J061--Sources Sought - Generator Testing, Maintenance, and Repair Services Black Hills Healthcare System

Closed
36C26326Q0697Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

AI Contract Overview

Show more

The Black Hills Healthcare System is seeking vendors to provide semi-annual generator testing, maintenance, and emergency repair services for critical emergency power systems at its Fort Meade and Hot Springs VA Medical Centers, with potential service to mobile units in Rapid City. The scope includes comprehensive preventive inspections and load bank testing of multiple emergency generators across several buildings, including high-capacity systems such as a 2000KW, 12,470-volt generator at Building 155 and smaller units ranging from 10KW to 400KW on various platforms from Cummins, Marathon, Generac, Onan, Kubota, and John Deere. Inspections are to be conducted twice yearly during October/November and May/June, with detailed reports submitted within 30 days, and annual load bank testing must adhere strictly to NFPA 110 standards with specified load profiles. Emergency repair services require a four-hour response time, and contractors must be prepared to provide standby backup generators while primary units are out of service. Any repairs exceeding $2,500 require formal written approval and a bilateral supplemental agreement, while minor repairs may be authorized via Government Purchase Card. Fluid testing must be performed by third-party laboratories and reported to the Contracting Officer’s Representative, and all work must comply with security, privacy, and HIPAA regulations as outlined in VA policy 6500.6 Appendix C and NARA guidelines. All personnel must complete required training and sign documentation, and contractors are prohibited from leaving generator systems in non-automatic or unattended mode without explicit approval. Contractors must respond to this market research solicitation by May 26th, 2026, via email to Joseph Bloomer, including their organization’s socioeconomic classification, identification of any existing government contracts under which the services could be ordered, and disclosure of any planned subcontracting, including percentage and scope. While no contract award will result from this solicitation, responses are critical to shaping future procurement strategy and may trigger application of FAR 52.219-14 or VAAR 852.219-75 subcontracting limitations depending on the vendor’s size and veteran-owned status. The work will occur at designated VA facilities in Fort Meade and Hot Springs, South Dakota, during standard business hours, with after-hours work requiring coordination. Contractors are responsible for all tools, parts, fluids, labor, and diagnostic capabilities, and must submit written corrective action plans if the same issue recurs on a

General Info

Seeking vendors for semi-annual emergency generator maintenance at SD VA Medical Centers, no contract awarded.

NAICS

811210 - Electronic and Precision Equipment Repair and Maintenance

Place of Performance

Black Hills HCS Fort Meade & Hot Springs Campuses, Fort Meade, SD, 57741, USA

Set-Aside

NONE

Documents

1

Sources Sought - Generator Testing, Maintenance, and Repair Services Black Hills Healthcare System 36C26326Q0697

DOCX, Low prioritysources-sought
Low

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

PhaseClosed
Posted

Sources Sought

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Get full access to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → Network Contract Office 23 (36C263)
Contacts1 person available
OfficeSaint Paul, MN, 55101, USA
Office AddressSaint Paul, MN, 55101, USA
Contacts
Joey BloomerContracting Officer

Full Description

Show more
The Black Hills Healthcare System requires Generator Testing, Maintenance, and Repair Services in accordance with the draft Statement of Work (SOW) below. This is a sources sought/proof of capability solicitation looking for vendors to perform the services per the SOW for market research purposes. No award of a contract will be made from this announcement. If you are a vendor that can complete the work described in the SOW with competitive pricing, please send your contact and organization information with a descriptive proof of capability to: Joey Bloomer, contact@example.gov on or before May 26th, 2026. Only emailed responses will be considered. Additionally, provide answers as appropriate to the following questions in the table below with your response to this sources sought. Failure to respond to the following questions may affect the acquisition strategy. 1. Identify your organization's socio-economic category.
2. State whether any of the requested services may be ordered against a government contract awarded to your organization (e.g Federal Supply Schedule (FSS), General Services Administration (GSA), etc.).
3. State if subcontracting is contemplated for this requirement and what percentage of the work will be subcontracted and for what tasks.
  *If applicable, VAAR 852.219-75 VA Notice of Limitations on Subcontracting Certificate of Compliance for Services and Construction, will apply to the potential solicitation if set-aside for Veteran Owned Small-Businesses or Service Disabled Veteran Owned Small-Businesses.* *If applicable, FAR 52.219-14 Limitations on Subcontracting, will apply to the potential solicitation if set-aside for Small-Businesses.*
STATEMENT OF WORK Semi-Annual VA BHHCS Emergency Generator Testing and Maintenance
1. SCOPE Provide semi-annual preventive maintenance inspections and services on emergency generators at the VA medical Centers at Ft Meade and Hot Springs, South Dakota and VA clinic in Rapid City (if mobile units are in place there). The Fort Meade campus has a 12470-volt primary system that includes various secondary voltages and both normal and emergency power sources. Inspection reports from attachments A & B to be provided to facilities POC s within 30 days of service.
2. CONTRACT POC S FOR SCHEDULING WORK AND COORDINATION ARE AS FOLLOWS: Fort Meade VAMC: Delane Erickson, Operations Supervisor, Phone: +1 (555) 000-0000 Hot Springs VAMC: Dan Cerveny, Maintenance Supervisor, Phone +1 (555) 000-0000
3. EQUIPMENT Fort Meade Emergency Generator equipment included in the scope of work is as follows: A. Bldg. 113 Emergency Generator Manufacturer: Cummins/ 750 KW/ 480V Generator Model; DQCB-1641706 / Serial Number: K160128689 Engine Model: QSK23G7 / Serial Number: 85002334
B. Bldg. 148 Emergency Generator Manufacturer: Cummins/ Onan/ 125 KW/ 480V Generator Model: DSGAB- 1321187 / Serial Number: B130456361 Engine Model: QSB7 G5 NR3 / Serial Number: 73494119
C. Bldg. 145 Emergency Generator Manufacturer: Cummins/ 250 KW / 208V Generator Model: DQDAA-1660802 / Serial Number: L160128689 Engine Model: QSL9-G7 / Serial Number: 74068824
D. Bldg. 137 Generator Manufacturer: Cummins/ Onan/ 100 KW/ 208V Generator Model: DSGAA- 1321189 / Serial Number: B130456362 Engine Model: QSB7 G5 NR3 / Serial Number: 73493506
E. Bldg. 160 Generator Manufacturer: DMH/ 165 KW/ 480V Generator Model: 200CL3 / Serial Number: 94-45-74-1 Engine Model: LTA-1062/ Serial Number: 34737406
F. Bldg. 155 Main Station Generator Manufacturer: Marathon / 2000KW / 12470V Generator Model: 1020FDH1242 / Serial Number: WA-6003864-0717 Engine Model: CD2000SX6T2 / Serial Number: 179811-1-1-1108
G. Bldg. T296 Fire Station Generator Manufacturer: Cummins/ Onan/ 16.8KW/ 240V Generator Model; DSKCA-193329 / Serial Number: L090070761
3. Hot Springs VAMC Emergency Generator equipment included in the scope of work is as follows: A. Bldg. 10 Emergency Generator Manufacturer: Marathon MTU/ 250KW/ 480V Generator Model: 573RSL4033/ Serial Number: MT-0132187-0223 Engine Model: 10V1600 / Serial Number: 95010501432
B. Bldg. 12 Emergency Generator Manufacturer: Generac/ 400KW/ 208V Generator Model: 433RSL4021/ Serial Number: LM-239579-0701 Engine Model: OA8829/ Serial Number: 8DC9-446846
C. Bldg. 18 Emergency Generator Manufacturer: Onan/ 230KW/ 208V Generator Model: 230DFAB / Serial Number: A980673745 Engine Model: LTA10-G1 / Serial Number: 12079
F. Bld. 66 Emergency Generator Manufacture: Cummins/ 125KW/ 208V Generator Model 125 DSGAB Engine Model: QSB7-G5 NR3
* Can be at any VA Medical Center locations: A. Mobile MRI Emergency Generator Manufacturer: Kubota Generator Model: V3800-T Serial Number: 2JS2095 45 KW / 480V B. Mobile CT Emergency Generator Manufacturer: John Deere Generator Model: 4045 / 100K / 480V
C. Mobile Morgue Trailer Emergency Generator Manufacturer: Kubota Generator Model: GL11000-USA Serial Number: 10 KW / 240V
4. SEMI-ANNUAL INSPECTIONS Semi-annual inspections shall be completed within October/November (Attachment A) and within May/June (Attachment B), and inspection reports shall be provided to the VAMC POC s within 30 days of completion of work. Work shall be scheduled 7 days in advance of planned work to minimize disruption to the facility. The scope of October/November inspections and testing shall include all work outlined in Attachment A. The scope of May/June Inspections will include all work outlined in Attachment B.
5. ANNUAL LOAD BANK TESTING
