Amendment 1 to 7 Ultrasonic Flowmeters
Contract Overview
Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.
AI Contract Overview
Amendment 1 to solicitation 1333ND26QNB610465 concerns the procurement of seven ultrasonic flowmeters for the Department of Commerce NIST in Gaithersburg, Maryland. The amendment provides critical technical clarifications regarding the cooling systems, specifying that the primary loop uses purified heavy water and the secondary loop uses water with minimal solids and some algae. Operating conditions are defined as having a maximum temperature of 114 degrees Fahrenheit and a maximum pressure of 10 psia. The agency clarified that the water is moderately clean and not a slurry, and while PC-based data logging is preferred, it is not a mandatory requirement. The solicitation is categorized under NAICS code 334516, with a response deadline of September 4, 2026.
General Info
Agency
NAICS
Place of Performance
Gaithersburg, MD, 20899, USASet-Aside
Documents
(3)AI Contract Breakdown
Uniform Contract FormatWhat is UCF?
Uniform Contract Format (UCF) uses AI to break down any contract into standardized sections—scope, pricing, deliverables, and evaluation criteria.
Timeline
Response Deadline
Organization & Contact Information
Full Description
Amendment 1to RFQ 1333ND26QNB610465
Clarification questions:
Vendor Question 1:
Could you please confirm the solids content (TSS) of the water? If this is clean water, with less than 2% TSS, please let us know so we can determine the appropriate unit for the application.
NIST Response:
This water is moderately clean, not a slurry (2% TSS is closer to wastewater) but not filtered
Vendor Question 2:
The factory has confirmed that no software is required to configure the meter, as very few ultrasonic meters require software for configuration.
NIST Response:
PC-based data logging is a nice-to-have but not a necessity.
Vendor Question 3: (clarification on the following process conditions for the primary and secondary cooling systems)
Operating temperature of the process fluid (or pipe surface temperature) at the measurement points, for both the primary and secondary cooling loops. This determines whether standard or high-temperature transducers are required.
NIST Response:
No higher than 114 degrees Fahrenheit.
Vendor Question 4: (clarification on the following process conditions for the primary and secondary cooling systems)
Operating pressure of the cooling water at the measurement points (primary and secondary).
NIST Response:
No higher than 10 psia.
Vendor Question 5: (clarification on the following process conditions for the primary and secondary cooling systems)
Confirmation of the process fluid — the SOW references cooling water; please confirm it is treated water with no significant entrained solids or aeration that could affect ultrasonic signal transmission.
NIST Response:
Primary – Heavy water, purified. Secondary - Water with minimal solids. Some algae to be expected but not significant.
As defined in the attached Combined Synopsis Solicitation, Statement of Work and RFO Provisions and Clauses.