J--501-16-3-408-0095 - ABQ - MAINT. CONTRACT FOR EMERGENCY STANDBY POWER GENERATORS

Awarded
Federal
Submission Closed
Solicitation #
VA25816N0629

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

AI Contract Overview

Show more

This contract is a Statement of Work for the maintenance, inspection, and refueling of two Kohler emergency standby power generators (Models 450ROZD71 and 100REOZJB) located at the VA Cooperative Studies Program Clinical Research Pharmacy Coordinating Center in Albuquerque, New Mexico. The services are critical to protecting high-value pharmaceutical warehouses, bio-repository holding tanks, and clean rooms from power outages that could compromise temperature-sensitive medical materials. The scope of work includes semi-annual Level I maintenance, annual Level II maintenance, annual load bank testing, and refueling with dyed diesel #2 fuel as needed. The agreement consists of a base year running from September 15, 2016, to March 14, 2017, with four subsequent one-year option periods extending through March 15, 2021. Key requirements include a two-hour emergency response time during weekday off-hours and a three-hour response time on designated holidays. The contract is set aside for Service-Disabled Veteran-Owned Small Businesses and specifies that all work must be performed according to manufacturer service manuals and guidelines, with performance verified through direct observation and documentation.

General Info

Contract Value

$57,399.93

NAICS

335312 - Motor and Generator Manufacturing

Place of Performance

VA Cooperative Studies Program Clinical;2401 Centre Avenue, SE;Albuquerque, NM 87106 USA, AZ, USA

Set-Aside

SDVOSBC

Award Issued Date

Potential End Date

March 14, 2021

Documents

0

No documents available

This contract was awarded without public documents.

AI Contract Breakdown

Uniform Contract Format

No documents to break down

The breakdown needs solicitation documents. None were found from this contract's source.

This one is closed. Find the next one like it.

Open contracts like this one, right now:

  • ROTOR, MOTOROpen now, due in 5 days
  • POWER SUPPLYOpen now, due in 5 days
See open contracts like this

Ask CLEATUS

I've read this contract. Ask me anything.

Timeline

3 updates
PhaseAwarded
Posted

Combined Synopsis

Deadline changed

Response deadline changed from Jul 14, 2016 to Jul 29, 2016.

Notice updated

Response deadline changed from Jul 29, 2016 to Aug 17, 2016. The notice title changed. Set-aside removed. The notice description changed.

Notice updated

Response deadline changed from Aug 17, 2016 to Sep 8, 2016. Set-aside added: Service-Disabled Veteran-Owned Small Business Set Aside. The notice description changed.

Awarded

Contract was awarded

Find active opportunities like this

Get full access to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → 258-NETWORK Cntrct Office 22G (36C258)
ContactsNo contacts available
OfficeMESA, AZ, 85212, USA
Office AddressMESA, AZ, 85212, USA
ContactsNo contact information available

Full Description

Show more
STATEMENT OF WORK (SOW) As of 07/07/2016 Contract Number: (to be completed by the CO at time of award) Task Order Number: (to be completed by the CO at time of award if a TO) IFCAP Tracking Number: 501-16-3-408-0095 Follow-on to Contract and Task Order Number: N/A 1. CONTRACTING OFFICER'S REPRESENTATIVE (COR). Name: Frank Lueddeke Section: Chief, Clinical Materials Management Section Address: VA Cooperative Studies Program Clinical Research Pharmacy Coordinating Center 2401 Centre Avenue, SE Albuquerque, NM 87106-4180 Phone: Sign up to see this detail Mobile: Sign up to see this detail Fax: Sign up to see this detail Email Address: Sign up to see this detail 2. SUBJECT MATTER EXPER (SME). Name: Mark Valdez Section: Clinical Materials Management Section Address: VA Cooperative Studies Program Clinical Research Pharmacy Coordinating Center 2401 Centre Avenue, SE Albuquerque, NM 87106-4180 Phone: Sign up to see this detail Mobile: Sign up to see this detail Fax: Sign up to see this detail Email Address: Sign up to see this detail 3. SCHEDULE OF SERVICES AND/OR SUPPLIES. BASE YEAR - POP: 09/15/16 to 03/14/17 Description Est. Qty. Unit CLIN 1 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 2 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 3 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 4 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 5 - Flat rate service - refuel both (2) emergency standby generators with dyed diesel #2 fuel (per gallon), as needed. 70 GL CLIN 6 - Delivery charge - diesel fuel delivery charge 1 EA CLIN 7 - Estimated sales tax @ 7.1875% 1 EA CLIN 8 - Potential emergency repairs 1 JB OPTION PERIOD 1 - POP: 03/15/17 to 03/14/18 Description Est. Qty. Unit CLIN 1 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 2 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 3 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 4 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 5 - Flat rate service - refuel both (2) emergency standby generators with dyed diesel #2 fuel (per gallon), as needed. 70 GL CLIN 6 - Delivery charge - diesel fuel delivery charge. 1 EA CLIN 7 - Estimated sales tax @ 7.1875% 1 EA CLIN 8 - Potential emergency repairs 1 JB ? OPTION PERIOD 2 - POP: 03/14/18 to 03/15/19 Description Est. Qty. Unit CLIN 1 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 2 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 3 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 4 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 5 - Flat rate service - refuel both (2) emergency standby generators with dyed diesel #2 fuel (per gallon), as needed. 70 GL CLIN 6 - Delivery charge - diesel fuel delivery charge. 1 EA CLIN 7 - Estimated sales tax @ 7.1875% 1 EA CLIN 8 - Potential emergency repairs 1 JB OPTION PERIOD 3 - POP: 03/14/19 to 03/15/20 Description Est. Qty. Unit CLIN 1 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 2 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 3 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 4 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 5 - Flat rate service - refuel both (2) emergency standby generators with dyed diesel #2 fuel (per gallon), as needed. 70 GL CLIN 6 - Delivery charge - diesel fuel delivery charge. 1 EA CLIN 7 - Estimated sales tax @ 7.1875% 1 EA CLIN 8 - Potential emergency repairs 1 JB OPTION PERIOD 4 - POP: 03/14/20 to 03/15/21 Description Est. Qty. Unit CLIN 1 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 2 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 450ROZD71 - Serial# 363603 1 EA CLIN 3 - Flat rate service - perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator. Includes parts, labor and mileage. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 4 - Flat rate service - perform an annual load bank test on the emergency standby power generator. Includes setup, breakdown and load bank equipment. Make: Kohler - Model# 100REOZJB - Serial# 0769882 1 EA CLIN 5 - Flat rate service - refuel both (2) emergency standby generators with dyed diesel #2 fuel (per gallon), as needed. 70 GL CLIN 6 - Delivery charge - diesel fuel delivery charge. 1 EA CLIN 7 - Estimated sales tax @ 7.1875% 1 EA CLIN 8 - Potential emergency repairs 1 JB 4. CONTRACT TITLE. Maintenance Contract for Emergency Standby Power Generators 5. BACKGROUND. The Department of Veteran Affairs (VA) Cooperative Studies Program Clinical Research Pharmacy Coordinating Center (CSPCRPCC) has a requirement to service, maintain and refuel two emergency power generators (Models 450ROZD71 & 100REOZJB) year round to ensure emergency power should the facility experience a power outage. CSPCRPCC maintains three pharmaceutical, packaging and medical device ware houses, as well as two pharmaceutical cold chain freezers, totaling 21,038 square feet. Materials housed in these areas contain critical one of a kind drug. Additionally CSPCRPCC also maintains and operates, -200° to 250° C +/-2.5° C bio-repository holding tanks and -90° to 25 C,+/- 0.5° C freezer's; five clean rooms, where drug compound materials are housed and used to perform drug manufacturing daily. Over fifty pieces of manufacturing, and packaging equipment are housed throughout the facility that are consistently operational so as to meet all veteran patient study projects that are ongoing and in a trial basis. The use of these emergency standby power generators is critical to the continued operation of the environmental monitoring system in place which monitors for humidity and dew point perimeters as well as to the continued operation of both cold storage freezers and -200° to 250° C +/-2.5° C bio-repository holding tanks and -90° to 25 C,+/- 0.5° C freezer's. If a power failure was to occur; temperature, and humidity increases could reach negative thresh hold range rendering all bulk, packaged and drug compounds currently stored in warehouses to be out of change specification and become non distributable. Cold storage freezers and bio tanks would not operate. This possibility of losing power would, potentially cause CSPCRPCC to lose millions of dollars in value as well as the critical need of veteran patients requiring this study medication for their health and safety. 6. SCOPE. a. Perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator on Model 450ROZD71/100REOZJB. Include parts, labor and mileage. b. Perform an annual load bank test on the emergency standby power generator (Model 450ROZD71) to include setup, breakdown and load bank equipment. c. Refuel both emergency standby power generators with dyed diesel #2 fuel (per gallon), as needed. d. Emergency after hour call desk to include all holidays e. Two (2) hour emergency after hour response time " Monday - Friday, 4:00 PM to 8:00 AM " Friday 4:00 PM thru Monday 8:00am f. Three (3) hour emergency response time during following Holidays " New Year's Day " Martin Luther King Jr. " Presidents Day " Memorial Day " Independence Day " Labor Day " Columbus Day " Veterans Day " Thanksgiving Day " Christmas g. Travel time and mileage. 7. SPECIFIC TASKS. 7.1 Task 1 - Perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator (Model 450ROZD71): Vendor will perform all required steps and procedures necessary to meet the specific requirements called out for each level of maintenance task. " Semi-Annual Level I maintenance service and inspections, including a detailed parts listing required, labor and mileage driven per service period. " Annual Level I maintenance service and inspections, including a detailed parts listing required, labor and mileage driven per service period. 7.2 Task 2 - Perform annual load bank test on emergency standby power generator (Model 450ROZD71): Vendor will setup test equipment and load bank equipment. In order to perform all required testing procedures, ensuring the power generator will meet the power and load rate requirements during a facility power failure. 7.3 Task 3 - Perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator (Model 100REOZJB): Vendor will perform all required steps and procedures necessary to meet the specific requirements called out for each level of maintenance task. " Semi-annual level I maintenance service and inspections, including a detailed parts listing, required labor and mileage driven per service period. " Annual level I maintenance service and inspections, including a detailed parts listing, required labor and mileage driven per service period. 7.4 Task 4 - Perform annual load bank test on emergency standby power generator (Model 100REOZJB): Vendor will setup test equipment and load bank equipment in order to perform all required testing procedures, ensuring the power generator will meet the power and load rate requirements during a facility power failure. 7.5 Task 5 - Refuel both emergency standby generators with dyed diesel #2 (per gallon) as needed. " Vendor will check fuel level per each site visit and fill each generator as needed. " Vendor will provide fair market value on fuel cost per gallon to be charged to the CSPCRPCC at the time of delivery. 8. PERFORMANCE MONITORING. Task Standard Acceptable Quality Level Surveillance Method 7.1 - Perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator on Model 450ROZD71 Performance will be carried out per equipment/ manufactures service manuals and check list System must meet type emergency power generator specifications Direct Observation, Documentation and reports 7.2 - Perform annual load bank test on emergency standby power Generator, Model 450ROZD71 Performance will be carried out per equipment/ manufactures service manuals and testing guidelines System must meet type emergency power generator specifications Direct Observation, Documentation and reports 7.3 - Perform semi-annual level I maintenance service and inspection and annual level II and maintenance service and inspection on the emergency standby power generator on Model 100REOZJB Performance will be carried out per equipment/ manufactures service manuals and testing guidelines System must meet type emergency power generator specifications Direct Observation, Documentation and reports 7.4 - Perform annual load bank test on emergency standby power Generator, Model 100REOZJB Performance will be carried out per equipment/ manufactures service manuals and testing guidelines System must meet type emergency power generator specifications Direct Observation, Documentation and reports 7.5 - Refuel both emergency standby generators With Dyed Diesel #2 (per gallon) as needed The refueling of both generators will meet diesel fuel requirements having #2 dye additives Diesel fuel will meet state and federal regulation standards Documentation 9. SECURITY REQUIREMENTS. All contractor(s) are required to present a valid ID (driver's license or government issued ID) to our Security Officer(s) in order to be physically checked in and given a visitor's badge. Contractor(s) must wear their visitor's badge and be escorted by a CSPCRPCC staff member at all times while in the facility. The contractor will not have access to any IT networks or patient information. The C&A requirements do not apply and a Security Accreditation Package is not required. ? 10. GOVERNMENT-FURNISHED EQUIPMENT (GFE)/GOVERNMENT-FURNISHED INFORMATION (GFI). The CSPCRPCC Plant Engineer may supply/assist the contractor with specialized hand tools and small shop supplies if needed. Any power and compressed air requirement for this system will be handled by CSPCRPCC Plant Engineer. 11. OTHER PERTINENT INFORMATION OR SPECIAL CONSIDERATIONS. No other pertinent information or special considerations are required to fulfill this service contract. a. Identification of Possible Follow-up Work. There is a possibility of follow-up work that cannot be identified at this time. b. Identification of Potential Conflicts of Interest (COI). There are no known potential conflicts of interest. c. Identification of Non-Disclosure Requirements. N/A d. Packaging, Packing and Shipping Instructions. e. N/A f. Inspection and Acceptance Criteria. The method used for the inspection process will be carried out by direct observation and any documentation or reports provided by the vendor. 12. PLACE OF PERFORMANCE. All services, maintenance tasks and equipment testing performed on the two emergency power generators by the contractor shall be conducted at the VA Cooperative Studies Program Clinical Research Pharmacy Coordinating Center located at 2401 Centre Avenue, SE, Albuquerque NM 87106-4180. 13. PERIOD OF PERFORMACE. The period of performance will be from when the contract is issued to selected contractor until all items listed have been delivered and installed. 14. DELIVERY SCHEDULE. SOW Task # Deliverable Title Format Number Calendar Days After CO Start 7.1 / 7.3 Perform semi-annual level I maintenance service and inspection and an annual level II and maintenance service and inspection on the emergency standby power generator on Model 450ROZD71 / 100REOZJB Per equipment/ manufactures service manuals and check list One (1) time annually and one (1) time Semi- Annually per level of maintenance performed One (1) month and Six (6) months after contract has been issued 7.2 / 7.4 Perform annual load bank test on emergency standby power Generator, Model 450ROZD71 / 100REOZJB Per equipment/ manufactures service manuals and check list One (1) time annually and one (1) time Semi- Annually per level of maintenance performed One (1) month and Six (6) months after contract has been issued 7.5 Refuel both emergency standby generators With Dyed Diesel #2 (per gallon) as needed Upon visual inspection of current fuel level in fuel tank When fuel replenishment is needed After contract has been issued *Standard Distribution: One copy of the transmittal letter without the deliverable to the Contracting Officer shall be emailed. 15. ACRONYMS. A. CO - Contracting Officer. The Federal employee who is warranted by the Government to enter into contracts on behalf of the Government and is the only person authorized to make changes to those contracts. B. COR - Contracting Officer's Representative. Individual designated by the CO to place orders, furnish technical guidance, advice, certify invoices, and provide general supervision of the work performed under the executed contract. C. CSPCRPCC - Cooperative Studies Program Clinical Research Pharmacy Coordinating Center. D. VAMC - Department of Veterans Affairs Medical Center E. NMVAHCS - New Mexico Veterans Affairs Healthcare System