J045--Boiler Safety Device Testing/Inspection Services
Contract Overview
Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.
AI Contract Overview
Contract 36C25626C0030 was awarded to ATZ Solution LLC on March 31, 2026, for a total amount of $165,000.00. The contract provides boiler safety device testing and inspection services for the Central Arkansas Veterans Health Care System, specifically serving the Eugene J. Towbin Healthcare Center and the John L. McClellan Memorial Veterans Hospital. The scope of work includes safety device testing for six fire tube boilers, two feed water deaerators, and two condensate tanks, as well as combustion analysis and adjustments. All services must be performed in accordance with the 7th Edition of the VHA Boiler Plant Safety Device Testing Manual using NIST-traceable calibration instruments. The agreement is a total small business set-aside under NAICS code 238220 and features a five-year period of performance consisting of a base year starting February 1, 2026, and four subsequent one-year options extending through January 31, 2031. Performance is managed by Contracting Officer Arlene A. Blade and COR John Ringo, with a requirement that only one boiler be out of service at a time to maintain facility operations. Payments are processed electronically via the VA Electronic Invoice Presentment and Payment system. The award was determined through a trade-off process where technical capability and past performance were weighted more heavily than price.
General Info
Contract Value
$29,000Place of Performance
MS, USASet-Aside
Awardee
ATZ SOLUTION LLCAward Issued Date
Timeline
Organization & Contact Information
Full Description
AMENDMENT 0004- The purpose of this amendment is to provide responses to vendors' questions. The following responses are provided: (SEE ATTACHMENT)
- Question 1: Place of Performance (pages 2 & 3):
Please confirm that there are two separate locations where services are required:
- Eugene J. Towbin Healthcare Center: 2200 West Fort Roots Drive North Little Rock, AR 72114.
- John L. McClellan Memorial Veterans Hospital: 4300 W 7th St. Little Rock. AR 72205.
Answer 1: Services are required at the two separate locations listed above.
- Question 2: Internal Boiler Inspection Requirement:
The PWS document does not specify whether annual internal boiler inspections are required. Please confirm if this contract includes internal inspections performed by a National Board (NB) / ASME-certified boiler inspector, or if the scope is limited strictly to safety device testing
If internal inspections are required, please confirm whether:
- VA will open, drain, clean, and prepare the boilers
- Any state of Arkansas jurisdictional inspection coordination is required under this contract
Answer 2: Safety device testing only.
- Question 3: Non-Destructive Testing (NDT):
The PWS document does not specify any non-destructive testing (NDT) requirements for boilers, deaerators, or condensate tanks. Please confirm whether any NDT services are included or excluded from this contract.
Answer 3: Safety device testing only.
- Question 4: VHA Boiler Plant Safety Device Testing Manual – Edition Conflict: The PWS references two (2) editions: Page 12 and Section 1.e/f reference the Fifth Edition. Section 1.b.v references the Seventh Edition. Please confirm the official edition of the VHA Boiler Plant Safety Device Testing Manual that the contractor is required to follow.
Answer 4: The official edition of the VHA Boiler Plant Safety Device Testing Manual that the contractor is required to follow is the most current, 7th Edition.
- Question 5: OEM Authorization:
Please confirm whether OEM authorization letters are required for:
- Each boiler manufacturer (Superior and Johnston)
- Burner management systems and safety controls (if different OEMs apply)
Also, please confirm whether subcontractors performing testing must also hold OEM authorization, or if authorization held by the prime contractor is sufficient.
Answer 5: OEM authorization letters are not required but will be accepted. However, contractor shall provide proof of certification attesting that all gauging and measurement equipment used has been currently calibrated either according to the manufacturer’s specifications or a standard traceable to the National Bureau of Standards. Combustion Analysis and Safety Device Testing personnel shall be qualified for boiler plant burner, control and instrumentation testing. Qualifications include completing at least a one-year trade school and five years of successful experience in this field. The experience shall be largely with institutional and industrial boiler plants similar in design to the VAMC plants.
- Question 6: Repairs and Out-of-Scope Work:
The PWS document indicates that adjustment and calibration of safety devices. Please clarify:
- Are minor adjustments and calibrations included in the base scope? :
- Are repairs, parts replacement, or corrective maintenance excluded and must be quoted separately?
- Should the contractor provide written repair recommendations only, or
- Is the contractor expected to submit repair quotes under this contract?
6. Answer 6:
- a. Minor adjustments and calibrations: Yes if adjustments can be made to bring device into compliance. If necessary, make adjustments to the fuel flow and combustion air controllers, control valves and dampers to obtain the required performance.
- Repairs, parts replacement, or corrective maintenance are excluded. Contractor shall immediately inform COR of any recommended repairs, modifications, or safety related problems. Contractor can quote separately if desired.
- Yes, contractor shall provide written repair recommendations only.
- Question 7: Emergency Call-Out Services
The PWS document does not reference emergencies, after-hours, or unscheduled call-out services related to boiler, burner, or safety device failures discovered during or outside the scheduled semi-annual testing. Please confirm whether emergency response or on-call services are:
- Included within the scope of this contract, or
- Excluded and to be handled under a separate contract or task order.
If emergency services are included, please clarify:
- Required response time (e.g., 2-hour, 4-hour, same-day)
- Whether after-hours, weekend, or holiday work may be required
- How these services are to be authorized and charged. There is not a CLIN number added to the cost schedule.
Answer 7: Emergency responses or on-call services are not included in this contract.
End
Similar Contracts
Same NAICS industry code
More opportunities from Department Of Veterans Affairs → 256-NETWORK Contract Office 16 (36C256)
Same awarding agency
Ready to Pursue This Opportunity?
Get AI-powered intelligence on this solicitation and the ones like it
Every page of the solicitation package shredded into a compliance breakdown
AI-powered matching based on your capabilities and past performance
Competitor and incumbent history on the requirement
Automated alerts on amendments, Q&A deadlines, and award
Join 750+ contractors already using CLEATUS