Heartland Behavioral Healthcare Biannual Legionella testing - 301df20250915
Contract Overview
Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.
Active Opportunities Like This One
AI Contract Overview
This contract involves comprehensive Legionella testing within the water systems of Heartland Behavioral Healthcare to ensure safety and regulatory compliance. The scope includes establishing baseline Legionella levels, conducting routine biannual testing, and focusing on high-risk areas such as showers, sinks, and other aerosol-generating devices. Testing procedures specify collecting water samples from designated locations, analyzing them at accredited laboratories using approved methods, and maintaining strict documentation for traceability. Results will be evaluated against CDC thresholds, with immediate corrective actions taken if Legionella concentrations exceed acceptable levels, including system adjustments or biocide treatments. The contract emphasizes adherence to federal and industry standards such as CMS, ASHRAE 188, and CDC guidelines, with detailed record-keeping of all activities, results, and remediation efforts. Site visits are scheduled for September 24 and 25, with a designated contact for coordination. The project aims to mitigate Legionella risks effectively, ensuring a safe environment for patients, staff, and visitors, with a contract value estimated between $50,000 and $150,000.
General Info
Place of Performance
OH, USASet-Aside
Timeline
Submission Closed
Organization & Contact Information
Full Description
2. Regulatory Compliance Centers for Medicare & Medicaid Services (CMS): Ensure adherence to infection prevention and control standards as per 42 CFR §482.42 for hospitals. ASHRAE Standard 188: Comply with guidelines for the design, installation, and operation of building water systems to minimize Legionella growth. CDC Guidelines: Follow the CDC's Routine Testing for Legionella and Environmental Assessment recommendations.
3. Testing Frequency and Locations Initial Testing: Conduct comprehensive testing upon implementation of the water management plan. Routine Testing: Perform testing biannually. High-Risk Areas: Prioritize testing in areas with aerosolizing water devices, such as showers, faucets, cooling towers, and decorative fountains.
4. Sampling Procedures Sample Collection: Collect 250 mL water samples from representative points within the water system, ensuring coverage of all major branches and devices. Laboratory Analysis: Utilize accredited laboratories following ISO 11731:2017 or CDC-approved methods for Legionella culture. PCR methods are not acceptable for routine testing. Chain of Custody: Maintain strict documentation and handling procedures to ensure sample integrity and traceability.
5. Data Interpretation and Reporting Result Evaluation: Analyze Legionella concentrations in colony-forming units per milliliter (CFU/mL) and identify species present. Action Thresholds: Refer to CDC's Routine Testing guidelines for interpreting results and determining necessary corrective actions. Reporting: Provide detailed reports to hospital administration, infection control teams, and relevant stakeholders.
6. Remediation and Corrective Actions Identification of Issues: If Legionella concentrations exceed acceptable thresholds, initiate immediate corrective actions. Strategies: Implement measures such as temperature adjustments, biocide treatments, or system modifications to eliminate Legionella growth. Documentation: Record all remediation efforts, including methods used, areas treated, and outcomes.
7. Documentation and Record Keeping Comprehensive Records: Maintain detailed logs of all testing activities, results, corrective actions, and training sessions. Accessibility: Ensure records are readily accessible for review by regulatory bodies and accreditation agencies.
** Initial water sampling plan will include the following locations. Location, Room #Spigot, Shower, OtherNotes1 City water point of entry 2 Hot water storage tanks 3 Administration, LobbyWater fountain 4 B1, Room 120Shower 5 B1, Room 122Shower 6 B1, Seclusion RoomSink 7 C1, Room 126Shower 8 C1, Seclusion RoomSink 9 D1, Room 118Shower 10 D1, Room 120Shower 11 D1, Seclusion RoomSink 12 B2, Room 227Shower 13 B2, Seclusion RoomSink 14 C2, Room 224Shower 15 C2, Seclusion RoomSink 16 D2, Room 218Shower 17 D2, Seclusion RoomSink 18 Dietary, Kitchen Sink #1Sink 19 Dietary, Kitchen ice machineIce machine 20 Mech Room under police dept, hot water heaterOutlet
SITE VISIT IS REQUIRED: VISIT DATES 9/24, AND 25TH FROM 1PM-2PM. CONTACT SHANE POSEY +1 (555) 000-0000.2300
Find Active Opportunities Like This
Get AI-powered intelligence on the opportunities still open
Every page of the solicitation package shredded into a compliance breakdown
AI-powered matching based on your capabilities and past performance
Competitor and incumbent history on the requirement
Automated alerts on amendments, Q&A deadlines, and award
Join 750+ contractors already using CLEATUS