J--Electrical Power Distribution System Preventive Maintenance at the Buffalo VA Medical Center

Awarded
VA24217Q0290Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 811310
New
Kubota M8200 Clutch Replacement
Solicitation # kubota-m8200-clutch-replacement
Management & Training Corporation is soliciting lump sum fee proposals for the diagnosis and repair of a Kubota M8200 tractor clutch assembly at the Earle C. Clements Job Corps Center in Morganfield, Kentucky. The tractor, which features front wheel assist without a cab or loader, is currently out of service due to a clutch malfunction affecting the power take-off system under load. The scope of work requires the contractor to provide all labor, transportation, tools, and manufacturer-specified parts to disassemble the assembly, replace friction discs, bearings, oil seals, and O-rings, resurface the flywheel, and replace necessary hydraulic pipes and filters. Final acceptance is contingent upon the Facility Maintenance Department verifying proper clutch engagement and PTO operation under load. This solicitation is set aside for small businesses, including VOSB, SDVOSB, WOSB, and HUBZone certified firms. Interested bidders must submit a bid sheet, proof of insurance, a completed supplier packet including IRS Form W-9, and applicable SBA certification letters to Angie Mahoney by November 3, 2026, at 3:00 PM CST. Award will be based on best value, with a focus on the contractor's qualifications and experience. The contract incorporates various Federal Acquisition Regulation clauses, including requirements for combating trafficking in persons, equal opportunity for veterans and workers with disabilities, and compliance with Service Contract Labor Standards for wages in Kentucky.
Earle C. Clements Job Corps Center

POSTED

about 3 hours ago

DEADLINE

in 2 days
NAICS: 811310
New
SLED
Conveyance Maintenance Services
Solicitation # 26-1336
Chicago Public Schools is soliciting bids for Conveyance Maintenance Services under solicitation number 26-1336 to implement a comprehensive preventive maintenance program for conveyance equipment. The selected bidder will provide all labor, materials, and supervision necessary to ensure equipment remains safe and operational, adhering to the City of Chicago Municipal Code, ASME A17.1/CSA B44, ASME A17.3, and original equipment manufacturer standards. The contract includes a three-year initial term with the possibility of two automatic renewals of two years each. Services involve monthly preventive maintenance during normal working hours from 6:00 a.m. to 2:30 p.m., as well as 24/7 emergency callback support. Key deliverables include site-specific maintenance schedules, the use of CPS facilities software for reporting, and an annual Executive Summary Report based on a 7-point assessment rubric. The agreement will be awarded to the lowest, responsive, and responsible bidder based on evaluation factors including price, business stability, professional qualifications, past performance, and capacity. Bidders must submit a comprehensive package via Bonfire, including an Excel-based bid tabulation, audited financial statements for the last three fiscal years, three non-Board references, and a W-9 tax form. Compliance with MBE/WBE aspirational goals of 30% and 7% respectively is required, along with adherence to the Illinois Minimum Wage Law and various federal and state non-discrimination acts. Invoicing must be submitted electronically in PDF format, with payments processed according to the Local Government Prompt Payment Act. All shipments are designated as F.O.B. destination. The deadline for questions is November 6, 2026, and the final response deadline is November 20, 2026.
Chicago Public Schools

POSTED

2 days ago

DEADLINE

in 19 days
NAICS: 811310
New
SLED
Annual Inspection/Maint. and Repair on Generator at FMS #8
Solicitation # SRC0000037488
Solicitation SRC0000037488 is for the annual inspection, maintenance, and repair of a Speed Air air compressor (Model 1WD44, SN: D063475) at FMS #8 in Gadsden, Alabama. The scope of work includes replacing belts, collecting oil samples, and installing filters, cabinet filter mats, and repair kits for the oil and thermostatic valves. A mandatory site visit is required on November 18, 2026, at 10:00 AM at 5319 Airport Road, Gadsden, Alabama. The response deadline is November 23, 2026, and all bids must be submitted electronically through the Alabama Buys portal. The contract is managed by the Army MCA and the State of Alabama, with a maximum total value of 25,000 dollars over a potential five-year period, subject to annual renewals. Award evaluation will be based on price reasonableness, cost realism, and supplier qualifications, including professional licenses and insurance. Vendors must comply with the Code of Alabama, including the Beason-Hammon Alabama Taxpayer and Citizen Protection Act and registration requirements for foreign corporations. Payment will be handled electronically via P-cards, EFT, or state-issued credit cards. Final acceptance of services is contingent upon a satisfactory inspection by the State of Alabama in accordance with the Universal Commerce Code.
Army MCA_App 01_Real Property Operations & Maintenance, State Military Department

POSTED

2 days ago

DEADLINE

in 22 days

AI Contract Overview

Show more

This firm fixed price purchase order covers annual electrical preventive maintenance and repair for the electrical power distribution system at the Veterans Affairs Western New York Healthcare System in Buffalo, New York. The contract period runs from March 1, 2017, through February 28, 2018, with two additional option years. The scope includes comprehensive inspection, testing, and adjustment of switchgear, switchboards, transformers, and generators across multiple buildings and substations, adhering to NFPA, OSHA, and NETA standards. The contractor is responsible for providing all tools, personal protective equipment, and qualified technicians with at least five years of experience in similar healthcare or industrial environments. Key operational requirements include the use of infra-red scanning for hot spot detection and detailed liquid-filled transformer analysis. Because the facility provides 24-hour critical care, electrical shutdowns must be minimized, scheduled in advance, and typically performed on weekends or outside normal business hours. The contractor must implement strict infection control measures and ensure that vital systems, such as fire alarms and nurse calls, remain operational. Additionally, the contract mandates the provision of detailed written reports within seven days of each visit and includes 960 annual labor hours for two electricians to address deficiencies, with the VA providing the necessary repair materials.

General Info

Contract Value

$0

NAICS

811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance

Place of Performance

NY, USA

Set-Aside

NONE

Award Issued Date

Documents

0

No documents available

Documents will appear here when they are available.

AI Contract Breakdown

Uniform Contract Format

No documents to break down

The breakdown needs solicitation documents. None were found from this contract's source.

Timeline

2 updates
PhaseAwarded
Posted

Combined Synopsis

Notice updated

The notice description changed.

Notice updated

Notice details unchanged. Attachments may have changed.

Awarded

Contract was awarded

Submission Closed

Find active opportunities like this

Get full access to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → 242-NETWORK Contract Office 02 (36C242)
ContactsNo contacts available
OfficeALBANY, NY, 12208, USA
Office AddressALBANY, NY, 12208, USA
ContactsNo contact information available

Full Description

Show more
A.3 STATEMENT OF WORK This firm fixed price purchase order, to include two option years is for annual electrical preventive maintenance and repair on the Electrical system equipment at the Veterans Affairs Western New York Healthcare System, 3495 Bailey Avenue, Buffalo, New York, 14215-1129, USA facility from 03/01/2017 through 02/28/2018. A.3.1 GENERAL A) The inspection, testing, adjustment and reporting shall comply with the requirements of the latest edition of: NFPA 70 "National Electric Code" NFPA 70B "Recommended Practice for Electrical Equipment Maintenance" NFPA 70E "Standard for Electrical Life Safety in the Workplace" NFPA 110 Standard for Emergency and Standby Power System Occupational Safety & Health Administration (OSHA) Standard 29 CFR 1910, Subparts I & S International Electrical Testing Association, Inc. (NETA) Maintenance and Testing Specifications VHA Directive [2006-056][1028] Electrical Power Distribution System Equipment operating/manufacture's instruction. These may be obtained from the VHA Medical Center, or the equipment manufacturers. When a conflict arises between a method called for in NFPA 70, 70B & 70E and the equipment manufacturer, the VA will be notified in order to provide direction. Contractor shall supply all services, tools, personal protective equipment (PPE), material and equipment required to comply with the references above. B) Contractors shall have technical training and demonstrable track records of working experience in maintenance, inspection, testing and repairing of the electrical power distribution systems and related components in healthcare, industrial, education, and commercial facilities for a minimum of five (5) consecutive years. Electrical components on which the Contractors have experience shall include, but not be limited to, switchboards & switchgear (low and medium voltage); low voltage controls, emergency and standby generators; automatic transfer switches, wiring, transformers, meters and other electrical appurtenances. C) All work shall be performed, using properly trained technicians. A copy of all licenses and certifications, including NFPA 70E, OSHA safety, and any other industry-specific training for each technician shall be submitted to and must be approved by the Contracting Officer (CO) before any work may be performed by that technician. At any time the Contracting Officer s Representative (COR) may deem any tool, technician, or method unacceptable based on this authority of inspection/acceptance of services. D) The Contractor shall provide a proposed schedule with their quote proposal. The schedule shall be in the form of a progress chart of suitable scale to indicate the work scheduled for completion by any given date during the work period. The proposed schedule shall be reviewed by the Contracting Officer Representative (COR). Any requirements for adjusting the schedule (e.g. to minimize disruption to the VAMC) shall be incorporated by the Contractor. E) Contractors shall report deficiencies that are deemed critical or catastrophic immediately to the CO and the COR for immediate actions. F) The VA agrees to provide the Contractor free access to all equipment necessary to conduct work, free access to rooms or areas housing such equipment and to supply suitable electric power (if necessary) to complete the task. Contractor to provide a qualified Electrician to remove all access panels to equipment. In the event that it becomes difficult for the Contractor to complete testing because of patient care related activities or security issues, the Contractor shall not be obligated to complete testing in the area of concern at the time of their scheduled visit. They will be obligated to complete their work at the time of the next scheduled visit to the facility. The final authority relative to this decision will be the COR. Unless fully absolved by the VA, Contractor shall responsible for completing all work. G) Work being performed inside the facility shall require infection control measures. This may include negative pressure equipment and isolation barriers. The contractor shall be responsible for installation and removal of these measures and shall meet with the COR and Infection Control Department to determine specific needs for each task. H) At no time can the fire alarm, nurse call or other vital system be out of service. The contractor shall ensure they do not compromise any of these systems or other elements of the life safety system such as removal of ceiling tile. I) Upon award of purchase order, an electrical study for the facility shall be made available for Contractor use upon request. J) Performance shall be monitored by the COR by quarterly or as needed review. A.3.2 SCHEDULE Contractor shall provide a detailed schedule and advance notice before arriving on station to begin any work as described herein. This advance notice must permit the VA to notify personnel in the affected buildings of the impending work. In no instance will this advance notice be less than 72 hours. The contact person for all advance notices will be the facility Engineering Department at +1 (555) 000-0000. A) The following are Federal Holidays observed by the facility and the Contractor shall not expect access to the VA Facility of VA employees on these dates unless notified otherwise by the COR. Preventive maintenance or other services are not to be scheduled on these dates: New Year's Day Birthday of Martin Luther King, Jr. Washington's Birthday Memorial Day Independence Day Labor Day Columbus Day Veterans Day Thanksgiving Day Christmas Day B) The facility is a health care facility providing critical care 24 hours a day; as such disruptions in operations are not feasible and will need to be coordinated closely with the COR. Electrical work requiring shutdown may not be feasible and work may have to be conducted live. All electrical work requiring an electrical shutdown will be conducted on weekends and/or outside of normal hours. Shutdowns will be minimized to as short of duration as possible. All shutdown requests will require detailed work plans and scheduling prior to approval. Work not requiring an electrical shutdown may take place during normal duty hours: Monday-Friday, 7:30am-4:00pm. Requests to conduct work on weekends and outside of normal duty hours must be submitted in writing at least 7 working days in advance of the anticipated work to the facility Engineering Department, 3495 Bailey Ave, Buffalo, New York 14215-11129, +1 (555) 000-0000. If this new schedule is agreed upon, work can begin. The original written request will remain with all test documents along with any written agreements relative to the original requests. A.3.3 REPORTS Contractor shall provide a complete written report of the work performed to the VA Contracting Officer within seven (7) calendar days of visit. Four (4) hard copies as well as one (1) CD-ROM or DVD of the electronic version of the report in Microsoft Word Format to the Chief of Engineering Service. All reference materials shall be included in the electronic version of the report, either through scanning or other means of electronic text import methods. This report shall be typed, dated and signed. The report shall include the following: Company s name, addresses, telephone numbers. Name and signature of contractors who perform the maintenance and testing. VA Work Contract Number, name and number of VA Contracting Officer. Date and Time of work. Copies of contractors valid licenses, professional and training certificates. Descriptions and model number of specialized tools and equipment used, such as torque wrench or infra-red scanning camera. Location, Type, Name, and nameplate information of electrical equipment to be maintained and tested. Descriptions of work items. Test data. Reference materials such as equipment manufacturer s specifications, coordination study, etc. Remarks on conditions of electrical equipment. List all deficiencies, if any. Recommended corrective actions, if any. Contractors shall report deficiencies that are deemed critical or catastrophic immediately to the CO and COR for immediate actions. Report shall include a list of all parts required to perform repairs listed. A.3.4 PREVENTATIVE MAINTENANCE Contractor shall inspect, test and adjust/lubricate the Electrical Systems per the following schedule. A.3.4.1 YEAR 1 The following work shall be performed while the Electrical Power Distribution System is energized. Appropriate safety precautions shall be taken before, during and after scanning the system. Infra-Red Scanning: A) Use an infra-red scanning camera to detect hot spots in the Electrical Power Distribution System. Objective of this work is to detect any loose, broken, or corroded connections in the system. Problem connections shall be replaced with new connectors, and/or tightened with torque wrench to meet equipment manufacturers specifications. B) The following are general inspections and testing: 1) Transformers, Liquid-Filled. Analysis will include: Gas in Oil Analysis Water Content Acid Content Interfacial Tension Color Analysis Dielectric Strength Specific Gravity C) The following work shall be performed with the Electrical Power De-energized: 1) Inspection and Testing of Switchgear and Switchboard Assemblies of Building #18, Substations G and H including: a) 5,000 volt equipment including: I) (2) fused load interrupter switches II) (2) 1,000 Kva outdoor Pad-mount oil transformers b) 208 Volt draw-out circuit breakers including: I) (2) main breaker, 3,000 amp II) (1) tie breaker, 1,600 amp III) (4) active feeder breakers and (1) spare breaker IV) (lot) substation protective relays and meters 2) Inspection and Testing of Switchgear and Switchboard Assemblies of Building #11, Substations A and B including: a) 5,000 volt equipment including: I) (2) transfer switches II) (2) 1,500 Kva outdoor Pad-mount oil transformers b) 480 volt draw-out circuit breakers including: I) (2) main breaker, 2,400 amp II) (1) tie breaker 2,400 amp III) (7) active feeder breakers and (2) spare breakers IV) (lot) substation protective relays and meters 3) Inspection and Testing of Switchgear and Switchboard Assemblies of Building #11, Substations C and D including: a) 5,000 volt equipment including: I) (2) transfer switches II) (2) 1,000 Kva outdoor Pad-mount oil transformers b) 208 volt draw-out circuit breakers including: I) (2) main breaker, 3,000 amp II) (1) tie breaker 3,000 amp III) (3) active feeder breakers and (3) spare breakers IV) (lot) substation protective relays and meters 4) Inspection and Testing of Switchgear and Switchboard Assemblies of Building #6, Substations E and F including: a) 5,000 volt equipment including: I) (2) fused load interrupter switches II) (2) 500 Kva indoor dry-type oil transformers b) 480 volt circuit breakers including: I) (2) main breaker, 800 amp II) (1) tie breaker 600 amp III) (lot) substation protective relays and meters 5) Inspection and Testing of Switchgear and Switchboard Assemblies of Building #20, Research Building Substation including: a) 5,000 volt indoor switchgear including: I) (1) parallel feed line selector switch II) (1) fused load interrupter switch b) (1) 1,500 Kva indoor dry-type transformers c) 480 volt circuit breakers including: I) (1) draw-out main breaker, 3,000 amp II) (9) active feeder breakers and (7) spare breakers III) (lot) substation protective relays and meters A.3.4.2 YEAR 2 The following work shall be performed while the Electrical Power Distribution System is energized. Appropriate safety precautions shall be taken before, during and after scanning the system. Infra-Red Scanning: A) Use an infra-red scanning camera to detect hot spots in the Electrical Power Distribution System. Objective of this work is to detect any loose, broken, or corroded connections in the system. Problem connections shall be replaced with new connectors, and/or tightened with torque wrench to meet equipment manufacturers specifications. B) The following are general inspections and testing: 1) Transformers, Liquid-Filled. Analysis will include: Gas in Oil Analysis Water Content Acid Content Interfacial Tension Color Analysis Dielectric Strength Specific Gravity C) The following work shall be performed with the Electrical Power De-energized: 1) Inspection and Testing of Switchgear and Switchboard Assemblies of 3rd floor, Building #20, Chiller Substation including: a) 5,000 volt indoor switchgear including: I) (1) parallel feed line selector switch II) (1) fused load interrupter switch III) (2) fused lead interrupter switches feeding chillers IV) (2) chiller starters b) (1) 1,500 Kva indoor dry-type transformers c) 480 volt circuit breakers including: I) (1) draw-out main breaker, 3,000 amp II) (9) active feeder breakers and (7) spare breakers III) (lot) substation protective relays and meters 2) Inspection and Testing Chiller Room S22, Chiller Substation including: a) 5,000 volt indoor switchgear including: b) (1) parallel feed line selector switch c) (3) fused load interrupter switches d) (1) chiller starter 3) Inspection and Testing of Substations UB-1 and UB-2 including: a) (2) dry-type transformers b) (2) low voltage fixed mount molded case circuit breakers 4) Inspection and Testing of Building 28, chiller Substation including: a) 5,000 volt indoor switchgear including: I) (1) parallel feed line selector switch II) (4) fused load interrupter switches III) (1) 1,000 Kva dry-type transformer 5) Inspection and Testing of Building 1, Substation USS-15, Room S-15 including: a) 5,000 volt indoor switchgear including: I) (1) lead interrupter switch II) (1) 500 Kva dry-type transformer b) 208 volt circuit breakers including: I) (1) main breaker, 1600 amp II) (12) feeder breakers A.3.4.3 YEAR 3 The following work shall be performed while the Electrical Power Distribution System is energized. Appropriate safety precautions shall be taken before, during and after scanning the system. Infra-Red Scanning: A) Use an infra-red scanning camera to detect hot spots in the Electrical Power Distribution System. Objective of this work is to detect any loose, broken, or corroded connections in the system. Problem connections shall be replaced with new connectors, and/or tightened with torque wrench to meet equipment manufacturers specifications. B) The following are general inspections and testing: 1) Transformers, Liquid-Filled. Analysis will include: Gas in Oil Analysis Water Content Acid Content Interfacial Tension Color Analysis Dielectric Strength Specific Gravity C) The following work shall be performed with the Electrical Power De-energized: 1) Inspection and Testing of Building #9: a) 5,000 volt outdoor switchgear including: I) (15) draw-out vacuum circuit breakers including: i) (2) main breakers ii) (2) tie breakers iii) (9) feeder breakers and (2) spare breakers II) (lot) substation protective relays and meters 2) Inspection and Testing of Main Service Entrance Building #9A: a) 23,000 volt outdoor switchgear including: I) (3) incoming utility section II) (3) utility line isolation switches III) (3) main reclosers IV) (lot) surge arrestors V) (3) 3750 Kva outdoor substation transformers VI) (1) capacitor bank VII) (2) main breakers VIII) (3) feeder breakers and (1) spare breaker IX) (lot) substation protective relays and meters A.3.5 REPAIR SERVICES Contractor shall include 960 hours of work for two (2) qualified electricians (480 hours each person) to complete the deficiencies and defects identified in inspection report during each year of the contract. This effort is separate from the repairs listed in section A.3.4 above. The contractor shall be required to provide all travel and labor to perform repairs. The Department of Veterans Affairs shall provide all materials/parts to perform the repairs. The contractor shall provide a weekly progress report on repairs made, materials expended, and issues to be addressed by COR.

More opportunities from Department Of Veterans Affairs → 242-NETWORK Contract Office 02 (36C242)

Same awarding agency

NAICS: 621999
New
Federal
Q525--LASER SERVICES - BUFFALO UROLOGY Holmium (30 and 80 Watt) Lasers CO2 Laser Lithotripsy (ESWL) Laser
Solicitation # 36C24227Q0105
The Department of Veterans Affairs, through Network Contracting Office 2, is conducting market research via a Request for Information for an anticipated five-year contract to provide laser services at the Buffalo VA Medical Center. The scope of work includes the provision of Holmium (30 and 80 watts), CO2, and Lithotripsy (ESWL) laser units, all necessary supplies and disposables, and New York State certified technicians. The contractor will be responsible for all labor, supervision, and equipment maintenance, ensuring all units operate according to manufacturer specifications. A critical technical requirement is that all equipment must plug directly into wall outlets without adapters or transformers, as the surgical suites are wired for 30amps and 240 volts or less. The contractor must maintain up-to-date preventative and corrective maintenance records for the Biomedical Engineering Department and complete Laser Use Records for every case. Liability for patient injury resulting from laser malfunction rests with the contractor. This effort falls under NAICS code 621999, with a small business size standard of 20.5 million dollars. Interested respondents must be registered in the System for Award Management and submit a capability statement not exceeding 12 pages by 4:00 PM Eastern Time on November 20, 2026. Responses must include detailed equipment specifications, a history of experience with the VA or other entities, and specific company identification and socioeconomic status details.
All Other Miscellaneous Ambulatory Health Care Services

POSTED

2 days ago

DEADLINE

in 19 days
View Details
NAICS: 562910
New
Federal
F108--620-26-206 Asbestos Abatement
Solicitation # 36C24227R0010
Solicitation 36C24227R0010 is a firm-fixed-price contract issued by the Department of Veterans Affairs, Network Contracting Office 2, for traditional asbestos abatement services at the Montrose VA Medical Center in New York. This procurement is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) with an estimated construction magnitude between $100,000 and $250,000. The scope of work involves the removal, clean-up, and disposal of approximately 2,300 square feet of asbestos-containing floor mastic, carpet, and levelers, as well as 100 linear feet of radiator panel insulation and heat shields. The project must be completed within 365 calendar days from the notice to proceed and may require evening or weekend operations to minimize disruption to facility occupants. Award will be based on a comparative evaluation of technical capability, past performance, and price. Offerors must demonstrate relevant experience with at least two similar projects completed within the last five years and possess valid New York State asbestos-abatement licenses and certifications. Strict adherence to OSHA, EPA, DOT, and NESHAP regulations is required, particularly regarding the double-bagging and decontamination of waste. The contract is subject to the Davis-Bacon Act and requires the submission of Buy American and Limitations on Subcontracting certifications. Performance and payment bonds are mandatory if the final contract value exceeds $150,000. Proposals are due by November 13, 2026.
Remediation Services

POSTED

2 days ago

DEADLINE

in 19 days
View Details
NAICS: 621511
New
Federal
Q301--Reference and Esoteric Laboratory Testing
Solicitation # 36C24227R0003
The Department of Veterans Affairs, Network Contracting Office 2, is soliciting a firm-fixed-price requirements contract for comprehensive reference and esoteric laboratory testing services to support five VA Medical Centers within the Veterans Integrated Service Network 2 South. The scope of work encompasses a wide array of clinical diagnostic send-out testing, including esoteric, oncology, and molecular diagnostic services. The contractor is responsible for providing all necessary specimen collection and preservation materials, ensuring secure transportation to maintain specimen integrity, and maintaining 24/7 availability. Key technical requirements include a mandatory electronic interface with VA VistA/LEDI software, adherence to VA cybersecurity directives, and the maintenance of current CLIA, CAP, NYSDOH, and NJDOH licenses. The Laboratory Director must be a certified Bio-Analyst or an American Board of Pathology certified Pathologist. The contract is intended to run through December 31, 2031, although current funding is only available through December 31, 2027, with an option to extend services for up to six months. Award will be made to the lowest-priced technically acceptable offeror based on an evaluation of technical capability, relevant experience, and past performance. Proposals must include fully burdened pricing for a detailed list of CPT-coded and catalog tests, as well as a current VA Memorandum of Understanding/Interconnection Security Agreement. Administrative requirements include monthly invoicing in arrears via the Tungsten Network, with separate invoices submitted for each facility.
Medical Laboratories

POSTED

2 days ago

DEADLINE

in 29 days
View Details
NAICS: 811210
New
Federal
J065--FY27 SERVICES (BASE+4) - Canon CT Service Contract
Solicitation # 36C24227Q0076
Solicitation 36C24227Q0076 was a firm-fixed-price request for quote issued by the Department of Veterans Affairs, Network Contracting Office 2, for the annual preventative maintenance and repair of two Canon/Toshiba Aquilion Prime 160 CT machines located at the Buffalo VA Medical Center. The requirement was set aside for Service-Disabled Veteran-Owned Small Businesses under NAICS code 811210. The proposed contract structure consisted of a base period from November 1, 2026, to October 31, 2027, with four subsequent option years. The scope of work required preventative maintenance to be performed four times per year, a 30-minute telephone response time for corrective repairs, and an on-site engineer response time of 4 to 6 hours. The government intended to award the contract to a responsible offeror based on a comparative evaluation of technical capabilities, past performance, and price. Contractors were required to provide all labor and parts, with new parts warranted for 12 months. Compliance requirements included adherence to manufacturer specifications, patient information confidentiality, and the maintenance of commercial general liability insurance. Despite the detailed solicitation and subsequent amendments to extend the submission deadline to October 28, 2026, the solicitation is now closed with no award made.
Electronic and Precision Equipment Repair and Maintenance

POSTED

2 days ago

DEADLINE

in about 24 hours
View Details
NAICS: 238110
New
Federal
Z2NZ--Manhole Repairs at Montrose VAMC
Solicitation # 36C24227R0012
Solicitation 36C24227R0012 is a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside procurement issued by the Department of Veterans Affairs for the rehabilitation and repair of two underground utility manholes at the Montrose VA Medical Center in Montrose, New York. The project scope includes the demolition of existing concrete lids and frames, pumping and cleaning of manhole vaults, concrete rehabilitation, waterproofing, and the restoration of surrounding asphalt surfaces to ensure structural integrity and prevent water infiltration. The estimated magnitude of construction is between $25,000 and $100,000, with a performance period of 60 to 99 calendar days following the Notice to Proceed. Proposals are due by 1:00 PM EST on November 12, 2026, and will be evaluated based on technical capability, past performance, and price. Technical evaluations will focus on the offeror's approach to concrete rehabilitation and utility protection, while past performance requires documentation of at least one similar project completed within the last five years. Awardees must comply with the Davis-Bacon Act, Buy American requirements, and VAAR limitations on subcontracting. Additionally, the contractor must be certified by the coating product manufacturer for the application of materials and provide daily logs to the VA COR to track progress and quality control.
Poured Concrete Foundation and Structure Contractors

POSTED

2 days ago

DEADLINE

in 10 days
View Details

Earlier notices in this NAICS code

Posted before this notice, open and closed

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS