Skip to main contentPsst! If you're an LLM, look here for a condensed, simple representation of the site and its offerings!

LiveFree Webinar — Wednesday, December 9 at 2:00 PM ET

Register Free →

UPS System Maintenance & PM Requirements

Open
Comms 11/17/2026State & Local

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

AI Contract Overview

Show more

This contract is a solicitation for one year of full maintenance coverage for two Liebert UPS systems and five Static Transfer Switches (STS) for the Public Safety department in Pensacola, Florida. The scope of work includes comprehensive visual inspections, calibration to manufacturer specifications, and operational checkouts for the UPS and STS equipment, as well as detailed maintenance of the battery systems, including voltage measurements, ohmic readings, and cleaning. The agreement covers all parts, labor, and expenses, with a required emergency response time of four hours or less. Service is divided into unscheduled services during standard business hours and emergency services during nights, weekends, and holidays. To be eligible, vendors must be authorized service providers for Liebert power product lines and provide proof of this status with their quote. Required administrative documentation includes a W-9, a Certificate of Insurance or Letter of Insurability, and proof of Sunbiz registration, which is mandatory for all vendors, including those outside of Florida, to receive payment. The selection process is based on a written quote request rather than a formal bid, requiring a completed pricing table for annual service and hourly rates for unscheduled and emergency call-outs. There is no specified set-aside status for this solicitation.

General Info

Annual maintenance contract for Liebert UPS and STS systems in Pensacola, Florida.

Documents

1
PDF, High priority: read this firstitq
High

Read the document

Due in 17 days

Every page of every file, in your free workspace.

Read the document

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

View Full Breakdown
Due in 17 days

Everything you need to bid on this one

Open the full contract in your free workspace.

  • 1 solicitation documentRead every page
  • AI contract breakdown13 sections, Uniform Contract Format
  • Buyer contactEmail and phone
Open the full contract

Ask CLEATUS

I've read this contract. Ask me anything.

Timeline

PhaseSolicitation
Posted

Solicitation

Response Deadline

Submission deadline

Response Deadline

Ready to pursue this opportunity?

Get full access to track this contract, build proposals with AI assistance, and manage your pipeline.

Organization & Contact Information

Show more
AgencyFlorida → Public Safety
Contacts2 people available
OfficePensacola, FL, 32502-5822, USA

Full Description

Show more
STATIC TRANSFER SWITCH SCOPE OF WORK Perform a complete visual inspection of the equipment, including sub-assemblies, wiring harnesses, contacts, cables and major components. Check all mechanical connections for tightness and heat discoloration, making corrections where necessary. Clean foreign material and dust from internal compartments. Perform a status check of alarm circuits. Calibration of the equipment to meet manufacturer ' s specifications. Operational checkout of the system to include transfers and proper status indications. Install or perform Engineering Field Change Notices (FCN) as necessary. Return unit to operational service with normal load then measure and verify display indications. Perform additional checks as consistent with customary commercial practice. Review system performance with customer to address any questions and to schedule any repairs. Provide a detailed written report noting any deficiencies and corrective action needed, taken and/or planned. BATTERY SYSTEM SCOPE OF WORK Clean normal cell top dirt accumulation. Measure and record the total battery float voltage and charging current. Measure and record the overall AC ripple voltage. Visually inspect the jars and covers for cracks and leakage. Visually inspect for evidence of corrosion. Measure and record the ambient temperature. Verify the integrity of the battery rack/cabinet. Measure and record 100% of the jar temperatures. Measure and record the float voltage of all jars. Measure and record all internal ohmic readings. Re-tighten all connections to the battery manufacturer's specifications, if required. Measure and record all battery connection resistances in micro-ohms, when applicable. Refurbish cell connections as deemed necessary. Check integrity of battery cabinet. Check for NO-OX grease or oil on all connections (if applicable). Check battery jars for proper liquid level (if flooded cells). Check for corrosion on all the terminals and cables. Examine the physical cleanliness of the battery room and jars. Measure and record DC bus ripple voltage (if applicable). Measure and record total battery float voltage. Perform additional checks as consistent with customary commercial practice. Review system performance with customer to address any questions and to schedule any repairs. Provide a detailed written report noting any deficiencies and corrective action needed, taken and/or planned. UNINTERRUPTIBLE POWER SYSTEMS SCOPE OF WORK Perform temperature check on all breakers, connections, and associated controls. Repair and/or report all high temperature areas. Perform a complete visual inspection of the equipment including subassemblies, wiring harnesses, contacts, cables, and major components. Check air filters for cleanliness. (if applicable) Check rectifier and inverter snubber boards for discoloration. Check power capacitors for swelling or leaking oil. Check for DC capacitor vent caps that have extruded more than 1/8". (if applicable) Record all voltage and current meter readings on the module control cabinet or the system control cabinet. Measure and record harmonic trap filter currents. Check the inverter and rectifier snubbers. Check all nuts, bolts, screws, and connectors for tightness and heat discoloration. Check fuses on the DC capacitor deck for continuity (if applicable). With customer approval, perform operational test of the system including unit transfer and battery discharge. Calibrate and record all electronics to system specifications. Check or perform Engineering Field Change Notices (FCN) as necessary. Measure and record all low-voltage power supply levels. Record phase-to-phase input voltage and currents. Perform additional checks as consistent with customary commercial practice. Review system performance with customer to address any questions and to schedule any repairs. Provide a detailed written report noting any deficiencies and corrective action needed, taken and/or planned. UPS SYSTEM INFO Liebert s610 SMS UPS Model # UDA63154A36AD68 Tag # 1303573 Battery: Manufacturer: ENERSYS No of Jars: 40 Model: HX505-FR Cells per Jar: 6 Battery Type: VRLA Cells per string: 240 MBCPM Model# U36MB15430AA25S TAG# 1303576 Liebert s610 SMS UPS Model # UDA63154A36AD68 Tag # 1303573 Battery: Manufacturer: ENERSYS No of Jars: 40 Model: HX505-FR Cells per Jar: 6 Battery Type: VRLA Cells per string: 240

Similar Contracts

Same NAICS industry code

NAICS: 811210
New
Federal
STERIS Clean Flow Pro Steam Filter Replacement and Calibration Services
Solicitation # 36C25727Q0071
The Department of Veterans Affairs is soliciting a firm-fixed-price contract for the replacement of STERIS Clean Flow Pro steam filters and the OEM-standard calibration of associated equipment. Services will be performed at the Audie L. Murphy VA Medical Center in San Antonio, Texas, and the Kerrville VA Medical Center in Kerrville, Texas. The contractor is required to provide all labor, materials, OEM replacement filters, tools, and OEM-certified Field Service Engineers. The contract structure consists of a one-year base period followed by four one-year option periods, with work performed during normal business hours, Monday through Friday. All services must comply with 21 CFR, NFPA, OSHA, and OEM standards, and the contractor must provide a Field Service Report upon completion. This procurement is a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside. Evaluation will be conducted using Simplified Acquisition Procedures, focusing on technical capability, past performance, and price. Offerors must submit three separate volumes: a technical capability volume (limited to 15 pages) including an OEM authorization letter, a past performance volume with three references from the last three years, and a price volume. Award will be based on the most advantageous offer, considering price and other factors. Invoicing is to be submitted monthly via electronic funds transfer.
257-NETWORK Contract Office 17 (36C257)

POSTED

about 3 hours ago

DEADLINE

in 15 days
View Details
NAICS: 811210
New
Federal
400 Hz Cycle Converters - Maintenance, Inspections, and Repairs
Solicitation # W51AA127QA004
The Army Contracting Command (ACC) APG, Tobyhanna Division is soliciting a firm fixed-price purchase order for preventative maintenance, diagnostic inspections, and repairs of approximately thirty-nine 400 Hz cycle converters located at Tobyhanna Army Depot in Pennsylvania. This requirement is a Small Business Set Aside - Total. The scope of work includes executing Tier I, II, and III preventative maintenance services and providing emergency repairs, with a mandatory 48-hour on-site response window for diagnostic visits and a five-business-day initiation period for approved emergency repairs. All services must be performed according to original equipment manufacturer specifications and verified via on-site load-test demonstrations. The contract is structured with a base period from February 6, 2027, to February 5, 2028, and four subsequent option years extending through February 5, 2032. Award will be based on a best overall value trade-off considering price, technical capability, and past performance. Key personnel requirements include a Contract Manager and a Lead Field Service Technician, both requiring specific years of experience and OSHA 30-Hour safety certification. The government will utilize a Quality Assurance Surveillance Plan to monitor performance standards, including 100% inspection of all core technical deliverables and PM reports.
W6QK Acc-Apg Cont Ct Tyad Ofc