead-Acid battery Input connection type NEMA 5-15P Output connection type NEMA 10 5-15R 5 Each CyberPower, M1100XL Medical Grade UPS System 1100VA/880W AVR Tower Brand Name or Equal Horizontal cable management unit for a 19" rack with a channel approximately 2"x3". Provides for a professional finish to hide cables in a switch rack. Color: White to match rack Single-Sided; 2U x 19" EIA x 8.2"D (208 mm) QUALITY Conformance Standards Refer to the section on Safety and Compliance in this SOW. Rework Rework or Remedy is defined as performing the Service again until the Purpose of this SOW is achieved in full. This involves less than Satisfactory Service by the Contractor as noted by the COR. Rework or Remedy occurs at no additional cost to the Government. Payment will be withheld until all services are performed to the Satisfactory level in accordance with this SOW and as documented by the COR. Inspection and Acceptance of Products and Services: The Government reserves the right to inspect and test services in accordance with this SOW and the Contract. The only individual authorized to officially accept services is the COR. While inspection of services may be delegated by the COR and a shared responsibility with departmental management staff, the COR is ultimately the only authorized individual to approve and accept services on behalf of the VA. PERFORMANCE PERIOD AND DELIVERY: All items to be delivered after receipt of purchase order starting on or around September 4th through September 12th. Delivery and receipt of the proposed items are anticipated to be directed to the location identified below. Confirmation of delivery location will be provided by the VA COR post-award. Delivery must be coordinated with VA COR before any delivery attempts. Any item that has not been coordinated will be turned away and any additional charges will be the responsibility of the sender/transportation company. Contractor`s responsibility will include offloading the equipment from the truck, moving the equipment to the correct delivery location in the space, uncrating or unboxing the equipment, removing all trash, and setting up the equipment according to the manufacturer`s specifications, followed by testing the equipment to verify that it is operational. Equipment paperwork & warranty information must be handed to the approved government contact onsite. VA STANDARD BUSINESS HOURS AND FEDERAL HOLIDAYS Hours: Normal duty hours are 8:00 a.m. through 4:00 p.m. for the VA, Monday through Friday, not including federal holidays. Whenever contact with a facility is required outside of normal duty hours, the Contractor shall coordinate these times with the designated COR. New Year's Day January 1st Martin Luther King's Birthday Third Monday in January President's Day Last Monday in February Memorial Day Last Monday in May Juneteenth June 19th Independence Day July 4th Labor Day First Monday in September Columbus Day Second Monday in October Veteran's Day November 11th Thanksgiving Day Fourth Thursday in November Christmas Day December 25th In addition to the days designated as holidays, the Government observes the following days: Any other day designated by Federal Statute Any other day designated by Executive Order Any other day designated by the President of the United States to be a Federal holiday Noncontract Charges: The contractor shall not perform any service that will result in additional charges without prior approval from the Contracting Officer. Payment: Payment will be made upon receipt of a properly prepared invoice, which references the period for which payment is due, the contract number, and/or assigned purchase order number. The invoice must include the correct payment address. Waste Removal: The contractor is responsible for removing and properly disposing of all waste related to the services provided on-site at all VA facilities. SAFETY AND COMPLIANCE The Contractor must perform services and ensure equipment functions in accordance with: local, state, and federal Occupational Safety and Health guidelines and legislation, including Occupational Safety and Health Administration (OSHA), the American National Standards Institute (ANSI) safety guidelines. local, state, and federal Fire and Safety legislation and guidelines, to include VA Health Care System directives and legislation on Fire and Safety, as well as the latest published edition of NFPA-99 (Health Care Facilities Code) REGULATORY REQUIREMENTS: Food and Drug Administration (FDA) Quality System Regulation as stated in 21 CFR Part 820 Occupational Safety and Health Administration (OSHA) Medical Center Policies Each VA Medical Center has policies that are updated from time to time. The COR can provide more detailed information to the contractor of these upon commencement of the contract and throughout the term of the contract, as needed, especially policies regarding, parking, possession of weapons, cell phone use and photography as well as smoking on VA property. Violations of such policies may result in individual fines or citations answerable in the United States (Federal) District Court.

More opportunities from Department Of Veterans Affairs → Rpo West (36C24W)

Same awarding agency

NAICS: 531120
New
Federal
Ponce Vet Center - Relocation
Solicitation # 36C24426R0012
The Department of Veterans Affairs, through the Rpo West office, is soliciting proposals for a fully serviced lease to relocate the Ponce Vet Center in Ponce, Puerto Rico. The requirement is for approximately 4,028 NUSF (4,833 ABOA / 5,438 RSF) of ADA-compliant space. The proposed lease term is 20 years, consisting of a 5-year firm period and a 15-year soft period, with the government maintaining termination rights after the firm term upon 180 days' notice. This is a total small business set-aside under NAICS code 531120. The facility must meet Facility Security Level II standards, including specific access controls and high-security locks, and must comply with seismic standards and NFPA fire and life safety codes. Key requirements include 30 on-site parking spaces, a professional sound masking system in lobbies and group rooms, and specific interior finishes and signage. Award will be based on a best value tradeoff process where technical factors—specifically the facility design, site, past performance, and experience—are significantly more important than price. Offerors must provide a detailed experience narrative limited to five relevant projects and submit past performance questionnaires directly to the Lease Contracting Officer. Proposals must include representations regarding foreign ownership for high-security space and compliance with prohibitions on certain telecommunications and video surveillance equipment. Construction activities associated with the lease are subject to Puerto Rico building construction prevailing wage determinations.
Lessors of Nonresidential Buildings (except Miniwarehouses)

POSTED

about 18 hours ago

DEADLINE

in 18 days
View Details
NAICS: 339112
New
Federal
ScriptPro - Pharmacy Workstations: Kiosk and Med Dispensing Unit
Solicitation # 36C24W27Q0012
The Department of Veterans Affairs Veterans Health Administration is conducting market research via a Sources Sought notice for the procurement of brand name ScriptPro pharmacy workstations, kiosks, and medication dispensing units for the Oakland VA Health Care System in California. This is a Firm Fixed Price requirement intended to identify capable manufacturers or distributors who can provide exact match or functionally equivalent equipment. The scope includes the purchase, delivery, assembly, and installation of three pharmacy workstations, three Zebra ZD621-2P printers, three Rx paperwork printers, one pharmacy patient kiosk, one Eyecon Model 9430, and specific pharmacy server software. To ensure compatibility with existing systems, the requirement is designated as brand name only, though equal products may be considered if they meet all salient physical and functional characteristics. The government strictly prohibits gray market items, requiring vendors to be OEMs or authorized dealers/distributors with valid authorization letters. Contractors must adhere to rigorous security standards, including FIPS 140-2 and NIST 800-52 compliance, and utilize VA-authorized technical security baseline configurations. Deliveries must be coordinated with 24-hour advanced notice and may involve working within active construction sites, requiring compliance with safety protocols such as the use of hard hats and safety vests. Performance will occur during normal business hours at the Oakland VA Clinic, and the contractor is responsible for all tools, labor, and materials necessary for a complete installation. This notice is for planning and size determination purposes only and does not constitute a formal solicitation or binding contract.
Surgical and Medical Instrument Manufacturing

POSTED

about 18 hours ago

DEADLINE

in 5 days
View Details

Earlier notices in this NAICS code

Posted before this notice, open and closed

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS