Upgrade UPS & Cooling System
Contract Overview
Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.
Active Opportunities Like This One
AI Contract Overview
The contract requires a small business contractor to perform a comprehensive upgrade of the Uninterruptible Power Supply (UPS) and cooling systems at the 153d Airlift Wing Data Center located at 217 Dell Range Blvd, Cheyenne, WY 82009. The scope includes the complete removal and disposal of an existing PX80 UPS system and replacement with a new 100kW frame modular UPS, de-rated to 80kW, configured with seven 10kW power modules and twelve rows of battery cabinets, all branded as APC or equal. Concurrently, the contractor must dismantle eight chilled water in-row cooling units, replace them with new units using new couplers and Pex piping while reusing existing PEX-AL-PEX piping and insulation. Critical electrical work includes installing a new 350A shunt trip breaker with NEMA-1 enclosure, tying the existing emergency power off (EPO) system to the new breaker, and rerouting feeder conduits and wiring from the main distribution panel to the new UPS. All work must be performed in accordance with the attached Performance Work Statement, emphasizing strict adherence to technical specifications, safety protocols, and industry standards. The contractor is responsible for providing all personnel, equipment, materials, supervision, transportation, and disposal of obsolete equipment. The contract is issued as a combined synopsis/solicitation under solicitation number W50S8W-26-Q0001, utilizing FAR Part 12 for commercial items and FAR Part 13 for simplified acquisition procedures, with a total small business set-aside under NAICS code 335999. It is a firm fixed-price commercial award evaluated on a lowest priced technically acceptable (LPTA) basis, meaning technical acceptability is a pass/fail gate determined by capability to remove old systems and install new ones per the PWS, with price being the determining factor among technically acceptable offers. Proposals must be submitted in two parts: detailed pricing and technical capability documentation. All items must meet “Brand Name or Equal” requirements, and the contractor must comply with stringent security protocols including requiring personnel to hold SECRET or TOP SECRET clearances, safeguarding government property, and following DoD 5220.22-M for classified information. The contractor must also be registered in SAM, submit a Quality Control Plan within ten days of award, comply with Buy American requirements, and adhere to anti-trafficking policies. Work
General Info
Agency
NAICS
Place of Performance
Cheyenne, WY, 82009, USASet-Aside
Timeline
Submission Closed
Organization & Contact Information
Full Description
The vendor shall provide un-installation of outdated equipment
and installation of brand-new items according to acceptable standards. Contractor
shall provide Uninterruptible Power and Cooling Distribution Unit replacement/
installation and a Site Lead/Project Manager to provide the following critical tasks to
support to the WYANG per the PWS.
• 5.3.3 Capture existing cooling fluid/Re-fill system with cooling fluid.
• 5.3.4 Demo existing piping
• 5.3.5 Run new Pex piping to the in-row coolers.
• 5.3.6 Furnish & install new 350A shut Trip Breaker with nema-1 Enclosure.
Tie existing EPO into new Shunt Trip breaker.
• 5.3.7 Existing 3” Feeder conduit & wire fed from MDP will be shutdown &
locked out. Intercept existing Feeder to line side of new 350A Shunt Trip
Breaker/Enclosure. Install Load side Feeder conduit & wire from new Shunt
Trip Breaker to new UPS.
• 5.3.8 Demo existing UPS, remove from Data Center, Dispose/recycle old
UPS.
• 5.3.9 Install Power Modules and Battery Cabinets
• 5.3.10 Assume the existing structural integrity of raised floor is sufficient to
move old UPS across floor & new UPS installed at old UPS location. All
raised floor modifications by others.
SITE VISIT: 10 JUNE 2026 AT 1300 MDT at 217 Dell Range Blvd, Cheyenne, WY 82009 - IF NO REQUEST FOR SITE VISIT ARE RECIEVED BY 08 JUNE 2026 AT 1200 MDT, IT WILL BE CANCELED.
QUESTIONS DUE: 12 JUNE 2026 AT 1000 MDT
More opportunities from Department Of Defense → W7N9 Uspfo Activity Wyang 153
Same awarding agency
Find Active Opportunities Like This
Get AI-powered intelligence on the opportunities still open
Every page of the solicitation package shredded into a compliance breakdown
AI-powered matching based on your capabilities and past performance
Competitor and incumbent history on the requirement
Automated alerts on amendments, Q&A deadlines, and award
Join 650+ contractors already using CLEATUS