H965--Walla Walla VA Medical Center - Generator and Fuel Testing

Closed
36C26026Q0462Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 811310
New
Kubota M8200 Clutch Replacement
Solicitation # kubota-m8200-clutch-replacement
Management and Training Corporation is soliciting lump sum fee proposals for the clutch replacement of a Kubota M8200 tractor with front wheel assist, located at the Earle C. Clements Job Corps Center in Morganfield, Kentucky. The scope of work requires a qualified contractor to provide all transportation, labor, materials, and equipment to diagnose and repair the clutch assembly and power take-off system. Key technical requirements include replacing friction discs, bearings, oil seals, and O-rings, resurfacing the flywheel, and replacing hydraulic pipes and filters as needed. The contractor must perform all work according to manufacturer specifications and provide a final summary of diagnostic findings, an itemized list of replaced parts, and warranty documentation upon completion. This solicitation is set aside for small businesses, including VOSB, SDVOSB, WOSB, and HUBZone certified entities. Bids must be submitted via email to Angie Mahoney by 3:00 PM CST on November 3, 2026, and must include a bid sheet, proof of insurance, a completed supplier packet with a W-9, and applicable SBA certification letters. Award decisions will be based on best value, with a focus on administrative compliance and technical qualifications. The contract is subject to various Federal Acquisition Regulations, including standards for combating trafficking in persons, Buy American restrictions, and Service Contract Labor Standards per Wage Determination 2015-4687 Revision 31 for Kentucky.
Earle C. Clements Job Corps Center

POSTED

about 1 hour ago

DEADLINE

in 5 days
NAICS: 811310
New
SLED
SMDOT Elevator Maintenance
Solicitation # 12701633
The City of Santa Monica Department of Transportation (SMDOT) is soliciting bids for turnkey maintenance, inspection, and repair services for three hydraulic elevators located at 1620 6th Street. The equipment includes two passenger elevators and one freight elevator, specifically models AAK137, AA2986, and AEP227. The scope of work requires monthly systematic examination, lubrication, and repair of critical components, as well as monthly emergency recall and override testing in accordance with California Administrative Code Title 8, Section 3000(h). All provided materials must be new and meet Original Equipment Manufacturer standards. Bids must be submitted electronically via the OpenGov portal by December 3, 2026, at 3:00 pm. Qualified bidders must possess a valid C-11 California contractor's license and provide a maintenance supervisor to ensure compliance with safety requirements. The contract award is based on a weighted evaluation of experience and technical competence (25%), ability to meet work plans and timelines (25%), cost (20%), stability and references (10%), value add (10%), and quality control (10%). The City is not required to select the lowest monetary bidder. Key contractual requirements include a payment bond for awards exceeding 25,000 dollars, a Living Wage Certification for awards over 54,200 dollars, and compliance with the Oaks Initiative and ADA Title II. Successful bidders must provide a Certificate of Insurance naming the City of Santa Monica as an additional insured. Payment terms are net thirty days. The agreement includes an initial term with four subsequent annual renewal options.
D600 DEPT OF TRANSPORTATION - SaMoDOT

POSTED

about 16 hours ago

DEADLINE

in about 1 month
NAICS: 811310
New
SLED
CNG Fueling Station Maintenance and Repair Services
Solicitation # 2026-RFP-0441
The County of Sacramento is soliciting proposals under solicitation 2026-RFP-0441 to establish a contract for Compressed Natural Gas (CNG) fueling station preventative maintenance and repair services. The contract covers two facilities located at the Fleet Services Division and the Department of Airports. The selected contractor must provide certified CNG technicians to perform twice-monthly preventative maintenance and major services at 4,000 and 8,000-hour benchmarks. Service requirements include 24/7 availability, with on-site response times mandated within 48 hours for standard service calls and 24 hours for emergency calls. All work must adhere to manufacturer specifications and Cal/OSHA safety standards, including the provision of GHS Safety Data Sheets. The contract is designed for an initial one-year term with the option for four additional one-year extensions upon mutual agreement, with a scheduled award date of December 14, 2026. Award decisions will be based on factors other than price alone, utilizing a points-based scoring system that evaluates cost and the proposer's technical approach. Bidders must provide a Public Works and Prevailing Wage Contractor Registration number and are encouraged to utilize the County's Procurement Opportunities Program for small and micro-business preferences. Proposals must be submitted electronically via the SacCountyE bids portal by the final extended deadline of November 13, 2026.
DGS: CAPSD - Procurement

POSTED

about 16 hours ago

DEADLINE

in 15 days
NAICS: 811310
New
SLED
ELEVATOR & ESCALATOR MAINTENANCE, INSPECTIONS, AND TESTING
Solicitation # BPM059230
The Maryland Department of Transportation Maryland Transit Administration (MDOT MTA) is soliciting bids for a firm-fixed-price contract, AGY-26-001-MT, to provide comprehensive maintenance, inspection, and testing for elevators, escalators, and wheelchair lifts across various Metro stations in Maryland. The scope of work includes systematic preventive maintenance, emergency repairs, and deep cleaning to ensure all equipment remains in first-class operating condition in accordance with ASME A17.1 and A17.2 standards. The contract features a five-year base period with a total basis of award calculated at 4,750,000 dollars, which includes a 950,000 dollar allowance for reimbursable parts and materials. Bidders must maintain an operational office within 20 miles of Baltimore and provide certified mechanics with at least three years of documented experience. Award will be granted to the responsible bidder offering the lowest total price. Key procurement goals include a 17 percent Minority Business Enterprise (MBE) and a 1 percent Veteran-owned Small Business Enterprise (VSBE) participation rate. Bidders must possess at least three years of firm experience with comparable equipment and provide proof of significant insurance coverage, including 1 million dollars in general liability and 5 million dollars in pollution liability. Bids are due by November 12, 2026, and must include a bid bond, a contract affidavit, and detailed pricing for preventive maintenance and hourly labor rates. Performance is measured by the completion of specific checklist tasks rather than labor hours, and the contractor is required to submit safety reports within 24 hours of any incident.
Maryland Transit Administration

POSTED

about 18 hours ago

DEADLINE

in 14 days
NAICS: 811310
New
SLED
WOOHDR30R - Overhead Door Repairs and Maintenance - MDOT/SHA Worcester County
Solicitation # WOOHDR30R
Solicitation WOOHDR30R is an Invitation for Bids issued by the Maryland State Highway Administration for the preventative maintenance and repair of 27 overhead doors and their related operators at the Worcester County Shop locations in Snow Hill and Berlin. The scope of work requires semi-annual 20-point inspections and on-call repair services with a mandatory response time of four business days. All repairs must be performed by technicians with at least two years of experience, adhere to manufacturer specifications and building codes, and utilize new, first-quality parts. The contractor is required to provide a not-to-exceed cost quotation before performing any repair work and must submit detailed written reports following each service visit. The contract will be awarded to the responsive and responsible vendor offering the lowest total bid price. To qualify, bidders must demonstrate at least two years of continuous professional experience in overhead door services, be registered with the State Department of Assessments and Taxation, and possess their own employees, equipment, and vehicles without the use of subcontractors. Required submission documents include the eMMA Price Form, a Bid/Proposal Affidavit, and reference checks from the last five years. Payment is processed through the Snow Hill Shop, with specific billing requirements for trip charges, manlift usage, and materials priced at or below retail cost or MSRP. All work must comply with MOSH and OSHA safety regulations.
State Highway Administration

POSTED

about 18 hours ago

DEADLINE

in 20 days

General Info

NAICS

811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance

Place of Performance

Jonathan M. Wainwright Memorial VA Medical Center, Walla Walla, WA, 99362, USA

Set-Aside

NONE

Documents

1

Sources Sought Notice 36C26026Q0462 - Generator and Fuel Testing Services

DOCX, High priority: read this firstsources-sought
High

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

PhaseClosed
Posted

Sources Sought

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Get full access to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → 260-NETWORK Contract Office 20 (36C260)
Contacts1 person available
OfficeVANCOUVER, WA, 98661, USA
Office AddressVANCOUVER, WA, 98661, USA
Contacts
Michael AllredContracting Officer

Full Description

Show more
The Department of Veterans Affairs (VA), Network Contracting Office 20 (NCO 20), is conducting market research on behalf of the Walla Walla VAMC to identify potential contractors capable of providing generator and fuel testing services. To be considered a responsive and potential source, interested parties shall provide a capabilities statement containing the following information: Business name, address, point of contact, phone number and email address. Business size designation (under NAICS 811310 sized standard $12.5M), type (SDVOSB, VOSB, WOSB or other), and SAM Unique Identifier Number Affirmation that the vendor is capable of performing in accordance with the attached Draft Performance Work Statement. Also, vendors shall include at least one example of relevant past performance wherein it is shown the quoter has performed similar work meeting similar performance standards in the past. Affirmation that the vendor is capable of performing in compliance with the Limitations on Subcontracting, in accordance with VAAR 852.219-75, if this were to be set-aside for SD/VOSBs or other Small Businesses. Additionally, contractors can provide feedback on the attached Draft Performance Work Statement, which may be considered if a solicitation is posted. Provide the requested information to Michael Allred at contact@example.gov before 12:00 PM PST on March 23rd, 2026. All questions must be submitted via email, no telephonic inquiries will be accepted. This is a sources-sought notice only. The purpose of this notice is to obtain information regarding the availability and capability of ALL verified sources to include qualified SDVOSB/VOSB to perform this potential requirement. Responses received will assist the Government in determining the appropriate acquisition strategy. The Government may or may not issue a solicitation as a result of this notice. There is no solicitation available at this time, and this is not a request for quotes. See attached document: Draft Statement of Work. EB.3 STATEMENT OF WORK (SOW)
Title: Emergency Generator Load and Fuel Testing
Background
The Jonathan M Wainwright Memorial VA Medical Center (VAWW), located at 77 Wainwright Drive, Walla Walla, WA, requires annual and triennial testing of emergency generators as required by NFPA 110 and fuel testing per NFPA 110 Part 8.3.7. There are currently eight diesel electric generators on the VAWW campus which have insufficient connected load and require annual testing with a supplemental load bank. There are 9 fuel storage containers that need to be tested as well.
Place of Performance
All work under this contract is to be performed at the following locations:
Walla Walla VA Medical Center, 77 Wainwright Dr, Walla Walla, WA 99362
Scope
Contractor shall furnish all labor, travel, equipment, supplies, and materials required to perform a complete inspection, testing, maintenance and repair service of the systems in accordance with the frequency and procedures outlined in the most current edition of the Applicable publications mentioned throughout all of the identified scope below.
Provide annual inspections and supplemental load bank testing according to the following NFPA 110 and VA Directive 1028 language:
If the monthly EPSS tests cannot exercise the generators at 30 percent load or acceptable stack exhaust temperature, an annual test must be conducted using supplemental load banks. Such test must meet applicable requirements of NFPA 99, NFPA 110, and The Joint Commission.
The generator must be tested at 50% nameplate load for the first 30 minutes and then at 75% nameplate load for 60 minutes following the first 30 minutes. In total, the generator will be tested for 1.5 hours.
Provide annual fuel testing per NFPA 110, generator manufacture s recommendations and ASTM testing standards to validate that the quality of fuel complies with manufacture s acceptable ranges for proper generator functionality.
Provide triennial generator testing using supplemental load bank testing according to the following VA Directive 1028 and The Joint Commission language:
The Joint Commission requires a 4-hour generator test under load (dynamic or static) that is at least 30 percent of the nameplate rating of the generator once every 36 months. To accomplish this the VA requests that the generator is tested for 180 minutes at 30% of nameplate load and then tested for 60 minutes at 75% nameplate load. The contractor will not perform annual tests during the same year that triennial tests are required. The VA has an agreement with NFPA that when triennial testing is performed to VA standards, NFPA accepts that our triennial testing as an annual test.
APPLICABLE PUBLICATIONS: The publications listed below shall be followed when engaging in any work required by this contract. There are specific references called out, but it is still expected that any requirements of these codes are followed. The most current edition of these standards shall be applicable.
National Fire Protection Association (NFPA): NFPA 110 Standard for Emergency and Standby Power Systems Underwriters Laboratories, Inc. (UL) American Society for Testing and Materials (ASTM) Including but not limited to: ASTM D975 The Joint Commission (TJC) Environment of Care Manual
Notification/Coordination
Upon award the Contracting Officer (CO) may designate a Representative (COR) to supervise the work performed for the duration of this contract. However, in no event, will any understanding, agreement, modification, change order, or other matter deviating from the terms of the contract between the contractor and any person other than the CO be effective or binding upon the Government, unless formalized by proper contractual documents executed by the CO, prior to completion of this contract. A copy of this designation shall be furnished to the Contractor.
The contractor shall perform triennial testing during the base year to set the cyclic period for this requirement. Within thirty days after contract award, for base and option years, the contractor shall provide the VA with an annual inspection and testing schedule, distinguishing between yearly and triennial events. The estimated yearly schedule is subject to COR approval. The Contractor shall provide the COR a finalized schedule for each task 30 days before the intended inspection and testing to confirm the scheduled date is still acceptable.
The Contractor and any Subcontractor shall report to the COR when arriving to perform any service under this requirement, including repairs only at the Walla Walla location. The contractor shall call the COR and coordinate with the clinic manager when arriving at the VA clinic. Check-in/out is mandatory at VA Police to obtain temporary badge. When the service is completed, the Contractor and any Subcontractor shall check out with the COR as well.
The Contractor shall coordinate with the Subcontractor directly for any tasks associated with SOW. It is the responsibility of the Contractor to ensure Subcontractor performs all work in accordance with the SOW.
Deliverables
Inspection/Testing Reports
When inspections are completed at the end of each day before the field technician leaves the site, they are required to furnish a digital or electronic copy of their field testing notes to the COR.
Deliver the final report to the COR no more than 30 days after completion of inspection and testing. This will be in electronic format.
If deficiencies are discovered during inspection and testing, the final report and the field testing notes are required to have a description of the system conditions, description of corrected measures needed and any other special notes (tests conducted and maintenance work that may need to be performed). The service technician signs and submits this form to the COR.
All services under this contract shall conform with the National Fire Protection Agency (NFPA), Occupational Safety and Health Administration (OSHA), and Original Equipment Manufacturer standards and specifications.
Inspection and Acceptance Criteria
The COR is responsible for monitoring and inspecting work performed under this contract is in accordance with the Statement of Work.
The Contractor and COR will work together to resolve deficiencies. Work not completed or not acceptable under general industry standards cannot be certified for payment.
Standards and Qualifications
Generator Testing and Maintenance
All Generator Technicians shall have the experience and training to perform the work and hold a current license or certification for installation of the systems involved. They must be certified by Caterpillar Inc. (CAT) through their training programs or by official documentation.
Number of Employees. The Contractor shall always have available a sufficient number of capable and qualified employees to enable the contractor to properly, adequately, and safely perform all work required under the terms of this contract.
Licenses & Permits. Contractor and subcontractor personnel engaged in the activities specified by this contract shall be also required to possess certificates of training, licenses, and permits as required by the state, county, parish, city, and other local jurisdictions.
Documentation. The Contractor shall provide to the Contracting Officer Representative (COR) or Contracting Officer Designee documentation of the certificates of training, licenses, and permits for all new employees not later than seven (7) days prior to that person beginning work under the terms of this contract. licenses, permits, and bonds are current and valid. All offers must include documentation and proof of the above certifications and qualifications for each employee.
Damage to Generators: Any damage to the generator or associated equipment (e.g. fans, pumps, electrical switchgear) caused by normal testing shall be repaired by the Contractor at no additional cost to the Government. At its discretion, the Government may have representatives present to witness any or all such tests. All costs associated with this damage shall be borne by the Contractor.
Work Hours
Normal Work Hours are defined as Monday through Friday from 8 a.m. to 4:30 p.m., excluding federal holidays or as otherwise arranged with the COR. The COR will communicate with the Contractor if work, inspection, testing, repair, etc. is able to be scheduled during normal work hours.
After Hours. The Contractor shall be required to perform some work, inspection, test, and repair outside the normal working hours of the building occupants or due to emergency conditions. Any scheduled work that is disruptive to the tenants during annual and triennial tests (generator noise or fumes from generator) shall be performed after the building occupant's normal working hours for the following generators: B86 Caterpillar/LC5, B86 Caterpillar C18, and B143 Caterpillar/L7C.
The holidays observed by the Federal Government are New Year's Day, Martin Luther King Day, President's Day, Memorial Day, Juneteenth, Independence Day, Labor Day, Columbus Day, Veterans Day, Thanksgiving Day, and Christmas Day. Also, any other day declared by the President of the United States to be a national holiday.
Risk Control
The Contractor shall comply with all applicable Federal, State, and local laws and regulations to include responsibility to conform by current Occupational, Safety, Health Administration (OSHA) & Environmental Protection Agency (EPA) regulations while working on this facility. Contractor shall comply with Walla Walla VA safety, security, and screening requirements.
Contractor is responsible for all reports required or requested by Federal, State and Local ordinances that pertain to any duties contained in the contract.
All Contractor employees must wear a reflective vest or suitable substitute approved by the COR.
All equipment operators shall yield to all pedestrians and traffic. All trucks that are hauling generator equipment must have proper company identification prominently displayed on them to inform facility police when they are conducting rounds.
Contractor shall take all precautions necessary to protect persons and property from injury or damage during the performance of this contract. Contractor shall be responsible for any injury to any Contractor s representative, or others, as well as for any damage to any personal or public property that occurs during the performance of this contract that is caused by the Contractor s fault or negligence.
The Government shall inform the Contractor of any known ACM in a generator enclosure. If the Contractor must disturb materials he suspects may contain ACM, the Contractor shall immediately report it to the Contracting Officer Representative (COR) or Contracting Officer Designee, and the Contracting Officer Representative (COR) or Contracting Officer Designee will investigate and instruct the Contractor how to avoid an airborne asbestos exposure.
Lead -Based Paint: The Government shall inform the Contractor of any known lead-based paint in a generator enclosure. If the Contractor must disturb materials he suspects may contain lead-based paint, the Contractor shall immediately report it to the Contracting Officer Representative (COR) or Contracting Officer Designee, and Contracting Officer Representative (COR) or Contracting Officer Designee will investigate and instruct the Contractor how to avoid lead-based paint contamination.
Housekeeping. The Contractor shall leave areas where he performs work neat, clean and orderly.
All damage done by the Contractor shall become the Contractor s responsibility and expense.
Contractor and/or Sub-contractor shall not have any history of previous safety violations at the Walla Walla VA campus.
Security Requirements
Following contract award, the Contractor is required to present a list of personnel and their qualifications, to include a contract manager that will supervise the performance of this contract to the Contracting Officer. All supervisory Contractor personnel shall be able to communicate well with the COR or designee. All Contractor employees are subject to current Medical Center Directives applicable to their conduct.
Government-Furnished Equipment (GFE)/Government-Furnished Information (GFI).
Not applicable
Contract Administrator
The Contractor shall establish processes and assign appropriate resources to effectively administer the requirement. The Contract Administrator shall respond to Government requests for contractual actions in a timely fashion and take immediate action to correct any deficiencies found. The Contractor shall have a single point of contact between the Government and Contractor personnel assigned to support the contract. An alternate point of contact may be assigned at the approval of the Contracting Officer. The Contract Administrator shall attend Quarterly Meetings as described below.
Contract Administrator shall in-person attend Annual Inspection and supervise any contractor or subcontractor personnel. Contract Administrator shall meet with COR while on-site to discuss any pertinent inspection information, deficiencies, and/or future coordination items.
Contract Administrator shall be the main POC for Repairs and Rider work unless an Alternative POC is approved by the COR. The Contract Administrator will respond promptly to CFR and emergent requests and coordinate all aspects of the work diligently with any Contractor or Subcontractor personnel while informing the COR daily of status and coordinating further approval as applicable.
Contract Administrator shall ensure all submitted invoices are correct and verifiable in accordance with invoices procedures outlined.
The Contract Administrator and/or assigned alternate shall be able to communicate well with the COR or designee and respond within one (1) business day to COR and/or CO inquiries.
Deliverable: Contractor shall provide Contract Administrator name, email, direct phone information and resume at quote submission and three (3) business days after change of personnel to the Contracting Officer and COR.
Miscellaneous
Government does not pay for services not received.
Appendix A: Generator Inventory and Fuel Tank Locations Generator Inventory Location Building Make/Model Voltage Rated KW Load Testing Required B86 Caterpillar/LC5 208 250 Yes B143 Outpatient Clinic Caterpillar/L7C 480 600 Yes B78 Theater John Deere/A75JFTL3 208 90 Yes B76 Boiler Plant Caterpillar/C7.1 208 260 Yes B140 RRU Generac/13653720100 480 150 Yes B145 Specialty Care Clinic Caterpillar/LC5 480 175 Yes B74 Cummins QSB7 480 125 Yes B86 Caterpillar/C18 480 600 Yes Fuel Tank Inventory Tank # Building Location Reason Gallons Quantity Above/Underground 1 76 Next to Boiler Plant, behind double set of steel doors Boiler Contingency Fuel 20,000 2 Underground 2 76 Behind 76 with set of double steel doors Fuel for 76 Generator and 80 Generator 6500 1 Underground 3 78 West end of 78 covered by concrete pad Fuel for 78 Generator 1100 1 Underground 4 86 South end in walled enclosure Fuel for Adjacent Generator 480 1 Aboveground 5 140 West side of building Fuel for 140 Generator 480 1 Aboveground 6 143 Southeast corner of building in walled enclosure Fuel for 143 Generator 900 1 Aboveground 7 145 Southwest corner of building in walled enclosure Fuel for 145 Generator 900 1 Aboveground 8 86 Double walled integrated tank, south end of building Fuel for Adjacent Generator 380 1 Aboveground 9 74 Right next to generator in double walled tank Fuel for Building Generator 350 1 Aboveground

More opportunities from Department Of Veterans Affairs → 260-NETWORK Contract Office 20 (36C260)

Same awarding agency

NAICS: 238220
New
Federal
J041--White City B249 SE HVAC Repair
Solicitation # 36C26027Q0102
Solicitation 36C26027Q0102 is a total set-aside for certified Service-Disabled Veteran-Owned Small Businesses (SDVOSB) issued by the Department of Veterans Affairs. The contract requires the repair of a Mitsubishi R-410A comfort-cooling system (Serial 07W0090) located on the southeast side of Building B249 at the VA Southern Oregon Rehabilitation Center and Clinics in White City, Oregon. The scope of work includes leak detection, brazing repairs with nitrogen purge, refrigerant recovery, evacuation to less than 500 microns, and recharging the system to nameplate requirements. The contractor must provide a detailed service report documenting the root cause, repair actions, and compliance with EPA Section 608 and VHA ICRA/PCRA controls for occupied healthcare facilities. The period of performance is 30 calendar days from the Notice to Proceed. Award will be granted to the responsible offeror whose proposal is most advantageous to the government, considering price and other specified factors. Key regulatory requirements include adherence to OSHA 29 CFR 1910.147 for lockout/tagout and 29 CFR 1910.333 for electrical safety. Payments will be processed via Electronic Funds Transfer, and invoices must be submitted electronically through the Tungsten Network. Offerors must provide their Unique Entity Identifier and maintain firm pricing for 60 calendar days from the response deadline of November 10, 2026.
Plumbing, Heating, and Air-Conditioning Contractors

POSTED

1 day ago

DEADLINE

in 12 days
View Details
NAICS: 334513
New
Federal
Boiler Plant O2 Sensor Replacement
Solicitation # 36C26027Q0101
The Department of Veterans Affairs, through the Network Contract Office 20, is conducting market research via a Sources Sought Notice for a firm-fixed price service contract to perform inspection, testing, maintenance, and repair of three model 6888 Rosemount flue gas analyzers. The work will be performed at the VA Southern Oregon Rehabilitation Center and Clinics in White City, Oregon. The primary scope involves replacing internal O2 analyzer components using original equipment manufacturer parts, specifically 18 inch standard cells, 18 inch heater strut assemblies, Hastelloy with Vee Deflectors for service up to 1300 degrees Fahrenheit, and new flange gaskets. The period of performance is six months, with on-site work required during core hours of 7:00 AM to 4:00 PM, Monday through Friday. This opportunity is designated as a total Small Business Set Aside under NAICS code 334513, with a size standard of no more than 750 employees. Qualified sources, including SDVOSB and VOSB entities, must provide company details, SAM.gov UEI numbers, and proof of manufacturer authorization if they are not the OEM. Contractors must employ qualified personnel, maintain general third-party liability insurance per FAR 52.228-5, and adhere to NEC, OSHA, and JCAHO standards. Deliverables include written daily reports to the Deputy Chief Facilities Management and testing documentation provided to the Contracting Officer's Representative. Interested parties are requested to provide a courtesy quote and capability statement to assist the government in evaluating price reasonableness and market availability.
Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial Process Variables

POSTED

2 days ago

DEADLINE

in 5 days
View Details
NAICS: 325998
New
Federal
Microbiological media purchase order for Clinical Microbiology laboratory.
Solicitation # 36C26027Q0104
The Department of Veterans Affairs Network Contracting Office 20 is seeking sources for a microbiology testing media purchase order to support the Seattle Division of the VA Puget Sound Medical Center. This requirement covers a wide range of critical supplies for identifying pathogenic organisms in veteran patients, including long shelf-life products like Oxidase and Indole, perishable selective agar, biochemical test kits, and ATCC organisms mandated by the College of American Pathologists for quality control. The contract is structured with a base year running from February 1, 2027, to January 31, 2028, followed by four subsequent one-year option periods ending January 31, 2032. Deliveries are to be made to the Microbiology Lab in Seattle, with weekly shipments typically scheduled for Tuesdays and individual requests fulfilled as available. Due to the perishable nature of many items, the vendor must provide tracking information, and the cost of next-day delivery for all perishable goods must be included in the individual item price. All temperature-liable products require immediate refrigeration upon delivery. Invoicing is processed through the Austin Automated Payment System in Texas, and the vendor must provide SDS sheets for all media upon request. This sources-sought notice specifically looks for capable sources, including qualified SDVOSB/VOSB entities, with a response deadline of November 10, 2026.
All Other Miscellaneous Chemical Product and Preparation Manufacturing

POSTED

2 days ago

DEADLINE

in 12 days
View Details
NAICS: 238220
New
Federal
Z1DA--CON-NRM-668-22-106 Correct Domestic Water System
Solicitation # 36C26027R0014
Solicitation 36C26027R0014 is a negotiated request for proposals for the Department of Veterans Affairs to correct domestic water system deficiencies in Buildings 1 and 12 at the Mann-Grandstaff VA Medical Center in Spokane, Washington. The project is 100% set aside for Service-Disabled Veteran-Owned Small Businesses under NAICS 238220, with an estimated contract magnitude between $1 million and $2 million. The primary objective is to modify hot and cold potable water distribution systems to comply with VHA Directive 1061 for the prevention of scald injuries and Health Care-Associated Legionella Disease. The scope includes all labor, materials, and equipment, with a specific requirement to flush potable water dispensing fixtures twice weekly from installation until final acceptance. The period of performance is 275 calendar days from the Notice to Proceed. The government will utilize a Best Value tradeoff process for award, prioritizing technical experience and past performance over cost. Technical evaluations will favor offerors with demonstrated experience in phasing and Infection Control Risk Assessment (ICRA) within 24-hour operational emergency rooms. Proposals must be submitted in three separate volumes—Technical, Past Performance, and Price—by November 23, 2026. Awardees must provide performance and payment bonds, adhere to Davis-Bacon Act wage determinations, and comply with Buy American requirements. Additionally, the contractor must maintain strict confidentiality regarding sensitive information and provide a one-year warranty on all materials and installation.
Plumbing, Heating, and Air-Conditioning Contractors

POSTED

2 days ago

DEADLINE

in about 1 month
View Details

Earlier notices in this NAICS code

Posted before this notice, open and closed

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS