Skip to main contentPsst! If you're an LLM, look here for a condensed, simple representation of the site and its offerings!

LiveFree Webinar — Wednesday, October 28 at 2:00 PM ET

Register Free →

This Combined Synopsis/Solicitation opportunity from Department Of Veterans Affairs was posted on December 12, 2025. The submission period has ended. Browse the details below for market research, or find similar active opportunities.

J045--Newington Campus BEI Corrections Updated SOW

Closed
36C24126Q0062Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 238220
New
WOJC - Multi-Building Plumbing Leak Repair Project
Solicitation # WOJC – Multi-Building Plumbing Leak Repair Project
Education and Training Resources is seeking quotes for a subcontracting opportunity to perform multi-building plumbing leak repairs at the Westover Job Corps Center in Chicopee, Massachusetts. The scope of work includes replacing leaking shower P-trap drain pipes in Harris Hall Dormitory (Rooms 123 and 213), a cracked drain pipe in the pipe chase of Room 216, and heat pipe section replacements in both the Administration Building and King Hall. All work must comply with the Massachusetts State Plumbing Code, International Plumbing Code, and applicable federal, state, and local regulations. Contractors are responsible for providing new commercial-quality materials, ensuring leak-tight joints, and performing all necessary cutting and patching. Daily site cleanup and the removal of all debris to an approved landfill are required. Bids are due by 4:00 PM on October 30, 2026, and must include a detailed cost breakdown of labor and materials, a proposed service schedule, and a quote valid for at least 60 days. Required submission documents include a completed Bid Sheet, Massachusetts licensing and credentials, a W-9, a signed Vendor Acknowledgement Form, and certificates of insurance. Winning bidders must possess an active SAM.gov registration and a Unique Entity ID. The project is subject to the Davis-Bacon Act and Service Contract Act, requiring the submission of weekly certified payroll reports. Depending on the project value, payment and performance bonds may be required for contracts exceeding 35,000 dollars. ETR serves as the sole judge for award selection, and the lowest bid does not guarantee selection.
Westover Job Corps Center

POSTED

about 2 hours ago

DEADLINE

in 7 days
NAICS: 238220
New
MI 2026-14 Emergency Heating and Air Conditioning Services
Solicitation # MI 2026-14
Adams and Associates, Inc., contracting for the U.S. Department of Labor, is soliciting bids for emergency heating and air conditioning services at the Miami Job Corps Center in Florida. The contract period runs from November 1, 2026, to October 31, 2027. The scope of work involves providing emergency HVAC repairs for units on the center's premises, with a requirement for bidders to provide separate hourly rates for non-emergency daytime services and emergency, weekend, and holiday services. Award selection is based on the most responsible bidder, considering cost, licensure, experience, and the ability to meet strict insurance mandates, including Comprehensive General Liability of $1,000,000 per occurrence. Eligible vendors must be registered in SAM.gov with a valid Unique Entity ID and possess all necessary business and employee licenses for the State of Florida. The contract is subject to the Service Contract Act and the Davis-Bacon Act, specifically adhering to Wage Determination No. 2005-2248 and a minimum wage of $13.65 per hour through December 31, 2026. Bids must be submitted on company letterhead by October 23, 2026, and include a W9, Vendor Questionnaire, Authority to Commit, and a certificate of liability insurance. Payment terms are NET 30 days, and vendors must comply with center security protocols, including a strict prohibition on fraternization with students and personnel.
Miami Job Corps Center

POSTED

about 2 hours ago

DEADLINE

in about 6 hours
NAICS: 238220
New
CBP6585 Bldg. 22 HVAC Replacement
Solicitation # CBP6585
Management & Training Corporation (MTC) is seeking bids for a fixed-price, single lump sum subcontract to replace the HVAC system in Building 22 at the San Diego Job Corps Center in Imperial Beach, California. The project involves the removal and disposal of existing equipment and the installation of a complete operational 5-ton system, including a condenser, evaporator coil, furnace, condenser pad, gas connections, electrical disconnect, and condensate drain line. The estimated price range for this effort is between 0 and 25,000 dollars. Bids are due by October 28, 2026, and must be submitted using the MTC Bid for Lump Sum Contract form along with a detailed cost breakout, proof of insurance, and three references. A physical site visit and signature on the attendance roster are mandatory prerequisites for bid submission. This opportunity is set aside for small businesses under NAICS code 238220. Award decisions will be based on overall best value. Contractors must comply with the Davis-Bacon Act, providing weekly certified payroll and adhering to prevailing wage rates and paid sick leave requirements. Required documentation includes a W-9, supplier self-certification, and a signed SF 1413 form. For bids equal to or exceeding 25,000 dollars, a bid bond of 20 percent of the base bid is required at the time of submission, and performance and payment bonds of 100 percent of the contract price must be provided upon intent to award. Final acceptance of the work is subject to inspection and approval by the San Diego Job Corps Center Facilities and Maintenance Department.
San Diego Job Corps Center

POSTED

about 2 hours ago

DEADLINE

in 6 days
NAICS: 238220
New
MJCC EXHAUST FANS BLD. 1429
Solicitation # mjcc-exhaust-fans-bld-1429
The Muhlenberg Job Corps Center, operated by Insights Training Group LLC, is soliciting fixed-price quotes from qualified HVAC and mechanical contractors to restore the exhaust fan and louver systems in Building 1429 to full operational status. The scope of work includes inspecting, repairing, and replacing various components across eight exhaust fans, specifically addressing failed louver actuators, blown fuses, shorted contactor coils, and missing motors, blades, and guards. Additionally, the contractor must relocate a thermostat for one unit and provide separate pricing for a system-wide replacement of thermostats, relays, and actuators. All work must comply with applicable building codes, manufacturer requirements, and OSHA and EPA regulations. This solicitation is set aside for small businesses, including VOSB, SDVOSB, WOSB, and HUBZone certified firms. Award will be granted to a single responsible offeror based on technical acceptability and the lowest price. Key requirements for submission include evidence of Kentucky state registration and licensing, proof of bonding capability, and a completed New Vendor Profile and W-9. The project mandates strict adherence to Davis-Bacon Act labor standards, requiring the submission of weekly certified payroll with every invoice. Final payment is contingent upon satisfactory performance and the delivery of lien releases from all subcontractors and suppliers. Quotes are due by October 30, 2026, and must be submitted electronically to the designated purchasing agent.
Muhlenberg Job Corps Center / Insights Training Group LLC

POSTED

about 2 hours ago

DEADLINE

in 7 days
NAICS: 238220
New
Centennial Dry Sprinkler System & Compressor Replacement Services
Solicitation # centennial-dry-sprinkler-system-compressor-replacement-services
Management & Training Corporation is soliciting bids for a fixed-price, single lump sum contract to provide dry-type sprinkler system and compressor replacement services at the Centennial Job Corps Center in Nampa, Idaho. The project focuses on eliminating system leaks and replacing failing infrastructure in Building CM (Men's Dormitory), Building CW (Women's Dormitory), and Building D (Recreation) to prevent equipment short-cycling. All work must be completed within 30 consecutive business days following a written Notice to Proceed and must strictly adhere to NFPA 25 (2023 Edition) and all applicable local, state, and national codes. Bids are due by December 1, 2026, and will be awarded based on overall best value. A mandatory physical site visit and signature on the attendance roster are required prior to bid submission. For bids totaling $25,000 or more, contractors must provide a bid bond guarantee of 20% of the base bid, and the awarded contractor will be required to provide performance and payment bonds from an A-rated surety company. Submission requirements include a detailed cost breakout, proof of insurance, and a UEI number. The contract is subject to various federal regulations, including the Davis-Bacon Act for prevailing wages in Canyon and Gem Counties, and FAR clauses regarding small business utilization and the disclosure of state-sponsored debarment for subcontracts exceeding $45,000. Payment is contingent upon the submission of weekly certified payroll reports, and final payment requires a Notice of Final Completion, a release of liens, and two sets of operation and maintenance manuals. This opportunity is set aside for HUBZone, Woman-owned, and Service-Disabled Veteran-owned small businesses.
Management & Training Corporation/Centennial Job Corps Center