Annual load bank testing included in Attachment A shall be accomplished in accordance with NFPA 110 (99) Sec 6-4.2.2. The testing shall be documented, and supplemental loads included at 25 percent of the name plate rating for 30 minutes. Followed by 50 percent of the nameplate rating for 30 minutes. Followed by 75 percent for 1 hour. All emergency generators will be load-bank tested annually. The Main station generator BLDG. 155 will be load-bank tested every other year starting with the first option year of the contract. Automatic Transfer Switches will be included in the semi-annual test for the Emergency Power Supply System (EPSS). This would consist of a transfer without load and resistance or amp drop reading depending on the state of the contacts.
6. CONTRACTOR RESPONSIBILITIES All supplies, fluid testing, filters, fluids, parts, tools, and labor will be supplied by the Contractor. Contractor is to diagnose other or larger problems and present quotes to the POC for approval, before additional work is conducted. Fluid testing will need to be conducted by 3rd party tester semiannually, and the report shall made to POC/COR within 30 days of service. The Contractor should provide priority for repairs to the BHHCS VA Emergency Generators and ATS Switches.
5. WORK HOURS Planned maintenance and testing shall occur Monday through Friday, 8:00 AM to 4:00 PM, excluding federal holidays. If the work needs to be partly outside of standard VA business hours, to minimize patient impact, scheduling with the COR/POC will be required. Emergency services shall be available with a four (4) hour response time.
6. CHECK-IN PROCEDURE Technicians must report to the contract POC at their respective location prior to beginning work.
7. SITE ADDRESSES The addresses of the VA Black Hills Health Care System is listed below. Hot Springs VAMC is located at 500 5th Street, Hot Springs, South Dakota 57747 Fort Meade VAMC is located at 113 Comanche Road, Fort Meade, South Dakota 57741
8. REPAIRS Any necessary repair/replacement parts or services created by testing of the equipment as part of this contract will be furnished/paid for by the facility and these repairs will be completed on an emergency basis. This designation will require the Contractor to stand down during repairs and to continue testing as soon as practical after the repairs have been made. During the time that the generator remains out of service, the Contractor will be required to connect and maintain their standby/backup generator and associated automatic connection equipment. The backup emergency generators shall provide service until all emergency repairs have been completed, and the successful load bank testing procedures have reached a satisfactory conclusion. The Contractor s responsibility for additional rental outlays due to this requirement shall be limited to standby service. Minor repairs shall include, but not be limited to such items as loose bolts, loose or broken lugs, wiring terminals, malfunctioning targets, dirty/high resistance connections, etc. and shall be corrected on site during testing if possible. The POC/COR can authorize requests for non-emergency repairs if they are submitted in writing and do not exceed $2,500, executed through Government Purchase Card (GPC) transaction. All requests for repairs shall be in writing with a detailed explanation, cost of parts, labor and all associated costs to complete repairs. Any repair that exceeds the $2,500 threshold shall require Contracting Officer approval prior to the ordering of parts or execution of services. The Contractor shall submit their request for repair to the CO and POC/COR. The repair quote shall be a detailed explanation and breakdown of costs. Authorized repairs shall be executed through a bilateral supplemental agreement on the contract between both parties if service costs exceed $2,500.
11. EMERGENCY REPAIRS Contractor shall provide a four-hour response time for call back service from the time a call for service is made by the Contracting Officer, Facilities Management Officer, POC/COR, or their designees. Contractor will be on site within this four-hour time frame, unless the situation isn t considered an emergency, and another mutually agreed upon time will meet the government s needs. The Contractor must be able to properly troubleshoot and diagnose all aspects of emergency generators. The Contractor shall provide all labor, materials and equipment for the emergency callback services for all generators at the Hot Springs and Fort Meade (Sturgis) VA Medical Centers, if the supplied quote is selected, and in accordance with specifications included in this scope of work. The Contractor shall submit a written plan of action to the Contracting Officer, or POC/COR, whenever unresolved problems occur three times on the same generator. Whenever the same problem recurs on the same generator three times, the VA requires an analysis of the corrective action required to resolve the problem. When generator systems fail, and require emergency repairs, the technician s Supervisor shall provide the BLACK HILLS HCS with a written statement and itemized quote assessing the generators system failure and that they have verified the generator system has been properly diagnosed and concur with the technician s assessment. The VA reserves the right to enlist a third-party expert to provide a 2nd opinion. It is the responsibility of the Contractor to reassess their proposed repairs and either reaffirm or correct their proposal based on the expert s notes. The reassessment shall include at a minimum, a substantive analysis of the third-party expert s points that contradict the Contractor s original conclusion. This reassessment shall be submitted within 5 business days of receipt of the third-party expert s opinion.

12. COORDINATION The contractor shall be responsible for coordinating any necessary utility system shutdowns and returning these systems to operational mode. In addition, the contractor must notify VA Facilities Management Service COR before any systems are shut down and when these systems are put back into full service. The contractor will not be permitted to leave any emergency generator system or component in a non-automatic connected mode or unattended mode during any portion of the testing. Should such non-automatic circumstances exist the contractor must have the approval of the Chief, Facilities Management Service. The contractor shall be responsible for any damage due to negligence to equipment that is created while performing the services required in this contract. Equivalent loads used for testing shall be connected such that they can be automatically replaced with emergency loads in case of failure of the primary power source.
13. TRAINING, SECURITY AND NARA REQUIREMENTS ALL Contractors on-site shall complete required training. Each contractor is required to print, review, and sign the attached TMS 20939 document. Contract owner/supervisor must send signed TMS 20939 documents to the contract COR.
6500.6 Appendix C Security and NARA PRIVACY-HIPAA CLAUSE a. ALL Contractors on-site shall read and comply with attached 6500.6 Appendix C Security and NARA PRIVACY-HIPAA CLAUSE documents.
See Attachment C for Security and Attachment D For NARA.

More opportunities from Department Of Veterans Affairs → Network Contract Office 23 (36C263)

Same awarding agency

NAICS: 811310
New
Federal
J039--JLG Boom Lift Hydraulic Leak Repairs - STC (VA-27-00010304)
Solicitation # 36C26327Q0084
The Department of Veterans Affairs, Network Contracting Office 23, is issuing a sources sought notice for market research to identify qualified contractors for hydraulic repairs on a JLG Boom Lift, Model 600S, at the St. Cloud VA Health Care System in Minnesota. Under NAICS code 811310, the required services include replacing all hydraulic hoses through the cat track, replacing the hydraulic line from the pump to the block, replacing hydraulic oils, and updating the basket display decal and operator and ANSI manuals. The selected contractor must be located within a 100-mile radius and will be responsible for the pickup and delivery of the equipment to and from the St. Cloud VA campus. All repairs must be completed within three weeks of the contract award and must meet industry and manufacturer operational standards. This notice is not a formal solicitation and does not obligate the government to award a contract. Interested parties must submit their company information, including DUNS and SAM Unique Entity ID, a capability statement, and their socio-economic size classification to Contract Specialist Evan Beachy by 4:00 PM Central Time on November 04, 2026. Additionally, respondents should specify if the procurement can be handled through GSA, FSS, SEWP, or other existing contract vehicles. Responses are intended solely for planning purposes to help the government make informed acquisition decisions.
Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance

POSTED

1 day ago

DEADLINE

in 6 days
View Details
NAICS: 811210
New
Federal
J065--Karl Storz Support Services IDIQ VISN
Solicitation # 36C26327Q0022
The Department of Veterans Affairs Network Contracting Office 23 is soliciting a brand-name only, five-year Indefinite Delivery, Indefinite Quantity (IDIQ) contract for OEM-certified support and service of Karl Storz OR1 Video Integration Systems across the VISN 23 Healthcare System. This requirement, managed under simplified acquisition procedures, covers multiple locations including Minneapolis, St. Cloud, Fargo, Central Iowa, Iowa City, Black Hills, and Sioux Falls. The scope of work includes preventive and corrective maintenance, replacement parts, software and firmware updates, cybersecurity compliance, and technical training for clinical and biomedical staff. The contract has a guaranteed minimum value of 300,000 dollars and a maximum lifetime cost limitation of 5,600,000 dollars. Award will be based on a comparative evaluation of price and technical factors, including vendor qualifications, cybersecurity capabilities, and service level agreement response times. The contractor must adhere to strict OEM standards, NIST calibration requirements, and VA security policies, including the submission of cybersecurity artifacts and a signed Business Associate Agreement for HIPAA compliance. Performance will be monitored via a Quality Assurance Surveillance Plan targeting 98.9 percent operational uptime and 99 percent response time rates. Offers are due by November 11, 2026, and must include a signed SF 1449, completed pricing schedules, and proof of OEM certification for technicians.
Electronic and Precision Equipment Repair and Maintenance

POSTED

2 days ago

DEADLINE

in 13 days
View Details
NAICS: 238330
New
Federal
Replace Operating Room 5 Flooring
Solicitation # 36C26327Q0019
Solicitation 36C26327Q0019 is a Service-Disabled Veteran-Owned Small Business set-aside for the Department of Veterans Affairs, Network Contracting Office 23. The project involves providing all labor, materials, tools, and supervision to remove and replace the flooring and subflooring in Operating Room 5 (Room 4211, Building 1W) at the Des Moines VA Medical Center in Iowa. The work must be completed within 120 calendar days following the Notice to Proceed. Award will be granted to the responsible, eligible quoter who submits the lowest-priced acceptable quotation that meets all solicitation requirements, provided the price is determined to be fair and reasonable. Key technical requirements include conducting asbestos survey testing, adhering to the Architectural Design Manual, and utilizing certified installers through INSTALL or a comparable four-year apprenticeship program. The contractor must provide a floor tile mockup of 100 square feet to establish quality standards and comply with strict packaging and marking regulations for asbestos waste and HEPA filters. Administrative requirements include the submission of an Accident Prevention Plan and Site-specific Safety Plan for COR approval, as well as the provision of payment bonds or irrevocable letters of credit for contracts exceeding 35,000 dollars. The contract is subject to the Davis-Bacon Act and Buy American requirements, with specific limitations on subcontracting to ensure a minimum of 15 percent of the work is performed by the prime SDVOSB contractor.
Flooring Contractors

POSTED

2 days ago

DEADLINE

in 5 days
View Details
NAICS: 238220
New
Federal
J045--Glycol Loop Flushing - NWI
Solicitation # 36C26327Q0060
Solicitation 36C26327Q0060 is a firm fixed price request for quotation issued by the Department of Veterans Affairs Network Contracting Office 23 for the flushing, cleaning, and recharging of two closed-loop glycol heating systems, specifically the Surgery and Microbiology loops, at the Omaha VA Medical Center. The project requires the contractor to provide all labor, materials, equipment, and disposal handling to restore the systems to a stable operating condition using propylene glycol-based heat transfer fluid. The anticipated period of performance runs from November 1, 2026, to October 31, 2027, with the initial service required within 30 calendar days of award and a second identical service performed approximately 12 months later. Work must be conducted during normal business hours when temperatures exceed 40 degrees Fahrenheit and must comply with NFPA-99, ASHRAE 170, CMS, JCAHO, and VA HVAC Design Manual standards. This procurement is a total set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), with strict limitations prohibiting the contractor from paying more than 50 percent of the government-paid amount to non-certified SDVOSB or VOSB firms. Award will be based on a comparative evaluation of price, technical quality, past performance, and veterans involvement. Key deliverables include pre-flush fluid sampling reports, system volume calculations, refractometer readings, and disposal manifests. Following Amendment 0001, the response deadline has been extended to November 10, 2026. Proposals must be submitted electronically to the contracting officer and include separate volumes for administrative documents, technical and past performance narratives, a subcontracting statement, and a labor standards statement confirming compliance with Service Contract Labor Standards.
Plumbing, Heating, and Air-Conditioning Contractors

POSTED

6 days ago

DEADLINE

in 12 days
View Details

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS