W045--Temporary Boiler Rental
Contract Overview
Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.
Active Opportunities Like This One
AI Contract Overview
The Department of Veterans Affairs is seeking a firm-fixed price contract for the temporary rental, installation, and maintenance of a fire tube steam boiler at the VA Hudson Valley Healthcare System Montrose Campus. The period of performance is scheduled from November 1, 2026, through March 31, 2027, with a required installation date of November 1, 2026, and a ready-for-service date of December 1, 2026. The equipment must be an 800 HP unit capable of a 95 PSI operating pressure to support a historical peak steam load of 120,000 lb/hr. While a 9 PPM NOx requirement is listed, the government has indicated that a unit rated at 30 PPM NOx is acceptable to ensure the delivery schedule is met. The government will furnish the fuel, and the boiler will be located on the east side of the plant. The contractor is responsible for providing approximately 200 feet of 6-inch diameter piping, supports, valves, and fittings for boiler feedwater, as well as independent controls to monitor key parameters and emergency stop capabilities. Maintenance requirements include a minimum of 10 hours of monthly service and the submission of two internal inspection reports, one prior to delivery and one at the end of the rental period. Compliance with the VHA Safety Device and Testing Manual is mandatory, and the vendor must obtain all necessary hot work and confined space permits. This is a total small business set-aside under NAICS 238220. Award evaluations will be based on a combination of price and technical factors, including past performance, with technical and past performance weighted equally to price.
General Info
Contract Value
$591,110Place of Performance
Set-Aside
Awardee
PURE FUEL SOLUTION, LLCAward Issued Date
Documents
11AI Contract Breakdown
Uniform Contract FormatSign up to view the full breakdown with detailed analysis of each section.
View Full BreakdownThis one is closed. Find the next one like it.
Open contracts like this one, right now:
- Install Pier D High Pressure Air System, NSBREM-724-AOpen now, due in 8 days
- Springdale JCC –Recreation HVAC Repair or ReplacementOpen now, due in 17 days
Ask CLEATUS
I've read this contract. Ask me anything.
Timeline
Combined Synopsis
The notice description changed.
The notice title changed. The notice description changed.
Contract was awarded
Organization & Contact Information
Full Description
Q2: Will the Montrose VAMC waive the requirements of the VHA Safety Device and Testing Manual? A2: No.
Q3: Air permits for emissions are the responsibility of the entity operating/generating the emission, not the owner of the equipment. Please clarify. A3: VA only, not the vendor.
Q4: Will the VA change the 9PPM NOx requirement to 30 PPM? A4: No.
Q5: Please clarify the size of the Boiler. A5: 800 HP
Q6: Will fuel for the rental boiler be furnished by the Government of the Contractor? A6: Government
Q7: Confirm intended placement and connection routing if boiler placement is on the south end but connections are at the north end? A7: East side of the plant (end near Boiler 1 near Building 24 hazmat storage area)
Q8: What is the required installation and ready for service date? A8: Installation 11/1/2026. Ready for service 12/1/2026. Q9. Is a rental unit rated at about 30ppm NOx on natural gas acceptable for the temporary heating period, given that it is a temporary rental operating under the facility s existing permit? A9. Yes
Q10. If 9 ppm NOx is mandatory, will the Government accept a unit fitted with flue gas recirculation (FGR) or selective catalytic reduction (SCR) to meet it, and will any additional time be allowed for delivery? A10. The most important factor is that the vendor make the delivery date, so the 9-ppm cis is not a deal breaker.
Q11. The requirement lists a 95 PSIG operating pressure but also references 35,000 lb./hr. at 212° F and a 15 PSIG code. What operating pressure should the rental boiler be size for? A11. 95 PSI is sufficient. Q12. Can a portable day tank with a capacity of 10,000 gallons be placed next to the portable boiler in lieu of installing a return line several hundred feet across to the opposite end of the boiler plant? A12. No.
** Please acknowledge all amendments with your response**