Walk-in Refrigerator

Closed
36C24W25Q0218P002Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 333415
New
Federal
4120--SPECIAL Duplex Strainer - MPLS
Solicitation # 36C26327Q0054
Solicitation 36C26327Q0054 is an accelerated request for quotes issued by the Department of Veterans Affairs Network Contracting Office 23 for the supply and delivery of a brand name or equal Keckley duplex strainer and gasket for the Minneapolis VA Health Care System. This is a small business set-aside conducted under FAR Part 12 for commercial products, utilizing NAICS code 333415. The government intends to award one firm fixed price contract for one 20 inch Keckley Basket Strainer 150 RF Duplex assembly and one O-ring gasket. All items must be new and unused, featuring a modular design with sections not exceeding 2,000 pounds, carbon steel shell construction, and a one year warranty covering defects in materials and workmanship. The period of performance is from November 9, 2026, to March 15, 2027, with all deliverables due at the Minneapolis facility by the end date. Delivery is required FOB Destination, and the contract price must include all equipment, accessories, and shipping charges. Prospective offerors must be registered in the System for Award Management and the SBA Small Business Search database. Quotes must be submitted via email to the contract specialist by 10:00 AM on October 30, 2026. Submissions must include a Buy American Certificate of Origin and details regarding the manufacturer's socioeconomic category.
Network Contract Office 23 (36C263)

POSTED

1 day ago

DEADLINE

in 9 days
NAICS: 333415
New
DIBBS
COOLING COIL, AIR, DUCT
Solicitation # SPE7M0-27-T-0178
Solicitation SPE7M0-27-T-0178 is issued by the DLA Weapons Support Maritime Supply Chain ESOC Buys for the procurement of one duct type air cooling coil, identified by NSN 4130011916131 and part number 19-80-2979M. The requirement is classified under NAICS code 333415 and is set aside for small businesses, with a specific price evaluation preference for HUBZone concerns. The original required delivery date is October 1, 2026, with a delivery window of five days after receipt of order. Delivery is FOB Origin, and both inspection and acceptance will occur at the destination, specifically the Puget Sound Naval Shipyard IMF in Bremerton, Washington. The contract mandates strict adherence to technical and quality requirements via the DLA Master List and specifies packaging and marking standards according to MIL-STD-2073-1E and MIL-STD-129. Special restrictions are in place regarding the use of mercury and the removal of government identification from non-accepted supplies. Administrative requirements include electronic invoicing through the Wide Area WorkFlow system and submission of all quotes via the DLA Internet Bid Board System by October 19, 2026. Key regulatory clauses apply, including the Buy American and Balance of Payments Program, NIST SP 800-171 assessment requirements, and safeguarding of covered defense information.
DLA WEAPONS SUPPORT MARITIME SUPPLY CHAIN ESOC BUYS

POSTED

2 days ago

DEADLINE

in 1 day
NAICS: 333415
New
DIBBS
COOLING COIL, AIR, DUCT
Solicitation # SPE7M0-27-T-0185
Solicitation SPE7M0-27-T-0185 is a request for quotations issued by the DLA Weapons Support Maritime Supply Chain ESOC Buys for the procurement of one duct type air cooling coil, identified by NSN 4130-01-257-9076. The requirement specifies part number 19-80-2612M1, associated with Edge Electronics Corporation and Electric Boat Corporation. Delivery is required within five days after order, with an original required delivery date of October 1, 2026. The item is to be delivered FOB Origin to the Puget Sound Naval Shipyard IMF in Bremerton, Washington, using the fastest traceable means, specifically prohibiting the use of parcel post. The contract mandates strict adherence to MIL-STD-2073-1E for packaging and MIL-STD-129 for marking, with a general requirement to avoid plastics for wrapping or cushioning. Technical and quality standards are governed by the DLA Master List, though it is noted that no approved Technical Data Package is currently available for this NSN. Material restrictions prohibit the intentional addition of mercury, and the use of additive manufacturing is forbidden unless specifically authorized. Compliance with the Buy American Act, Berry Amendment, and NIST SP 800-171 cybersecurity standards is required. Inspection and acceptance will occur at the destination, and all invoicing must be processed electronically through the Wide Area Workflow system.
DLA WEAPONS SUPPORT MARITIME SUPPLY CHAIN ESOC BUYS

POSTED

2 days ago

DEADLINE

in 1 day

General Info

NAICS

333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing

Place of Performance

Tulsa, OK, 74127, USA

Set-Aside

SDVOSBC

Documents

1

Amendment 0002 - Walk-in Refrigerator (Tulsa 623)

PDF, High priority: read this firstamendment
High

AI Contract Breakdown

Uniform Contract Format

Contract not broken down yet

CLEATUS splits the solicitation into Uniform Contract Format (UCF) sections: scope, pricing, deliverables, and evaluation criteria.

Timeline

PhaseClosed
Posted

special-notice

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Start your free trial to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → Rpo West (36C24W)
Contacts1 person available
OfficeMCCLELLAN, CA, 95652, USA
Office AddressMCCLELLAN, CA, 95652, USA
Contacts

Full Description

Show more
NOTICE FOR REQUEST FOR QUOTE AMENDMENT SOLICITATION NUMBER: 36C24W05Q0218 AMENDMENT NUMBER: 0002 DATE: August 06, 2025 PROJECT NUMBER: N/A PROJECT TITLE: Walk-in Refrigerator LOCATION: VA Medical Center, Tulsa, OK, 74127 REASON FOR AMENDMENT: Answer Questions 1-38, Response to drawings - additional walk through ______________________________________________________________________AMENDMENT: 0002 Question: 1 - Response to Drawings: ADD #1 RFI #9 response stated that drawings would be made available to pre-bid walk attendees on 7/23. Drawings were not distributed and have still not been made available on 7/28. Please provide drawings as previously noted. VA Response: Please see attachment with Amendment. Question: 2 - Provide Sign-in Sheet and Notes: Please provide pre-bid sign-in sheet and notes from walk on 7/23 VA Response: The Sign-in is for VA Contracting use and vendors are responsible for their own notes. Question: 3 - Condenser Specifications: ADD #1 RFI #2 states condenser is to be installed on top of the cooler. Specification 114121-2.8-B states that the outdoor unit shall include individual dedicated air-cooled condensers. Please clarify. VA Response: The unit is not outdoors; therefore 114121-2.8-B does not apply. Question: 4 - Drawing Provided: Drawings have yet to be provided, and exterior work is required that was not addressed at pre-bid walk. VA Response: Exterior work is not required. Question: 5 - Expect More Questions: Once we receive drawings, we expect to have more questions. VA Response: Acknowledged. Question: 6 - Ceiling Drywall/Drop Ceiling: To accommodate the proposed walk-in box, the ceiling above it would need to be partially removed to allow placement of the condensing units on the roof of the box. This will require coordination with another trade. The top of the box will also need to be sealed against the ceiling to meet installation standards. Will there be any modifications from another trade to address this concern? VA Response: As per the statement of work, the awarded contractor is responsible for all of the work mentioned. Question: 7 - Unit Width Concern: The unit's width also presents a major concern. The measured available space is exactly 9'4", which is also the specified width of the proposed box. With no installation tolerance, this creates a significant challenge for placement and would likely require modification to the existing wall structure. Could the spec for the box size be changed? VA Response: As per the statement of work, - the overall size and layout of the walk-in must be designed to maximize given space. The site condition may be modified to accommodate the refrigerator. All modifications to the site-condition must be coordinated and approved by the COR and chief of engineering. All modifications to the site condition must meet industry standard for the type of product being installed, and final finish must match surrounding finish and meet infection control, safety, engineering and interior designs approval. Question: 8 - Sprinkler System: A sprinkler system is present in the ceiling area and would need to be extended into the box per code. However, the documentation does not specify whether the VA or the contractor is responsible for coordinating with a fire suppression company to complete the final connections. Can you please advise how this concern would be addressed? VA Response: The placement of the sprinkler head is intended to remain above the box. Any modifications to fire suppression will need to be done by certified technicians. It is the awarded vendors responsibility to provide such technicians. Question: 9 - Electrical Services: Electrical service has not been run to the installation site. A licensed electrician will be required to run power and complete the final electrical connections. VA Response: There is a junction box in the ceiling with the needed electrical circuit. If additional circuits are needed, it is the awarded contractor's responsibility to provide them. Question: 10 - Drainage: Drainage may require trenching. There did not appear to be a nearby drain accessible from the location we were shown, and any trenching would need to be performed by a licensed plumber. VA Response: The site is on the second floor; trenching will not be allowed or possible. Per the SOW, - Installation will include all new associated subsystems associated with the function of the units, and connections to building systems including power and data. This includes plumbing and drains. Question: 11 - Ventilation: Given that this is an air-cooled unit and the drop ceiling space appears to be sealed off from the conditioned area below, we have concerns about adequate ventilation and heat rejection. This may negatively impact on the unit's operational efficiency and long-term reliability. VA Response: Per the statement of work, - The contractor will design an airflow solution that allows the cooling unit to function properly and limits disruptions to surrounding airflows and room pressures. Question: 12 - Serviceability: Accessibility and long-term serviceability will be significantly limited due to the confined and fully finished nature of the install area. VA Response: Acknowledged. Question: 13 - Integrating Wal-in Controls: Who would be responsible for integrating the walk-in controls to the buildings system? VA Response: Per SOW, - Installation will include all new associated subsystems associated with the function of the units, and connections to building systems including power and data. The contractor is responsible for all parts and labor for connection to building systems. Coordination will be required with VA Engineering and the COR. Question: 14 - Response Time: If you could please provide answers to our questions and concerns at your earliest convenience, we would greatly appreciate it. VA Response: Please understand all questions are responded to in a timely manner, due to workload and availability. Question: 15 - Walk through: To support our efforts, we would like to request an additional site visit and kindly ask for responses to the following questions to help us develop a more accurate and competitive quote. VA Response: No additional site visits will be given at this time. Question: 16 - Type of Units: Air cooler unit or water-cooled units? VA Response: Water cooled units will not be accepted. Question: 17 - Design Direction: Will the Mechanical Engineer which is over the Veterans affairs building Construction be available to give us directions as far as where the Tie-Ins can be? VA Response: Yes, the awarded contractor is expected to design in collaboration with the COR and VA Engineering. Question: 17 - Sub-Contracting: Do we need to add in for supporting contractors. Wrights can coordinate but will need further information and will need to be able to do another site walk with sub's and someone who can give us more clarification of connection points. VA Response: The awarded contractor is responsible for the entirety of the SOW. The hiring of subcontractors is permitted. The VA has no opinion on the hiring of subcontractors. Further discussion of - connection points and other design elements is expected to take place post-award in the design process. Question: 18 - Mechanical Space: Is there a small Mechanical room close that the equipment can go to rather than installing above the ceiling? VA Response: There is no mechanical room that is designed or designated for that purpose. 1. ELECTRICAL 2. PLUMBING 3. SPRINKLER 4. SHEET ROCKERS 5. PAINTERS 6. FRAMING FLOOR DRAIN FOR CONDENSATION Question: 19 - Floor Drain Location: Who is responsible for getting the floor drain installed? Will a plumber be needed? VA Response: Per the SOW, - Installation will include all new associated subsystems associated with the function of the units, and connections to building systems including power and data. This includes plumbing and drains. The precise location will be decided in the design process post-award. The awarded contractor is responsible for all parts and labor in the SOW. Question: 20 - Floor Drain Per Code: Who will determine what existing lines the piping for the floor drains to be piped into per code? Original construction Mechanical Engineer? VA Response: Piping and tie-ins will be coordinated with VA Engineering and the COR in the design process post-award. Question: 21 - Line to Tie Into: Need to know what lines we can tie into? VA Response: Water cooled is not an option. Question: 22 - Connections Supplied: Will there be connections supplied, or will we need to build into our quote to the tapping into the lines? VA Response: Water cooled is not an option. Question: 23 - Drain Down of Lines: Will building Engineer do drain down of lines which are being tapped into or overseeing the process? VA Response: Water cooled is not an option. Question: 24 - Walk-through: Will need additional job walk to see what is entailed in installing taps, we will need to revisit site to determine what equipment needs turned off, lines that need valved off and drained down process? VA Response: Water cooled is not an option. Question: 25 - Building Return: Building return chase if air cooled? VA Response: I do not understand the intent of the question enough to answer. Question: 26 - Building Return: What is the plan for getting rid of the condenser heat and keeping the unit cool? VA Response: Per the SOW, - The contractor will design an airflow solution that allows the cooling unit to function properly and limits disruptions to surrounding airflows and room pressures. Question: 27 - Refrigerator Leak: Is it approved for the condenser air to be returned into the building AC system? (In case of refrigerator leak) VA Response: Per the SOW, - The contractor will design an airflow solution that allows the cooling unit to function properly and limits disruptions to surrounding airflows and room pressures. Further discussion of design is expected to be conducted post-award in the design process. Question: 28 - Wall Installation: Will a wall need to install above the front of walk-in to enclose space above the unit. This will allow us to put a return and supply AC ducts with damper system and thermostat to keep the space the condenser is in regulated. VA Response: No wall is required above the ceiling. It is required that the ceiling and the walk-in are joined or sealed in such a way that no airflow is allowed between the above and below ceiling compartments. Any additional walls or compartments above ceiling would be permitted, as long as they do not interfere with life safety devices or utilities and are approved by VA Engineering in the post-award design process. Question: 29 - Additional Compressor: Does an additional compressor need to be onsite waiting or built into the system? The reason I ask is if goes to ground and both are in the system they are both ruined. Would it be best to have a back condenser skid available on top of the box ready for emergency repair. VA Response: The intention is that no manual intervention is required to switch between redundant systems. The redundant compressor must be piped into the system. Question: 30 - Separate Systems: Are we needing 2 complete separate systems installed in the box? VA Response: The requirement is for redundancy of the compressor. Question: 31 - Extending Warranty: Is the VA requesting extended warranty beyond 1-year labor, 1-year parts, and 1-year proper installation? VA Response: No, extended warranty was not requested in the SOW. Question: 32 - System Plans: Plans will be required. Arch., Fire Suppression, Plumbing, Mechanical, Electrical and Special Systems plans will be required to determine impacts, tie-in locations and overall routing between refrigerator and outdoor condenser packages, access to power and drainage. VA Response: Will be provided shortly. Question: 33 - Plans Provided: If plans are not going to be provided, identify where and what circuit(s) to power the refrigerator, lighting, controls, etc. VA Response: Plans will be provided. Question: 34 - Plans Provided: If plans are not going to be provided, identify what drain lines can be tapped into for new floor drain installation. VA Response: Plans will be provided. Question: 35 - Plans Provided: - If plans are not going to be provided, identify where remote equipment is to reside and provide the routing of refrigerant, power, plumbing and drain lines. Include impacts on existing construction and finishes. VA Response: Plans will be provided. Question: 36 - Return Air: Can building return air be used to exhaust condenser heat if installed on top of unit? VA Response: Per the SOW, the contractor will design an airflow solution that allows the cooling unit to function properly and limits disruptions to surrounding airflows and room pressures. Further discussion of design is expected to be conducted post-award in the design process. Question: 37 - Return Air: - If not, can additional HVAC supply and return be installed to control temp above unit and sealed to ceiling per Scope note #3? VA Response: The aforementioned would be permitted, provided it does not interfere with life safety equipment or utilities. Question: 38 - Plumbing: Once plumbing is identified, and additional job walk will be required to determine what equipment needs turned oB, lines that need valved and coordinate the drain down process. VA Response: No additional site walks will be offered pre-award. THE DUE DATE FOR OFFERS IS NOW AUGUST 21, 2025 @ 12:00PM. ______________________________________________________________________ All other terms and conditions remain unchanged.

More opportunities from Department Of Veterans Affairs → Rpo West (36C24W)

Same awarding agency

NAICS: 531120
New
Federal
VHA seeking 20,250 RSF for a Community Based Outreach Clinic in Twin Falls, ID
Solicitation # 36C24W26R0017
The Department of Veterans Affairs, through RPO West, is soliciting proposals for the lease of approximately 15,000 to 20,250 square feet of contiguous space to establish a Community Based Outpatient Clinic (CBOC) in Twin Falls, Idaho. This procurement is designated as a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside. The government seeks a fully serviced lease with a 20-year total term, including a 10-year firm period, and requires at least 50 parking spaces. The facility will house a variety of clinical and support services, including an Outpatient/PACT clinic, mental health services, pharmacy, laboratory medicine, and a canteen. The project involves stringent design and construction standards, including compliance with USP 800 clean air requirements for pharmacy compounding, VA Facility Security Level II standards, and specific seismic design requirements. Offerors must provide a comprehensive design team covering architecture, civil, mechanical, electrical, and low-voltage engineering. The government has established a Tenant Improvement (TI) allowance of $354.16 per ABOA square foot. Proposals will be evaluated based on a best-value tradeoff process, weighing price against technical factors such as architectural concept, site characteristics, and neighborhood compatibility. Submissions must be delivered in two separate volumes, technical and price, by the revised deadline of October 27, 2026.
Lessors of Nonresidential Buildings (except Miniwarehouses)

POSTED

1 day ago

DEADLINE

in 20 days
View Details
NAICS: 339115
New
Federal
Corneal Analyzer OPD-Scan III Wavefront Aberrometer
Solicitation # 36C24W27Q0010
The Department of Veterans Affairs Veterans Health Administration is conducting market research via a Sources Sought Notice for the procurement of one OPD-Scan III Visual System Wavefront Aberrometer/Corneal Analyzer for the San Francisco VA Health Care System in Oakland, California. This is a brand name or equal requirement, meaning the government will accept the specified Marco system or a functionally equivalent product that meets all salient physical and performance characteristics. The system must provide combined functionality for auto-refraction, auto-keratometry, topography, aberrometry, and pupillometry, with a spherical power range of -20.00 to +22.00 D and cylindrical power of 0.00 to ±12.00 D. It must also be compatible with Marco TRS-6100/5100 and NIDEK RT-6100 automated refraction systems. The final contract will be a Firm Fixed Price award requiring a minimum one-year manufacturer warranty. To prevent the acquisition of gray market items, the vendor must be an original equipment manufacturer or an authorized dealer/distributor, providing an authorization letter to verify that OEM warranty and service are maintained. Delivery is set as FOB Destination to the Oakland facility, with a specific constraint that items cannot be delivered before February 10, 2027. All deliveries must occur during normal business hours (0800 to 1500 PST) and be coordinated one week in advance. The Buy American Statute applies to this procurement. This current notice is for planning and size determination purposes only and does not constitute a solicitation or a binding offer.
Ophthalmic Goods Manufacturing

POSTED

1 day ago

DEADLINE

in 13 days
View Details
NAICS: 531120
New
Federal
Request for Lease Proposal (RLP): Las Vegas, NV Medical Facility
Solicitation # 36C24W26R0046
The Department of Veterans Affairs is soliciting proposals for the lease of a medical facility in Las Vegas, Nevada, under solicitation number 36C24W26R0046. The government requires between 23,721 and 27,280 ABOA square feet of contiguous space for a 20-year lease term, with the first 10 years being firm. The facility must accommodate a mental health outpatient clinic and meet strict technical go/no-go criteria, including a minimum finished ceiling height of 90 inches, a prohibition on VRF HVAC systems, and at least one ambulance stretcher-accessible elevator for multi-story buildings. Additionally, the site must support 6-foot-wide clear patient corridors and provide 90 to 120 parking spaces, including five ADA-compliant spots. The award will be based on a best value tradeoff process where technical factors, specifically the proposed space layout's ability to meet Agency Specific Requirements, are significantly more important than price. Offerors must submit pricing via GSA Form 1364, itemizing shell rent, operating costs, and parking, with a Tenant Improvement allowance set at 350 dollars per ABOA square foot. Proposals must be submitted electronically in PDF format to the authorized broker, Carpenter/Robbins Commercial Real Estate, Inc., by 4:30 PM Pacific Time on November 16, 2026. Required documentation includes GSA Form 1217, seismic compliance certifications, and evidence of SDVOSB or VOSB status to determine potential set-asides.
Lessors of Nonresidential Buildings (except Miniwarehouses)

POSTED

2 days ago

DEADLINE

in 26 days
View Details
NAICS: 531130
New
Federal
X1GZ--REQUEST FOR LEASE PROPOSAL: Warehouse - Las Vegas, Nevada
Solicitation # RLP36C24W26R0045
The U.S. Department of Veterans Affairs, through the General Services Administration, is soliciting proposals for a warehouse lease in Las Vegas, Nevada, to support the VA Southern Nevada Health Care System. The government seeks a facility for a 20-year lease term, with the first 10 years being firm. Key requirements include a specific parking capacity of 75 to 90 spaces, Facility Security Level II compliance, and adherence to strict architectural and technical standards, such as sealed concrete finishes for loading docks and specific seismic safety certifications. The facility must also meet ADA accessibility and environmental standards, including TSCA Title VI compliance for wood products. Award will be determined using a best value tradeoff process, where technical factors—including space layout efficiency, site quality, parking flexibility, maintenance response, and past performance—are considered significantly more important than price. Proposals must be submitted by November 30, 2026, at 4:00 PM PDT, and must include GSA Form 1364WH, a detailed construction schedule, and CAD floorplans in .DWG format. The contract is subject to the Davis-Bacon Act and requires offerors to maintain active SAM registration and provide representations regarding telecommunications equipment and seismic compliance.
Lessors of Miniwarehouses and Self-Storage Units

POSTED

5 days ago

DEADLINE

in about 1 month
View Details

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS