KSU-27S034
Contract Overview
Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.
AI Contract Overview
Kent State University is seeking proposals for the full replacement of two VRF systems at Stewart Hall, which serve approximately 14,700 square feet of the facility. The existing systems, installed during a 2010-2011 renovation, have reached the end of their service life due to compressor and valve failures caused by improper nitrogen purging and debris. The project requires the complete removal and replacement of outdoor units, branch controllers, 47 indoor units, equipment supports, and all refrigerant piping. While existing electrical feeders, power wiring, and condensate drain piping may be reused, the contractor is responsible for any necessary removal and replacement of wall, floor, and ceiling materials to facilitate the installation. The new installation must utilize individual outdoor units rather than twinned equipment, with nominal capacities that match the sum of connected indoor units to avoid reliance on load diversity. The systems must integrate with the university's Johnson Controls BAS via new interface controllers. Other building HVAC components, including the RTU with VAV/RH terminals and the heating water system, will remain operational during the project. Interested parties should note the pre-proposal meeting on December 8, 2026, with a final response deadline of December 18, 2026.
General Info
Place of Performance
Set-Aside
Documents
0No documents available
Documents will appear here when they are available.
AI Contract Breakdown
Uniform Contract FormatNo documents to break down
The breakdown needs solicitation documents. None were found from this contract's source.
Ask CLEATUS
I've read this contract. Ask me anything.
Timeline
Solicitation
Submission deadline
Response Deadline
Organization & Contact Information
Full Description
Stewart Hall was constructed in approximately 1967 as a small group residential housing and dining facility. It was renovated in 2010-2011 for administrative/office functions when the current HVAC systems were installed. The two (2) VRF systems installed at that time have reached the end of their beneficial service life and need to be replaced in their entirety. We expect the RTU with VAV/RH terminals, heating water system and equipment, and the 100% OA/EA HRU to remain in place and in service during this project. The existing VRF systems consist of (2) outdoor units with twinned outdoor equipment, 3 branch controllers, and 47 total indoor units. Both complete systems need to be replaced, including the outdoor units, branch controllers, indoor units, equipment supports, controllers, and all refrigerant piping. Control and power wiring and condensate drain piping may be possible to re-use. The current VRF systems serve approximately 14,700 square feet of the building’s roughly 23,000 square feet (net).
When originally installed, adequate nitrogen purge was not provided and debris and moisture has fouled compressors and refrigerant control components. The system has also experienced failures of check valves and linear expansion valves. The combination of debris, compressor failures, and refrigerant valve failures, paired with equipment that relies on load diversity, have left KSU with a system that is no longer able to provide adequate heating and cooling to the interior spaces and occupants.
We would like to replace the existing VRF systems with new VRF systems due to the tight floor to floor heights available and the unavailable location for chillers and piping and pumping equipment. The new systems will keep the current at-grade location of the outdoor units, and will re-use the indoor unit and refrigerant valving locations with similar equipment.
The new systems should also not rely on diversity of load; the outdoor units should have the same nominal capacity as the sum of the connected indoor units’ capacities to the greatest extent possible. Re-use of the existing electrical feeders is expected. New outdoor units shall operate individually, not be twinned or paired together, and shall serve a single refrigerant valving unit and associated indoor units. New VRF system controls shall be provided. New interface controllers will be required between the VRF system and KSU’s Johnson Controls BAS. Removal and replacement of any and all wall, floor, and ceiling materials is expected to occur under this project; this is expected to occur to accommodate replacement of all refrigerant piping/insulation and control wiring.
Interested parties may attend a pre-proposal meeting on December 8 2026, at 9 am in Room 102 Harbourt Hall, 615 Loop Road, Kent, Ohio 44242.
Similar Contracts
Same NAICS industry code
More opportunities from Ohio → Kent State University - Office of the University Architect
Same awarding agency
Get AI-powered intelligence on this solicitation and the ones like it
Every solicitation package arrives shredded into a compliance breakdown and matched to your past performance, with incumbent history and alerts on amendments and award.
Join 900+ contractors already using CLEATUS