Skip to main contentPsst! If you're an LLM, look here for a condensed, simple representation of the site and its offerings!

LiveFree Webinar — Wednesday, November 11 at 2:00 PM ET

Register Free →

This Government Contract opportunity from Department Of Veterans Affairs was posted on November 4, 2009. The submission period has ended. Browse the details below for market research, or find similar active opportunities.

44--Evaluation of Boilers

Awarded
VA244-09-RP-0310Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 541330
New
SLED
Road Asset Management
Solicitation # FY27-ENGCP-002-6
The Bulloch County Board of Commissioners is soliciting Statements of Qualifications for project FY27-ENGCP-002-6, focused on Road Asset Management. The selected consultant will be responsible for collecting and analyzing field data, creating a road asset inventory, and developing a Capital Improvement Plan with an outlook extending to FY 35. The scope includes GIS database development, web-based mapping, and the identification of structural hazards and drainage failures to minimize safety risks and legal liability. All prime and sub-consultants must be GDOT Prequalified Contractors as of the submission deadline on November 20, 2026, at 3:00 PM EDT. Proposals are evaluated based on a composite scoring system that weights prime consultant experience and technical approach at 20% each, GIS capabilities at 20%, asset prioritization methodology at 15%, workload capacity at 15%, and past references at 10%. The highest-ranked consultant will be invited to negotiate a contract. Key requirements include a Principal-in-Charge with at least 10 years of industry experience and comprehensive insurance coverage, including professional malpractice and general liability of at least 1 million dollars per occurrence. Submissions are limited to ten pages, excluding mandatory forms and charts, and must include a Non-Collusion Affidavit and Bidder Declaration. Either party may terminate the resulting agreement with 30 days written notice.
Bulloch County Board of Commissioners

POSTED

about 9 hours ago

DEADLINE

in 22 days
NAICS: 541330
New
International
CoT RFP Event Q30-01-2026-27
Solicitation # Q30-01-2026-27
The City of Tshwane is soliciting a service provider for professional engineering services to support town planning subdivision application processes on city-owned properties. The scope of work is divided into three primary categories: Civil Services Reports, Geotechnical Investigations, and Route Determination Reports. All services must be led by a Professional Engineer registered with the Engineering Council of South Africa and must comply with the Gauteng Transport Infrastructure Act, National Building Regulations SANS 10400, and various SANS and SANRAL standards. The project follows a strict timeline, requiring an inception meeting within one month, draft reports within three months, final reports within five months, and project close-out within six months of appointment. The solicitation, numbered Q30-01-2026-27, closes on November 12, 2026, at 10:00. Awards are based on an 80/20 preferential point system in accordance with the Preferential Procurement Policy Framework Act and 2022 Regulations, with specific goals including points for women-owned, youth-owned, and disability-owned enterprises, as well as local economic participation. Evaluation occurs in four stages, starting with administrative responsiveness and a functionality score of at least 70 out of 100. Successful bidders must enter into a Service Level Agreement, with payment terms set at 30 days following the receipt of an invoice. Required submission documents include company registration, tax clearance or a CSD unique pin, and B-BBEE certification.
City of Tshwane

POSTED

about 11 hours ago

DEADLINE

in 13 days

AI Contract Overview

Show more

The Department of Veterans Affairs Coatesville Medical Center requires a professional engineering firm to conduct a reliability and life expectancy evaluation of four D-type E. Keeler boilers manufactured in 1968. Because these boilers have exceeded their standard useful life expectancy per VHA Directive 2003-050, a comprehensive assessment is necessary to determine if they should be retained or replaced. The selected contractor must provide a Qualified Professional Inspector and ASNT Level II certified non-destructive testing personnel to perform visual inspections, ultrasonic thickness testing, magnetic particle testing, and potential metallurgical analysis. The scope of work includes inspecting welded connections, support structures, furnace tubes, and drum internals to identify corrosion, erosion, or structural defects. The contractor is responsible for calculating the maximum allowable working pressure and remaining life expectancy using ASME Code formulas. The final deliverable consists of an oral briefing and a detailed written report featuring test results, photographic evidence of deterioration, repair recommendations with cost estimates, and an expert judgment on the cost-effectiveness of continued operation.

General Info

Contract Value

$41,885

NAICS

541330 - Engineering Services

Place of Performance

PA, USA

Set-Aside

NONE

Award Issued Date

Documents

0

No documents available

Documents will appear here when they are available.

AI Contract Breakdown

Uniform Contract Format

No documents to break down

The breakdown needs solicitation documents. None were found from this contract's source.

Timeline

1 update
PhaseAwarded
Posted

Sources Sought

Notice updated

Response deadline changed from Jul 20, 2009 to Aug 14, 2009. The notice title changed. The notice description changed.

Type Changed

Sources Sought → Combined Synopsis

Awarded

Contract was awarded

Submission Closed

Find active opportunities like this

Get full access to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → 244-NETWORK Contract Office 4 (36C244)
ContactsNo contacts available
OfficePITTSBURGH, PA, 15215, USA
Office AddressPITTSBURGH, PA, 15215, USA
ContactsNo contact information available

Full Description

Show more
DEPARTMENT OF VETERANS AFFAIRS COATESVILLE MEDICAL CENTER SCOPE OF WORK ENGINEERING EVALUATION OF BOILER RELIABILITY/LIFE EXPECTANCY FOR BOILERS 1,2,3,4 1. Introduction: VA medical centers provide critical health care which requires reliable steam supply for sterilization, domestic hot water, kitchens, and building heating/air conditioning. Boilers serving VA medical centers must be reliable, safe and efficient. The age of boilers is often a major indicator of reliability. The VHA Directive 2003-050, BOILER PLANT OPERATIONS, assigns useful life expectancy, in years, to the boiler plant equipment. The Directive requires that retention of equipment beyond the useful life expectancy must be based on an engineering evaluation of the reliability, efficiency and cost effectiveness of continued operation. Following are boilers to be included in evaluation #1 - D-type E. Keeler Company mfg. 1968, 20,000#/hr, serial # 14579-1 #2 - D-type E. Keeler Company mfg. 1968, 20,000#/hr, serial # 14579-2 #3 - D-type E. Keeler Company mfg. 1968, 40,000#/hr, serial # 14580-2 #4 - D-type E. Keeler Company mfg. 1968, 20,000#/hr, serial # 14580-1 2. Summary of Requirements: When boilers reach the end of their expected lives, VAMC engineering personnel should review the condition of the boilers as reflected in the operational records, maintenance and repair history and in the reports of the annual boiler inspections. If there is no clear indication on whether the boilers should be retained or replaced, an engineering evaluation of life expectancy should be commissioned. A professional engineering firm that specializes in life expectancy evaluations should be contracted to evaluate the boiler by means of visual inspection and non-destructive testing utilizing experienced boiler inspectors and non-destructive testing experts. Their report must describe all conditions found and include sufficient information that VAMC engineers can make decisions on retaining or replacing the boilers. 3. Qualification Requirements for Inspection Personnel: A. The inspections shall be supervised on-site by a Qualified Professional Inspector, defined as any one or combination of: 1) A boiler inspector who has a valid commission from the National Board of Boiler and Pressure Vessel Inspectors. 2) A boiler inspector who has qualified by passing a written examination under the laws, rules and regulations of a jurisdiction of a state. 3) A boiler inspector who is regularly employed as a boiler inspector by a jurisdiction that has adopted and administers one or more sections of the ASME Boiler and Pressure Vessel Code as a legal requirement, and has a representative serving as a member of the ASME (American Society of Mechanical Engineers) Conference Committee. 4) A boiler inspector who is regularly employed by an insurance company that has been licensed or registered by the appropriate authority of a state of the United States to write boiler and pressure vessel insurance. B. Non-destructive testing personnel shall be certified to American Society for Non-destructive Testing (ASNT) Level II, who are experienced in evaluating boilers. 4. VAMC Responsibilities for Preparation of Boiler for Inspection: A. All preparation work shall be done prior to arrival of inspection personnel. B. Coordinate preparation work with the requirements of the inspection firm. C. Records of maintenance and repair activities, water treatment logs, operational logs, inspection reports, and histories of prior problems shall be readily available during the inspection. Records for three years are suggested. D. Remove all manway and handhole covers, access panels. E. Remove all drum internals. F. Furnish copies of the original National Board (NB) Manufacturers Data Report inspection form that was prepared for the boiler when it was new and NB Report of Repair forms if boiler pressure vessel repairs have been performed. 5. Inspection Requirements: Contractor shall arrange for personal protective equipment and safety personnel for any OSHA requirements to include confined spaces. A. Visually inspect: 1) All welded and threaded pipe connections to the boiler shell or drum for signs of leakage or defects in the welded areas. Defects should be non-destructively tested. 2) Boiler support structure for proper alignment, evidence of sagging, shifting or misalignment. 3) Boiler casings for signs of warping, misalignment and overheating. 4) All furnace tubes and all accessible convection tubes for alignment, evidence of corrosion, erosion, bulges, sagging, defective or deteriorated welds. 5) Exposed surfaces of steam and mud drum in furnace, particularly ligament areas between tubes, for evidence of corrosion, cracking, scale buildup, other defects. 6) Refractory for cracking, shifting, sagging, bulging or general deterioration. 7) Internal areas of steam drum and mud drum (inside boiler shell in fire tube boilers). a. Welded outlet connections. b. Surface of drums for pitting or surface discontinuities. c. Ligament areas between tube holes for cracking. d. Each tube end and internal surface of representative number of tubes for pitting, erosion, corrosion and excessive scale buildup. Utilize fiber optic inspection equipment to inspect interior of tubes. e. Clean and inspect shell or tube sheet between tube holes for cracking. B. Non-destructive testing: 1) Ultrasonic thickness testing of representative samples of all components. Note: A specific number of tests at various areas should be specified. 2) Ultrasonic thickness testing of all areas visually noted to have corroded or eroded. 3) Magnetic particle testing of all areas where indications of defects have been found visually. 4) Metallurgical analysis of representative samples of boiler metal if there are indications or a record of overheating. C. Calculation of maximum allowable working pressure and remaining life expectancy: 1) Utilize ASME Code formula. 2) Remaining life calculation based on original material thickness, current material thickness, evaluation of other factors in the condition of the boiler. 3) Obtain sufficient material thickness measurements to accurately reflect the condition of the entire boiler. This shall include removal and reinstallation of casing and insulation as necessary to inspect lower D-tubes near mud drum. 6. Report Requirements: A. Provide oral report of condition of the boiler to VAMC engineering management at the conclusion of the inspection. B. Provide six hard copies and electronic version of report. 1) Provide complete narrative, test results, photographic views of deteriorated areas. 2) Calculate remaining life based on calculated present maximum allowable working pressure vs. original maximum allowable working pressure when the boiler was new. 3) Describe all deteriorated areas; provide expert judgment on need for repairs, repair methods and cost estimates. 4) Provide expert judgment on cost effectiveness of retaining the boiler in service.

More opportunities from Department Of Veterans Affairs → 244-NETWORK Contract Office 4 (36C244)

Same awarding agency

NAICS: 325412
New
Federal
6505--INTENT TO SOLE SOURCE Radiopharm - Lutathera & Pluvicto - Lebanon VAMC
Solicitation # 36C24427Q0045
The Department of Veterans Affairs, Network Contracting Office 4, intends to establish a firm-fixed-price contract for the procurement and delivery of name-brand Lutathera and Pluvicto radiopharmaceuticals for the Lebanon VA Medical Center. The scope of work includes the distribution, transportation, and inventory management of 8 doses of Lutathera and 48 doses of Pluvicto, both at 200mCi intravenous injection. The proposed period of performance is from January 1, 2027, to December 31, 2027. The government intends to sole source this requirement to Novartis Pharmaceuticals Corporation under the Revolutionary FAR Overhaul (RFO) for FAR 8.4 and GSAM/R 538.71, in accordance with Executive Order 14275. The contractor must be licensed by the Nuclear Regulatory Commission and comply with FDA, OSHA, and DOT regulations, including the use of lead-shielded containers and specific labeling requirements such as bar-coding for dose tracking. Deliveries must be made F.O.B. Destination to the Lebanon VA Medical Center, with routine shipments arriving at least one hour before calibration time. Preference will be given to contractors utilizing non-High Enriched Uranium sources. This notice is for planning purposes, and interested vendors must submit a one-page capability statement, including their SAM UEI number and socioeconomic category, to the Contracting Specialist by November 3, 2026, at 14:00 PM EST. The procurement falls under NAICS code 325412 with an SBA size standard of 1,300 employees.
Pharmaceutical Preparation Manufacturing

POSTED

about 18 hours ago

DEADLINE

in 5 days
View Details
NAICS: 339112
New
Federal
6515--Full Body Phototherapy
Solicitation # 36C24427Q0046
The Department of Veterans Affairs is conducting market research through a Sources Sought Notice to identify qualified sources for the one-time acquisition of one full body clinical phototherapy cabinet for the Wilmington VA Medical Center in Delaware. The equipment is intended for treating dermatologic conditions such as psoriasis, vitiligo, and eczema. Key technical requirements include a minimum operational lifespan of five years, a minimum one-year manufacturer service warranty, and the ability to support narrowband UVB, UVA, and combination therapies. The unit must feature forty-eight high-intensity six-foot ultraviolet lamps, an integrated dosimetry system, a touchscreen interface, and a temperature-management system with patient-controlled cooling. Additionally, the cabinet must be wheelchair accessible, include ultraviolet-transmitting acrylic shields, and maintain treatment history locally without requiring connection to the VA network. Vendors must also offer yearly maintenance services as part of their commercial catalog. This notice is for market research purposes only and does not constitute a binding offer or a formal solicitation. Interested respondents must submit their company details, SAM UEI number, business size classification, and any existing government contract vehicles to the designated point of contact by 6:00 am ET on November 10, 2026. The acquisition falls under NAICS code 339112 with a size standard of 1,000 employees. Small businesses must demonstrate compliance with the nonmanufacturer rule and provide a letter of authorization from the original equipment manufacturer if acting as a distributor. Large businesses are required to disclose any designated distributors. Responses should include capability materials such as brochures or hyperlinks to help the government determine the technical capabilities of the proposed equipment.
Surgical and Medical Instrument Manufacturing

POSTED

about 18 hours ago

DEADLINE

in 11 days
View Details
NAICS: 561730
New
Federal
S218--Snow Removal Services Wilmington VAMC
Solicitation # 36C24427Q0O12
Solicitation 36C24427Q0012 is a combined synopsis and request for quote for snow removal and deicing services at the Wilmington VAMC in Delaware. This is a five-year Indefinite Delivery/Indefinite Quantity (IDIQ) contract with an anticipated period of performance from December 1, 2026, through November 30, 2031. The contract has a minimum guarantee of 5,000 dollars and an estimated maximum value of 500,000 dollars, with funds obligated via individual task orders. The procurement is a total set-aside for certified Service-Disabled Veteran-Owned Small Businesses (SDVOSB) under NAICS code 561730. The scope of work includes clearing all levels of a multi-level parking garage, stairwells, entrances, and exposed ramps, with a requirement that all areas be cleared by 6:00 AM EST following overnight snowfall. Specific chemical restrictions are in place, prohibiting rock salt in the garage and requiring the use of garage-friendly chemicals such as sodium acetate, potassium acetate, or calcium magnesium acetate. The contractor must provide an on-site supervisor for every operation and ensure personnel wear OSHA-required PPE and high-visibility vests. Performance will be evaluated based on a Quality Assurance Surveillance Plan, and the award will be based on a comparative evaluation of technical capability and past performance, as well as price. Offerors must be registered in the System for Award Management and submit their quotes via email to the designated contract specialist. Submissions must include a technical document not exceeding 20 pages, firm fixed pricing for all line items, and three examples of past performance for similarly scoped work. Invoices are to be submitted electronically in arrears upon job completion and are due within 30 days. Compliance with applicable wage and hour laws and limitations on subcontracting are mandatory for the prime contractor.
Landscaping Services

POSTED

3 days ago

DEADLINE

in 3 days
View Details

Earlier notices in this NAICS code

Posted before this notice, open and closed

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS