Amendment - Air Compressor and Desiccant Unit, IND

Active
36C25026Q1017_0001Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

AI Contract Overview

Show more

This contract is for the supply and delivery of a single oil-free screw type air compressor system for general shops and control system air supply at the VAMC in Indianapolis. The equipment must be brand neutral but should closely match the specifications of a Quincy QGDV series unit, featuring a 25 horsepower motor, a 120 gallon horizontal receiver factory-mounted as one package, and a Q-Control Touch Controller for performance monitoring. The system must operate at a 125 psig working pressure and adhere to Quincy specifications for all other technical requirements. The scope of work is limited to supply and delivery to the facility dock, with the VA handling all rigging, transport, and installation. The supplier is responsible for providing an authorized factory startup to ensure the unit is eligible for the Quincy True Blue extended warranty. This is a total small business set-aside opportunity managed by the Department of Veterans Affairs, with the primary objective of procuring a high-performance compressor package delivered to the Indianapolis site.

General Info

Supply and delivery of one oil-free screw air compressor for VAMC Indianapolis.

Agency

Department Of Veterans Affairs → 250-NETWORK Contract Office 10 (36C250)View Agency

NAICS

333912 - Air and Gas Compressor ManufacturingView NAICS

Place of Performance

Indianapolis, IN, 46240, USA

Set-Aside

SBA

Documents

(1)

Amendment+-+36C25026Q1017+0001.docx

DOCX

AI Contract Breakdown

Uniform Contract Format

What is UCF?

Uniform Contract Format (UCF) uses AI to break down any contract into standardized sections—scope, pricing, deliverables, and evaluation criteria.

Timeline

Posted

special-notice

Response Deadline

Submission deadline

Response Deadline

Ready to pursue this opportunity?

Start your free trial to track this contract, build proposals with AI assistance, and manage your pipeline.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → 250-NETWORK Contract Office 10 (36C250)
Contacts1 person available
OfficeDAYTON, OH, 45428, USA
Organization / Agency
Department Of Veterans Affairs → 250-NETWORK Contract Office 10 (36C250)
View Agency Profile
Office AddressDAYTON, OH, 45428, USA

Full Description

Show more

1) Can you please confirm with the client for the compressor do they want oil free rotary screw? Or oil flooded rotary screw?
Normally you see desiccant dryers with oil free applications but wanted to confirm with you.
Answer: Oil free screw type
2) Is the requested compressor intended to be a current Quincy model, a legacy Quincy model, or a brand neutral performance specification?
Answer: Brand neutral
3) The current Quincy QGSV 25 is variable speed and direct drive, and its current public table lists 125.1 cubic feet per minute at 100 pounds per square inch gauge. The current QGD 25 is gear driven and fixed speed, and its current public table lists 109.8 cubic feet per minute at 125 pounds per square inch gauge. What exact current model or combination satisfies variable speed, gear drive, 25 horsepower, and 117.6 cubic feet per minute at 125 pounds per square inch gauge?
Answer: The model selected should be as close to matching Quincy QGDV series unit
4) Is a current Original Equipment Manufacturer controller accepted if the named Q Control Touch controller is unavailable on the compliant
25 horsepower model.
Answer: No we want the Q-Control Touch Controller as a way to monitor compressors performance and maintenance status
5) Must the compressor and 120 gallon horizontal receiver be factory mounted as one package?
Answer: Yes
6) Please identify the required discharge connection, working pressure, relief setting, air quality, ambient conditions, altitude, ventilation, maximum sound level, electrical full load current, disconnect, starter, dryer dew point, filter grades, pressure drop, separator drain, condensate treatment, and any installation boundary.
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
Page 3 of 3
Answer: Air compressor to be used in Indianapolis. This is for supply and delivery-not installation. 125 psig working pressure, discharge connection shall be standard for Quincy QGVD-25 unit. Use Quincy specs for the remainder of your questions.
7) Does factory startup include electrical energization, piping, anchoring, configuration, testing, training, and a written startup report, or only an authorized technician visit after Government installation?
Answer :Authorized start up shall be sufficient to obtain extended warranty per Quincy True Blue requirements
8) What delivery date, site access, receiving, inside delivery, rigging, offload, acceptance, and invoice timing apply?
Answer: Supplier will deliver and off load to Shops dock at the VAMC, Indianapolis. VA forces will move from dock and install.
9) May Sentiq remain the prime and seller of record while an authorized local Quincy distributor supplies, delivers, starts, and services the package?
Answer: Yes so long as Quincy provides the warranty
10) What is the intended usage of the system? Medical Air, Instrument Air, Compressed Air, etc.
Answer: General shops and control system air supply
11) Is this a single compressor, or should it be duplexed?
Answer: Single compressor
12) Is this material and parts only, or does this include installation? This includes factory startup which makes it seem like we are supposed to provide installation.
Answer: VA will receive and transport from dock to use site. VA personnel will plumb, connect electricity to compressor. Factory start up will be to inspect, start and provide services as required to make unit eligible for extended warranty

Similar Contracts

Same NAICS industry code

NAICS: 333912
New
Federal
Nitrogen Generator with Training
Solicitation # FA466126Q0078
Solicitation FA466126Q0078 is a Request for Quote issued by Dyess Air Force Base for the procurement of a containerized high pressure nitrogen compressor system. This Disadvantaged Small Business set-aside will be awarded as a Firm-Fixed Price contract based on best value, considering technical acceptability, delivery time, and price. The required system must be skid or trailer mounted, capable of continuous operation for at least 24 hours, and meet specific technical standards including a minimum flow rate of 26 scfm at 95.5 percent nitrogen, a storage pressure of 500psig, and a discharge pressure of 400psig. The system must utilize a design consisting of an air compressor feed to nitrogen membranes and a nitrogen booster compressor with 900 scf on-board storage, powered by 480vac, 3ph, 60hz. The contract scope includes the delivery of the hardware, unit acceptance testing conducted for eight hours at the contractor's facility, electronic operational manuals, and onsite installation at Dyess AFB. The government desires delivery and installation within 120 calendar days after the date of the contract. Additional requirements include the provision of a system matter expert and a one-year warranty. Payment will be processed electronically via the Wide Area WorkFlow system with NET 30 terms. Offerors must submit their quotes via email, including a signed RFQ page and a technical capabilities package demonstrating their ability to meet the salient characteristics.
FA4661 7 Cons Cd

POSTED

about 11 hours ago

DEADLINE

in 6 days
View Details

More opportunities from Department Of Veterans Affairs → 250-NETWORK Contract Office 10 (36C250)

Same awarding agency

NAICS: 516210
New
Federal
Audio Visual System
Solicitation # 36C25026Q0996
Solicitation 36C25026Q0996 is a request for a firm-fixed price purchase order from the Department of Veterans Affairs, Network Contracting Office 10, to design, build, and install a new audio-visual system for the Large and Small Learning Resource Center conference rooms at the Chalmers P. Wylie VA Ambulatory Care Center in Columbus, Ohio. The scope of work includes the de-installation of existing equipment and the implementation of a comprehensive system featuring monitors, in-ceiling microphones, surface-mounted speakers, control processors, and a mobile lectern. A critical requirement is the integration of a VA-provided laptop and a Cisco presentation rack system into the VA network to support Microsoft Teams for in-person, virtual, and hybrid meetings. The contractor is also responsible for providing on-site training for staff and one year of maintenance and remote support. The proposed period of performance is from September 21, 2026, to December 31, 2026. A non-mandatory site visit is scheduled for September 16, 2026, at 2:00 p.m. at the facility. Interested offerors must email all questions to Contracting Officer Gina P. Crank by September 18, 2026, and submit their final quotes, including a completed pricing schedule and product capability documentation, by September 22, 2026, at 2:00 p.m. Award will be based on a comparative evaluation of quotes to determine the response most advantageous to the government in accordance with FAR 12.
Media Streaming Distribution Services, Social Networks, and Other Media Networks and Content Providers

POSTED

about 11 hours ago

DEADLINE

in 6 days
View Details
NAICS: 811310
New
Federal
J041--Chiller Plant Preventative Maintenance
Solicitation # 36C25026Q0837
The Department of Veterans Affairs is soliciting a firm-fixed-price service contract for preventative maintenance of the chiller plant at the Richard L. Roudebush VA Medical Center in Indianapolis, Indiana. The scope of work involves the maintenance of five York centrifugal liquid chillers, including four 1,000-ton units and one 500-ton unit, along with their associated Toshiba and York variable frequency drives. Services include quarterly and annual inspections, oil and refrigerant analysis, coolant replacement for 480V drives, vibration analysis, and refrigerant leak testing. The contractor is required to provide detailed documentation in PDF format, including signed checklists, refrigerant equipment service forms compliant with 40 CFR Parts 82 and 84, and photographs of any issues requiring attention. The contract consists of a one-year base period from November 1, 2026, to October 31, 2027, with two subsequent one-year option periods extending the performance through October 31, 2029. This procurement is 100% set aside for small business concerns, specifically HUBZone small businesses, under NAICS code 238220. Award decisions will be based on a comparative evaluation of technical capability and price, with a focus on the offer most advantageous to the government. Offerors must provide professional certifications and licenses to prove personnel qualifications and must adhere to OSHA safety standards. Quotations are due by September 18, 2026, and must remain firm for 60 calendar days.
Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance

POSTED

about 11 hours ago

DEADLINE

in 12 days
View Details

Ready to Pursue This Opportunity?

Get AI-powered intelligence on this solicitation and the ones like it

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS