DSCR B100/CDC Fire Panel Replacement Project

Closed
SP470326Q0032Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 238210
New
Transformer Oil Testing Services
Solicitation # RFP-VC-26-010
The Inland Empire Utilities Agency is soliciting proposals under RFP-VC-26-010 for transformer oil testing services to enhance the reliability, safety, and maintainability of its transformers across six locations, including RP-1, RP-2, RP-4, RP-5, CCWRF, and CDA. The scope of work comprises three primary objectives: performing visual and infrared thermographic inspections to identify thermal anomalies, installing standardized external oil sampling devices for safer collection, and conducting comprehensive oil testing analysis. Additionally, the contractor is required to evaluate nitrogen blanket systems to ensure positive pressure and provide on-site training for up to 20 agency staff members on inspection tools and defect identification. All work must adhere to NETA MTS, IEEE, NFPA 70E, and ASTM D923 standards, with infrared inspections performed by technicians certified to ASNT Level 1 or higher. This is a fixed-pricing contract with a not-to-exceed total price, intended as a single award to the most capable and cost-effective offeror. Evaluation criteria include the proposer's past performance, specifically requiring at least two similar projects completed within the last five years, as well as the proposed staffing plan, methodology, and fee structure. Proposals must be submitted electronically via PlanetBids by December 23, 2026, and must include a detailed company profile, project approach, and various required forms such as a Non-Collusion Statement and Workers Compensation Certificate. Selected contractors must be registered with the Department of Industrial Relations as public works contractors and must accept electronic payments via ACH.
Inland Empire Utilities Agency

POSTED

about 2 hours ago

DEADLINE

in about 2 months
NAICS: 238210
New
Centennial JCC Emergency Lighting Replacement, Upgrade, Testing & Maintenance Services
Solicitation # centennial-jcc-emergency-lighting-replacement-upgrade-testing-maintenance-services
Management and Training Corporation is soliciting bids for a fixed-price, single lump sum contract to provide emergency lighting replacement, upgrade, testing, and maintenance services at the Centennial Job Corps Center in Nampa, Idaho. The project involves the inspection, repair, and certification of emergency lighting systems to ensure compliance with NFPA 101 (2024 Edition) and NFPA 70 standards. The contractor is responsible for inventorying all fixtures, performing functional testing by simulating utility outages, applying durable tracking labels to each fixture, and integrating recurring maintenance into the facility's Computerized Maintenance Management System. The estimated contract value ranges between $25,000 and $100,000. Bids are due by December 1, 2026, and must be submitted via email to Sandra Clore. A mandatory physical site visit and signature on the attendance roster are required prior to bid submission. For bids equal to or greater than $25,000, contractors must provide a bid bond guarantee of 20% of the base bid, and the awarded contractor will be required to provide performance and payment bonds from a surety company with at least an A- rating. Evaluation is based on overall best value. The contract is set aside for small businesses, including VOSB, SDVOSB, WOSB, and HUBZone certifications. Compliance requirements include adherence to the Davis-Bacon Act, Federal Contractor Minimum Wage requirements, and Executive Order 13706 regarding paid sick leave. Contractors must provide certificates of disposal for hazardous materials and manufacturer warranties for all equipment and workmanship. Final payment is contingent upon a joint substantial completion inspection and the resolution of any punch list items.
Management & Training Corporation/Centennial Job Corps Center

POSTED

about 2 hours ago

DEADLINE

in about 1 month

AI Contract Overview

Show more

This solicitation, issued as a combined synopsis and request for quote under FAR Part 12, is a total small business set-aside for the complete replacement of the fire alarm system at Building 100, the Child Development Center at Defense Supply Center Richmond in Chesterfield County, Virginia. The contract is awarded on a lowest-priced, technically acceptable basis as a firm-fixed price arrangement with a 120-day period of performance following notice to proceed, and has an estimated value between $125,000 and $175,000. The NAICS code 238210 applies, with a size standard of $19 million, and the contractor must maintain a bona fide place of business within 125 miles of the site. All work must be performed after regular hours to avoid disruption to the child care facility, and the existing system must remain fully operational throughout replacement; if interrupted, a 24/7 fire watch is mandatory. The new system must include a fully addressable, point-to-point fire alarm and emergency voice notification system using a single manufacturer’s integrated platform: the Notifier NFS-320 fire alarm panel, SigCom MNS-100EXP mass notification panel, and SigCom sixteen zone DTX transceiver. All components must be compatible with the existing TRX-50 fire alarm reporting network serving key base facilities, and the system must support live voice evacuation, wireless RF communication to the dispatch center, HVAC shutdown integration, and full compliance with UFC 3-600-01 and UFC 4-021-01. The contractor must remove and responsibly dispose of all existing components, including batteries, through RCRA-approved recyclers, and install entirely new wiring, conduits, initiating devices, notification appliances, and a remote annunciator. Technical oversight requires a NICET Level III certified technician for supervision, manufacturer-certified personnel for programming, and documentation of all certifications before work begins. Third-party verification and final acceptance by the Authority Having Jurisdiction are required, along with submission of as-built drawings, O&M manuals, system passwords, and backup files. A mandatory site visit on May 12, 2026, requires pre-enrollment in DBIDS with a minimum five-day vetting window, and all attendees must be sponsored and provide QR codes to the project manager. Questions are due by COB May 14, 2026, and quotes must be submitted via

General Info

DoD seeks small business for $125K-$175K fire alarm system replacement at DSCR CDC, 120 days.

NAICS

238210 - Electrical Contractors and Other Wiring Installation Contractors

Place of Performance

GRASSY CREEK, VA, 23237, USA

Set-Aside

SBA

Documents

3

DSCR-100-SOW-Fire-alarm-panel-replacement2.pdf

PDF

SF1449+SP470326Q0032.pdf

PDF

Wage+Determination+20260007.pdf

PDF

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

PhaseClosed
Posted

Combined Synopsis

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Start your free trial to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Defense → Dcso Richmond Division #1
Contacts2 people available
OfficeRICHMOND, VA, 23237, USA
Office AddressRICHMOND, VA, 23237, USA
Contacts
Robert Moragues Contracting Officer
Kyle Gregory Contracting Officer

Full Description

Show more

This is a combined synopsis/solicitation for commercially available services prepared in accordance with the format in FAR Part 12, and supplemented with additional information included in this notice.  The solicitation number SP470326Q0032 is issued as a request for quote(RFQ).  Award will be made to the Lowest Priced Technically Acceptable offeror.   


The resulting contract will be a firm-fixed price award with an expected Period of Performance of 120 days from issuance of notice to proceed. 


Disclosure of magnitude: the estimated magnitude of the award is between $125,000.00 - $175,000.00


This acquisition is set-aside for 100% small business.  


The North American Industry Classification System (NAICS) Code is 238210 (Electrical Contractors and Other Wiring Installation Contractors).  The small business size standard is $19M.  Department of Labor Wage Determination based on location of the service provided (Chesterfield County, VA).  Partial proposals will not be accepted.  


A site visit will be held on 05/12/2026@1000. See "Additional Details" below for full text for parties interested in attending the site visit. Please note: Parties interested in attending the site visit MUST be vetted through security prior to the date of the site visit - vetting can take 5 business days, interested parties should plan accordingly. 


Deadline for questions is COB 05/14/2026 - Questions and Answers will be publicly posted as an attachment to the same notice id on SAM.gov as the solicitation.  Generally, answers will be posted to SAM.gov within 2 working days of the deadline for questions.  


Deadline for quote is COB 05/27/2026.  


Acceptable method of quote: Email to contracting officer Robert Moragues <contact@example.gov>



**********************************Specific Requirements***************************


For an offer to be considered for award, the contractor must own, possess, or otherwise control a bona fide place of business from which mobilization occurs within 125 miles of Defense Supply Center Richmond. A bona fide place of business refers to a location where the offeror regularly maintains an office with at least one full-time employee. The offeror must include the address of this location within the offer submitted.


OBJECTIVES


Provide a complete replacement of the existing fire alarm system with a new, fully
addressable Fire Alarm and Emergency Voice/Alarm Communication System that complies
with current DoD Unified Facilities Criteria (UFC). The new system shall provide fire
detection, occupant notification, and intelligible live voice evacuation capability throughout
the facility.


BACKGROUND


Building 100 serves as the installation Child Development Center (CDC) and houses a
vulnerable population requiring continuous and reliable life safety protection. The existing
fire alarm system has exceeded its useful service life and is no longer fully supported by the
manufacturer. Full system replacement is required to ensure compliance with current fire
protection engineering standards, improve reliability, and ensure compatibility with base
wide emergency communication system.


To enhance the reliability and maintainability of life-safety systems at Defense Supply
Center Richmond (DSCR), the Site Director has mandated the standardization of all fire
alarm and mass notification panels. Effective immediately, all systems will be consolidated
to a single commercially available off the shelf brand and type. This initiative is designed to
streamline technician training, reduce repair times by ensuring parts availability, and
mitigate previously identified operational deficiencies.


SPECIFIC REQUIREMENTS


The Contractor shall provide all labor, materials, equipment, design coordination,
supervision, and incidentals necessary to remove the existing system and furnish and install
a complete, operational Fire Alarm and Emergency Voice/Alarm Communication System.


3.1 System Removal


o Disconnect and remove the existing Fire Alarm Control Panel (FACP), annunciators,
power supplies, batteries, and associated components.
o The contractor is solely responsible for the proper handling, collection, and disposal of
all fire alarm batteries removed. This responsibility includes ensuring the batteries are
recycled at a resource conservation and recovery act (RCRA) approved facility.
o Remove all existing initiating devices including smoke detectors, heat detectors, duct
detectors, manual pull stations, and monitor/control modules.
o Remove all existing notification appliances including horn/strobes, strobes, speakers,
and bells.
o Remove existing fire alarm wiring, conduit where determined to be noncompliant,
damaged, or unsuitable for reuse.
o Properly dispose of all removed equipment in accordance with federal, state, and local
regulations.


3.2 New System Installation


A new, complete, and unified fire alarm system is to be installed in building 100. This
system will be a Class B, fully addressable, point to point system that includes integrated
mass notification and emergency voice services. All components of the system must be
from a single manufacture to ensure seamless integration and functionality, precluding a
“piecemealed” assembly of parts from various suppliers.


o Furnish and install new initiating devices throughout the facility, including smoke
detectors, heat detectors, manual pull stations, duct detectors, and monitor/control
modules.
o The following is a list of panels required to be used in this project, or their most up to
date equivalent models:
􀁸 Notifier NFS-320 fire alarm panel with RS 232/485 port.
􀁸 SigCom MNS-100EXP mass notification panel with LOCs
􀁸 SigCom sixteen zone DTX transceiver


o Installation of speaker/ strobe notification appliance to provide audible, visual, and live
voice evacuation messaging.
o Provide new live microphone capability and pre-recorded emergency messages.
o System interface and compatibility with the installation’s base-wide radio frequency
fire alarm reporting network.
o Transmit point to point data, including individual alarm, supervisory, and trouble
signals, directly to the installation dispatch center.
o Provide new fire alarm wiring and conduit as required to support the new system.
o Integration with HVAC shutdown and other required life safety interfaces.
o Provide new system with batteries sized in accordance with code-required standby and
alarm duration.
o Furnish and install a new remote annunciator panel
o Every connection within the system, including devices such as pull stations and
tamper switches, must be clearly and accurately labeled.
o All fire alarm and MNS components must be compatible, integrated, code compliant
and communicate and interface with existing TRX-50 (Signal communications) fire
alarm reporting system serving buildings 201 (Fire department), 56 (Fire pumps), and
41 (Dispatch).
o The appointed contractor shall be responsible for providing a complete design
submission along with shop drawings for review by the government. All submitted
documentation must be in accordance with the standards and requirements outlined in
UFC 3-600-01 and 3-601-02.


3.3 Installation Phasing and Occupancy Requirements


o Building 100 is an actively occupied Child Development Center. Contractor shall
coordinate all work to minimize disruption to daily operations.
o Work shall be performed after normal operating hours between 1830-0530.
o The fire alarm system must remain operational during its replacement. If the system is
down or impaired, a designated person must implement a formal, 24/7 fire watch to
ensure continuous safety.
o The contractor shall provide advance notice of any planned outages.
o The contractor shall provide a temporary portable toilet for the duration of the project.
3.4 Testing and Turnover
o Perform 100 percent functional testing of all initiating devices and notification
appliances with UFC 3-600-01 and UFC 4-021-01.
o Verify proper RF communication and point to point signal transmission to dispatch.
o Test live voice evacuation functionality, including microphone and pre-recorded
messages.
o Ensure the installation contractor has pre-tested the system to avoid failures during the
official third-party inspection.
o Use Third Party-Verification by a qualified and authorized person. A third-party
professional is recommended to verify the new system is compliant, properly
installed, and fully functional. Also, the third party will perform acceptance testing
with stakeholders, verifying that all components function as intended and that system
communicates with emergency services.
o The final approval for the system will be granted by the Authority Having Jurisdiction
(AHJ), ensuring compliance with UFC 4-021-01.
o Coordinate final acceptance testing with the project manager and the Authority Having
Jurisdiction (AHJ).
o Provide as-built drawings, approved shop drawings, battery calculations, O&M
manuals, and programming backup files.
o Provide all system passwords, administrative credentials, and access codes to the
project manager.
o The Government shall retain full administrative control of the system upon project
completion.


3.5 Codes and standards


All design, installation, testing, and commissioning shall comply with the latest adopted
editions of the following:
o UFC 3-600-01- Fire protection engineering for facilities
o UFC 4-021-01- Mass notification systems


CONTRACTOR QUALIFICATIONS


The contractor shall specialize in fire alarm system installation and shall have a minimum of ten
years of documented experience performing fire alarm system installations.


o System installation shall be supervised by a technician certified at a minimum of
NICET Level III in fire alarm systems.
o System layout and programming shall be performed and reviewed by personnel
certified in fire alarm systems in accordance with NICET requirements.
o Documentation of NICET certifications shall be submitted to the project manager prior
to commencement of work.
o Technicians performing programming shall be manufacturer certified for the installed
system.


PERIOD OF PERFORMANCE


Completion date shall be no later than 120 days after notice to proceed.


See SOW for complete project requirement detail.


**********************ADDITIONAL INFORMATION*******************


A site visit will be held 05/12/2026 @1000.  See p.48 of SOW for DSCR map - CDC/B100 is marked with a red dot and labeled "CDC/B100" 


In order to attend the site visit interested parties MUST follow the instructions below no less than 5 business days prior to the site visit.  This is to allow time for vetting by base security.  Plan on arriving at DSCR an hour prior to the site visit time, as the processing time through the visitor center fluctuates.  Follow the link below to register through DBIDS, and a QR code should be provided for each visitor.  The QR codes MUST be emailed to the Project Manager, Raymond Massey <contact@example.gov> (Work Cell: +1 (555) 000-0000).  The QR code MUST be emailed to the project manager as soon as possible due to the lengthy vetting process of approximately 5 business days. The project manager will also serve as the sponsor for site visit attendees.  


A new system was implemented on 3 January 2023 to screen visitors and contractors for installation access at DSCR.The new system is designed to increase efficiencies, enhance the protection of personal information during the vetting process and eliminate the use of hard copy DLA Form 1815s.  The new screening system will require visitors and contractors to pre-enroll in DBIDS (Defense Biometric Identification System). To begin the process, visitors and contractors will complete registration through the pre-enrollment website: 


https://dbids-global-enroll.dmdc.mil.


Upon entry of their information, visiting personnel will be provided an electronic form to download, which will have
an individualized barcode and alpha numeric code. The codes need to be sent to the visiting person’s
sponsor. Once in receipt of the barcode, the sponsor will email Security and Emergency Services and provide the
barcode and sponsorship information. Once the visitor/contractor is vetted and approved for installation access,
Security & Emergency Services will notify the sponsor that the visitor/contractor can go to the DSCR Visitor Center to
obtain his/her pass. At the Visitor Center, the visitor provides the barcode and code provided earlier in the process
and completes the credentialing process.


See attached SOW for full requirement details. Parties interested in submitting a quote for this project are advised and expected to have reviewed the entire SOW prior to site visit attendance.

More opportunities from Department Of Defense → Dcso Richmond Division #1

Same awarding agency

NAICS: 236220
New
Federal
DSCR B34 & B42 System Smoke Testing & Hydro Jetting
Solicitation # SP470327Q0003
The Defense Supply Center Richmond (DSCR) is soliciting quotes for a firm-fixed-price contract to perform smoke testing, hydro jetting, and comprehensive evaluations of the Drain, Waste, and Vent (DWV) systems in Buildings 34 and 42. The primary objective is to identify defects, leaks, and obstructions causing sewer odors, though no repairs are authorized under this scope. Key deliverables include the hydro jetting of accessible sanitary drain systems, CCTV inspections with footage provided on a USB drive, and a detailed written report outlining findings and recommended corrective actions. The estimated magnitude of construction is between $25,000 and $100,000, with a period of performance of 60 days from the Notice to Proceed. This acquisition is a 100% small business set-aside under NAICS code 236220. Award will be made to the lowest priced, technically acceptable (LPTA) offeror. To be considered, prime contractors must be located within a 120-mile commutable radius of the DSCR facility and demonstrate at least three years of experience with commercial DWV systems, including five relevant projects completed within the last five years. Required submission documents include a project narrative with a timeline of definable features of work and a list of previous relevant experience. The contract includes strict administrative and safety requirements, including the use of the US Army Corps of Engineers three-phase inspection process and adherence to USACE EM 385-1-1 safety standards. Contractors must provide performance and payment bonds within five days of award and maintain an onsite Quality Control System Manager during all work. Payment is managed via Wide Area Workflow (WAWF), with a cap of 80% of the total contract value payable until the final inspection is accepted. Liquidated damages for delays are set at $500 per calendar day. Access to the facility requires pre-enrollment in the Defense Biometric Identification System (DBIDS).
Commercial and Institutional Building Construction

POSTED

7 days ago

DEADLINE

in about 20 hours
View Details

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS