Transformer Oil Testing Services

Closed
SS-260020346Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

General Info

NAICS

541380 - Testing Laboratories and Services

Place of Performance

Princeton, NJ, 08543, USA

Set-Aside

LAS

Documents

1

Statement of Work for Transformer Oil Sampling and Analysis C-FAC-SOW-056 R0

PDF, High priority: read this first7 pages · sow
High

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

PhaseClosed
Posted

Sources Sought

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Get full access to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Energy → Princeton Labor - DOE Contractor
Contacts1 person available
OfficePrinceton, NJ, 08540, USA
Office AddressPrinceton, NJ, 08540, USA

Full Description

Show more

The Princeton Plasma Physics Laboratory is searching for a qulaified contractor to perform the following services


Subcontractor shall perform the following tasks and provide associated documentation.
5.1.1 Provide experienced personnel to inspect transformers and take required samples from oil
filled transformers at PPPL at a mutually agreed upon time. All sampling containers and
transport to subcontractors’ analyses facilities shall be provided by the subcontractor and
include in the pricing schedule.
5.1.2 Perform appropriate analyses of oil samples in subcontractor’s laboratory. Most samples will
be mineral oil. Silicone and bio-based oils will be identified in the sampling plan (if part of
routine analyses) or on individual samples. Transformers requiring these analyses will be
identified by the PTR. Subcontractor may use alternate ASTM methods to those called out in
the SOW.
1. Oil Screen Analyses shall include the following.
Analysis ASTM Standard
a. Neutralization Number ASTM D 974
b. Interfacial Tension (IFT) ASTM D 971
c. Relative Density (Specific Gravity) ASTM D 1298
d. Color ASTM D 1500
PWR-SOW-056, Rev 2 PAGE 3 of 7
e. Visual Examination ASTM D 1524
f. Dielectric Breakdown Voltage ASTM D 877
2. Moisture in Oil
Analysis ASTM Standard
a. Moisture in Oil ASTM D 1533
3. Dissolved Gas Analysis
Analysis ASTM Standard
a. Dissolved Gas Sampling ASTM D 3613
b. Analysis by Gas Chromatography ASTM D 3612
4. Discretionary Analyses
Subcontractor shall also offer other analyses on a sample by sample basis, including the
following.
Analysis ASTM Standard
a. Oxidation Inhibitor ASTM D 2668
b. Liquid Power Factor ASTM D 924
c. Furan Content ASTM D 5837
d. Metals in Oil ASTM D 3635
5.1.3 Subcontractor may properly dispose of sample remains 6 months after analysis.

Earlier notices in this NAICS code

Posted before this notice, open and closed

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS