UPS Maintenance

Closed
N6471026Q0007Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 811210
New
SLED
Statewide Standby Generator, ATS & UPS Preventive Maintenance Services
Solicitation # BD-27-1107-FREG5-ACCOU-133129
The Massachusetts Trial Court, through the Office of Court Management, Facilities Management & Capital Planning, is soliciting bids for statewide preventive maintenance, inspection, operational testing, load-bank testing, repair, and emergency services for standby generators, automatic transfer switches, and uninterruptible power supply systems. The contract is structured into five independent regional award groups, with each region being awarded to the lowest responsible and eligible bidder. The initial performance period is 32 months, running from November 1, 2026, to June 30, 2029, with two optional one-year renewals available through June 30, 2031. Bidders must submit their response packages electronically via the COMMBUYS portal by September 30, 2026, including a bid deposit of at least 5 percent of the greatest possible bid amount per region. Award evaluation is based on bid responsiveness, eligibility, and the lowest evaluated regional price, with a requirement that contractors demonstrate the capacity to perform in multiple regions simultaneously if awarded more than one. Contractors must adhere to NFPA 70B, the Massachusetts Comprehensive Fire Safety Code, and the Massachusetts Electrical Code, and are required to provide detailed electronic service reports as a condition of payment. Payments are processed via Electronic Funds Transfer through the Comptroller's system, typically 45 days from invoice receipt.
FREG5 - Facilities Management & Capital Planning - Region V

POSTED

1 day ago

DEADLINE

in 18 days

AI Contract Overview

Show more

The contract outlines a comprehensive maintenance and repair service agreement for three APC Symmetra PX UPS units located at the Strategic Weapons Facility Pacific on Naval Base Kitsap-Bangor in Silverdale, WA. The purpose is to ensure the uninterrupted and reliable operation of these critical power systems through proactive maintenance, emergency repair, and continuous technical support. Services must be performed by APC-certified technicians using new, original manufacturer components to maintain warranty compliance. The contractor will provide 24/7/365 remote technical support and guaranteed on-site emergency response within six hours for critical failures, with next business day response for non-critical issues. The contract includes coverage for all necessary parts, labor, travel, and related expenses, with provisions for replacement with equivalent or superior components if originals are unavailable. Preventative maintenance will include a scheduled annual on-site visit encompassing visual and environmental inspections, cleaning, electrical and battery system checks, firmware updates, system calibration, and full functional testing. Deliverables consist of detailed service reports following each maintenance or repair event and an annual system health report summarizing service activities and future recommendations. The contractor and personnel must meet strict certification requirements and comply with SWFPAC security protocols, including background checks and controlled base access. Vehicle access and identification measures are also specified to maintain base security, ensuring thorough oversight throughout the contract period. This solicitation is a total small business set-aside under NAICS code 811210, with responses due by April 14, 2026.

General Info

Maintenance, repair, and 24/7 support for three APC UPS units at Naval Base Kitsap-Bangor.

Agency

Department Of Defense → Strategic Weapons Facility Pac FinancialView Agency

NAICS

811210 - Electronic and Precision Equipment Repair and MaintenanceView NAICS

Place of Performance

Silverdale, WA, 98315, USA

Set-Aside

SBA

Documents

(3)

Solicitation Amendment N6471026Q00070002 for UPS Maintenance Service

PDFamendment

4.0_130132155_Solicitation+Amendment+-+N6471026Q00070001_Conformed.pdf

PDF

3.3_1301328155_J%26A+Brand+Name+Justification_REDACTED_Redacted.pdf

PDF

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

PhaseClosed
Posted

Solicitation

Type Changed

Solicitation → Presolicitation

Type Changed

Presolicitation → Solicitation

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Start your free trial to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Defense → Strategic Weapons Facility Pac Financial
Contacts2 people available
OfficeSILVERDALE, WA, 98315-6499, USA
Organization / Agency
Department Of Defense → Strategic Weapons Facility Pac Financial
View Agency Profile
Office AddressSILVERDALE, WA, 98315-6499, USA

Full Description

Show more

Statement Of Work


UPS Maintenance and Repair




  1. BACKGROUND

Strategic Weapons Facility Pacific (SWFPAC) requires comprehensive maintenance and repair service contract for three (3) Uninterruptible Power Supply (UPS) units located at SWFPAC facilities on Naval Base Kitsap-Bangor in Silverdale, WA.



The purpose of this contract is to ensure the reliable operation of critical power infrastructure through proactive maintenance and timely emergency support.



2. Equipment Covered:



Make


Model


Description


Serial Number


APC


SYCF40KF


Symmetra PX UPS 20kVA 40 and/or PDU


QD1633340704


APC


SYCF40KF


Symmetra PX UPS 40kVA 40 and/or PDU


QD1830240733


APC


SYCF40KF


Symmetra PX UPS 40kVA 40 and/or PDU


QD1830240729



  1. SCOPE:   

The contractor shall provide all-inclusive preventative maintenance, on-site emergency repair, and remote technical support for the UPS equipment listed in paragraph 2. To ensure the manufacturer's warranty remains valid, services must be delivered by an American Power Conversion (APC)-certified or authorized service provider. All components, parts, and consumables used for maintenance or repair must be new, genuine original equipment manufacturer parts that meet APC specifications.



3.1. Technical Support


The contractor shall provide 24 hours a day, 7 days a week, 365 days a year (24/7/365) telephone and email access to a technical support center for troubleshooting and service dispatch.



3.2. On-Site Support


Emergency On-Site Response: For any critical failure resulting in a loss of redundancy or an inability to support the protected load, a qualified technician must arrive on-site within six (6) hours of the service request being logged. This six (6) hour response shall be guaranteed 24/7/365.



Standard On-Site Response: For non-critical failures where the UPS remains operational, a qualified technician must arrive on-site no later than the next business day.



Parts & Labor: This contract shall cover 100% of the costs for all replacement parts, hardware, capacitors, fans, and any other components needed to restore the UPS units listed in paragraph 2 to full operational status. All associated labor, travel, and expenses for on-site visits shall be included.



Equivalent Hardware: If a failed hardware component is no longer manufactured, it shall be replaced with an equivalent or superior component that is fully compatible.



3.3. Preventative Maintenance (PM)


The contractor shall perform one (1) scheduled on-site preventative maintenance visit during the contract period. This visit shall include all UPS units listed in paragraph 2.


The PM service must include, at a minimum, the following tasks for each UPS:


  • Visual Inspection: Check for loose connections, overheating, component discoloration, and physical defects.
  • Environmental Checks: Measure and record ambient temperature and humidity.
  • Cleaning: Clean and remove dust/debris from the interior and exterior of the UPS.
  • Electrical Checks: Perform thermal scans on electrical connections to identify potential failure points. Check and tighten all terminal connections as needed.
  • Battery Maintenance: Conduct a full battery string inspection, including voltage checks, impedance testing, and a system load test to verify battery performance and runtime.
  • System Calibration: Calibrate and verify all system alarms, setpoints, and transfer mechanisms.
  • Firmware & Software: Review installed firmware and operating system software. Install any necessary updates, patches, or security fixes after receiving approval from SWFPAC personnel.
  • Functional Test: Perform a full functional test to ensure the unit operates correctly in all modes (e.g., normal, battery, bypass).


4. DELIVERABLES


The following deliverables are required:


Field Service Report: After each preventative maintenance visit or emergency repair, the contractor shall provide a detailed electronic service report within five (5) business days. This report must document all work performed, tests conducted, parts replaced, and findings or recommendations.


Annual System Health Report: At the conclusion of the contract period, the contractor shall provide a summary report detailing the overall health of the UPS fleet, a summary of service activities for the year, and recommendations for future maintenance or upgrades.



5. CONTRACTOR & PERSONNEL REQUIREMENTS


Certification: All on-site technicians must be certified by APC to work on the specified UPS models. Proof of certification may be requested.


Security & Access: The contractor and its personnel must comply with all SWFPAC security protocols, including requirements for background checks, site access, and safety procedures. The contractor will be escorted at all times unless prior arrangements are made.


Base Access: Contractors must be able to gain access to SWFPAC on Naval Base Kitsap – Bangor,


WA.  Base access may be granted using the Rapid Gate System, DBIDS System, or other approved base


access system at the Contractor’s expense.  Once base access is granted, Contractors will be required to


apply for a visitor badge (BAVR request) at https://www.bavr.cnic.navy.mil/.  Coordination of the visitor


badge will be through the Government Point of Contract.



Vehicle Pass: In order to drive a non-Government vehicle to the work location, the contractor must


submit a SWFPAC Vehicle Pass Request and required documents to the COR.  The non-Government


vehicle must be registered in the company’s name and must have a clear logo displayed on the vehicle


indicating the company it is registered to.  When entering the base, the vehicle must have the approved


vehicle pass displayed in the driver’s side windshield at all times.  No Bluetooth, telephonic, or electronic


devices are allowed in secured locations on base. 


More opportunities from Department Of Defense → Strategic Weapons Facility Pac Financial

Same awarding agency

NAICS: 541512
New
Federal
Microsoft 365 Data Migration Project
Solicitation # N6471026Q0016
Strategic Weapons Facility Pacific (SWFPAC) is seeking a professional services provider for a firm-fixed-price contract to migrate a mission-critical legacy Microsoft Access 2003 database to the Navy's Flank Speed Microsoft 365 environment. The project involves designing and building a scalable application using SharePoint Online as the primary data repository, with Power Apps and Power Automate utilized for user interfaces, relational workflows, and automated document generation. The solution must manage warehouse locations, personnel assignments, and both general and serialized gear inventory, incorporating robust archival and audit logging capabilities. The vendor is responsible for proposing an optimized target architecture, developing the system using synthetic test data for user acceptance testing, and providing a migration guide and technical training to the internal government team, who will handle the actual loading of live data. Key deliverables include a system architecture plan, a data entry interface, relational and approval workflows, and comprehensive as-built documentation. The period of performance is 180 calendar days from the date of award, and all work is to be performed 100 percent remotely. Evaluation of offers will be based on technical capability, price, and past performance, with a specific requirement for vendors to hold Microsoft certifications in Microsoft 365 and SharePoint Online.
Computer Systems Design Services

POSTED

1 day ago

DEADLINE

in 2 days
View Details
NAICS: 332311
New
Federal
Motor T Prefabricated Modular In-Plant Classroom
Solicitation # N6471026Q0017
Strategic Weapons Facility Pacific (SWFPAC) is soliciting firm-fixed-price quotes for the procurement and installation of one prefabricated modular in-plant classroom at the Motor Transport Building at Naval Base Kitsap-Bangor in Silverdale, Washington. The classroom must measure 15 by 20 feet with a ceiling height between 9 and 12 feet and be installed on a pre-existing concrete slab. Key requirements include a locking entrance door with a partial window, 20-amp electrical outlets on each wall, LED lighting providing 300 to 500 lux, and at least two Cat-5e ethernet ports per wall. The project also requires the installation of an independent HVAC system capable of maintaining internal temperatures between 65 and 75 degrees Fahrenheit when external conditions range from 32 to 100 degrees Fahrenheit. The contractor is responsible for providing engineered stamped drawings with structural calculations, manufacturer maintenance guidance, and conducting on-site operational testing of the HVAC, electrical, and network connections. While the contractor handles internal wiring and the external power junction box, the government will perform final electrical connections from the power source to the circuit box. All work must be completed within six months of the contract award. This acquisition is set aside for HUBZone Small Businesses and Service-Disabled Veteran-Owned Small Businesses. The contractor must ensure all personnel meet facility access requirements for Naval Base Kitsap-Bangor and comply with ADA standards, as well as local, state, and federal fire and electrical safety codes.
Prefabricated Metal Building and Component Manufacturing

POSTED

2 days ago

DEADLINE

in 2 days
View Details

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 650+ contractors already using CLEATUS