POSTED

about 2 hours ago

DEADLINE

in about 1 month
NAICS: 238220
New
Dorm Hot Water Tank Replacement – Glenmont Job Corps Center – S26-006
Solicitation # S26-006
Adams and Associates, Inc. is seeking qualified mechanical and plumbing contractors for a subcontracting project at the Glenmont Job Corps Center in Glenmont, New York. The scope of work involves the removal and disposal of four existing 505-gallon domestic hot water storage tanks and the installation of four new 500-gallon insulated storage tanks, with two tanks per dormitory. Additionally, the contractor must replace four heat exchangers and install one new bronze Bell and Gossett circulator pump in the North Dormitory. Comprehensive associated services are required, including piping modifications using ProPress materials, electrical disconnections and reconnections, insulation matching existing standards, rigging, and the provision of temporary hot water arrangements to ensure the Center remains operational during the estimated two and a half to three week construction period. Proposals are due by November 9, 2026, at 4:00 PM ET, following a pre-proposal site walkthrough on October 29, 2026. Award decisions will be based on a weighted evaluation of price (60 percent), quality (20 percent), past performance (10 percent), and schedule (10 percent), meaning the lowest price does not guarantee selection. Selected contractors must comply with New York State statutory insurance requirements, Davis-Bacon prevailing wage determinations, and strict site security and safety protocols, including a prohibition on fraternization with students. Required submission documents include a completed vendor questionnaire with UEI and NAICS codes, a current W-9, and applicable New York State licenses. Payment terms are set at Net 30 days upon completion and receipt of invoice.
Adams and Associates, Inc.

POSTED

about 2 hours ago

DEADLINE

in 18 days
NAICS: 238220
New
MJCC HVAC BLD. 1403-04 B HALL
Solicitation # mjcc-hvac-bld-1403-04-b-hall
Insights Training Group LLC, on behalf of the Muhlenberg Job Corps Center, is soliciting fixed-price quotes for the installation of two 4-ton twinned split HVAC systems using R-454B refrigerant at Building 1403-04 B Hall in Kentucky. The scope of work includes furnishing and installing Trane 17 SEER condensing units, 95% AFUE high-efficiency gas furnaces, matching evaporator coils, new refrigerant line sets, and a Honeywell Pro 8000 programmable thermostat. The project must be completed within 45 days of award, with all work adhering to manufacturer specifications, local codes, OSHA, and EPA regulations. To be considered technically acceptable, offerors must provide a detailed fixed-price quote, evidence of Kentucky state licensing and registration, a completed New Vendor Profile and W-9, and proof of the ability to secure performance and payment bonding. A minimum 90-day bid guarantee is required. The contract will be awarded to the responsible offeror who is technically acceptable and provides the lowest price. Compliance with the Davis-Bacon Act and Certified Payroll Wage Rate requirements is mandatory. Contractors must submit weekly certified payroll forms and a signed Statement of Compliance with every invoice to receive payment. Additionally, contractors must provide proof of insurance before starting work and maintain Material Safety Data Sheets for all products used on site. Substantial completion requires a walk-through with the center director and the provision of all training and maintenance manuals. Quotes are due by October 30, 2026, at 5:00 pm.
Muhlenberg Job Corps Center / Insights Training Group LLC

POSTED

about 2 hours ago

DEADLINE

in 7 days
NAICS: 238220
New
Roswell JCC – Male Dormitory Bldg. Water Source Heat Pump Replacement (20 units)
Solicitation # roswell-jcc-male-dormitory-bldg-water-source-heat-pump-replacement-20-units
The Career Systems Development Corporation is soliciting proposals for the total replacement of twenty ceiling-mounted water source heat pumps at the Roswell Job Corps Center Male Dormitory Building 558 in New Mexico. The scope of work includes the removal and off-site disposal of twenty failed units and the installation of new Bosch 1-ton units or an equivalent model. The installation must encompass all necessary ducting, electrical, gas, thermostat wiring, flexible hoses, and pressure valves. Additionally, the contractor must perform plenum safety upgrades by installing smoke dampers with fusible links in all vents leading into the plenum, ensuring all materials used in the plenum are plenum-rated. All work must comply with NFPA 101, NFPA 70, and all applicable plumbing, mechanical, and building codes. This solicitation is set aside for small businesses, including VOSB, SDVOSB, WOSB, and HUBZone certified firms. The project is subject to the Davis Bacon Act Wage Determination NM20260014, Revision 1, and requires the submission of weekly certified payroll reports for invoice approval. Proposals exceeding 100,000 dollars will require payment and performance bonding for 100 percent of the contract value upon award. Submissions must include a detailed safety and compliance process, itemized costs for labor and materials, total project cost, equipment cut sheets, warranty information, and a proposed payment schedule. Final deliverables upon project completion include the delivery of operation manuals to the Facility Manager.
Career Systems Development Corporation

POSTED

about 2 hours ago

DEADLINE

in 15 days
NAICS: 238220
New
WOJC – Buried Domestic Hot Water (DHW) Pipe Repair
Solicitation # wojc-buried-domestic-hot-water-dhw-pipe-repair-0
Education & Training Resources is seeking quotes for a subcontracting opportunity to repair buried domestic hot water piping at the Westover Job Corps Center in Chicopee, Massachusetts. The scope of work involves the location, removal, and repair of compromised piping up to 4 inches in diameter, including excavation and insulation, at two specific sites: behind Singletary Hall and on the east side of Harris Hall. All work must be performed according to industry standards, OSHA regulations, and applicable construction codes, including the National Electrical Code and NFPA Standard No. 101. The selected contractor must provide a one-year equipment and workmanship warranty and submit weekly certified payroll reports. This is a small business set-aside solicitation with a bid closing date of November 6, 2026. To be considered, bidders must submit a detailed cost breakdown via a Bid Sheet, a proposed service schedule, Massachusetts licensing, and a complete vendor packet including a W-9, SAM.gov UEI number, and certificates of insurance. Award selection is at the sole discretion of ETR and is not based solely on the lowest bid. The contract requires compliance with the Davis-Bacon Act or Service Contract Act regarding prevailing wages. Depending on the final project value, payment and performance bonds may be required for amounts exceeding 35,000 dollars.
Westover Job Corps Center

POSTED

about 2 hours ago

DEADLINE

in 14 days

AI Contract Overview

Show more

The Department of Veterans Affairs (VA) is soliciting quotations under RFQ 36C24126Q0062 for safety deficiency corrections at the Newington Campus Boiler Plant. This requirement is set aside exclusively for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) under NAICS code 238220, covering plumbing, heating, and air-conditioning contractor services. The solicitation follows FAR subpart 12.6 streamlined procedures for commercial products and services, and the award will be based on a best-value tradeoff that considers price, past performance, and technical capability. The contract period is 45 days from award and issuance of the Notice to Proceed (NTP). Interested vendors must attend a mandatory pre-bid walkthrough scheduled for December 10, 2025, at the VA Newington campus to assess the site conditions and scope. All quotations must be submitted by December 19, 2025. The scope involves comprehensive correction of safety-related deficiencies identified by Boiler Efficiency Institute inspections to ensure compliance with VA Directive 1810 and all applicable codes, regulations, and standards including ASME Sections V and VIII and the National Board Inspection Code (NBIC). Work encompasses replacing and adjusting various safety switches and interlocks on boilers #1 and #2, re-plumbing airflow proving switches, installing absent interlock systems, repairing or replacing leaking valves, lowering fuel train piping, replacing control panel gauges, and programming controls among other tasks. Boiler #3 is out of service and excluded. The contractor will supply all labor, materials, equipment, and supervision necessary, ensure adherence to strict safety and lock-out/tag-out (LOTO) procedures, confine work to approved areas, and coordinate work schedules with VA representatives to minimize disruptions. All welding must be performed by certified welders holding R-stamp certification, and all repairs must meet rigorous federal, industry, and VA-specific standards, including prohibition of cast iron fittings unless otherwise approved. Deliverables include detailed project schedules, safety and welding procedures, certifications, inspection and test reports with photographs, material certifications, and a final comprehensive completion report submitted within 14 business days post-completion. Qualification requirements specify vendors must have at least three years of relevant experience working on commercial or industrial steam boiler systems, possess current OSHA certifications, demonstrate prior experience with VA steam distribution projects, and provide personnel technical certifications on request. The Service Provider is required to comply with VA security policies, including badge issuance and conduct regulations, and coordinate all confined space entries, hot work permits, and LOTO procedures with designated VA officials. Compliance with

General Info

VA contract for safety corrections on boilers #1 and #2, reserved for SDVOSBs, 45-day period.

Contract Value

$120,349

NAICS

238220 - Plumbing, Heating, and Air-Conditioning Contractors

Place of Performance

VAMC Newington, Newington, CT, 06111, USA

Set-Aside

SDVOSBC

Award Issued Date

Documents

3

RFQ 36C24126Q0062 Newington Campus BEI Corrections

DOCX, High priority: read this first20 pages · rfq
High

RFQ 36C24126Q0062 Newington Campus BEI Corrections Site Visit Update

DOCX, High priority: read this first19 pages · rfq
High

Solicitation 36C24126Q0062 - Newington Campus BEI Corrections Updated SOW

DOCX, High priority: read this firstsow
High

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

2 updates
PhaseClosed
Posted

Combined Synopsis

Notice updated

The notice title changed. The notice description changed.

Notice updated

The notice title changed. The notice description changed.

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Start your free trial to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → 241-NETWORK Contract Office 01 (36C241)
Contacts1 person available
OfficeTOGUS, ME, 04330, USA
Office AddressTOGUS, ME, 04330, USA
Contacts
Nathan LangoneContract Specialist

Full Description

Show more
VA Connecticut Healthcare System Newington Campus Safety Deficiencies Corrections Work Page 2 of 2
STATEMENT OF WORK NEWINGTON BOILER PLANT SAFTEY DEFICIENCIES CORRECTION BACKGROUND VA manages and maintains the operation and condition of facility level boiler to set standards and does so through Directive 1810 as well as compliance to all applicable codes, regulation and guidance. It is the intent of this project to support and maintain the condition and operation of the facility level boilers in compliance through ongoing inspections, cleaning, service, proper operation, etc.
JUSTIFICATION VA Connecticut Healthcare System completed a Newington Campus Boiler Plant inspection. This inspection by the Boiler Efficiency Institute, Inc. (BEI) identified several safety concerns that need to be addressed to properly close out open findings. These items and their corrections ensure that the boilers are operating to standard and in compliance with VA Directive 1810, codes, regulations, etc.
PLACE OF PERFORMANCE The place of performance for this contract is VA Connecticut Healthcare System, located at Newington Campus, 555 Willard Avenue, Newington, CT 06111.
PERIOD OF PERFORMANCE The Contract Time Period of Performance is 45 days from the contract award and Notice to Proceed (NTP).
QUALIFICATIONS To be considered eligible for consideration, potential bidders shall have a field service representative located within 100 miles of the Newington Campus of the VA Connecticut Healthcare System. The Service Provider acting as a Prime with subcontracted labor shall meet this requirement.
The Bidders shall provide, upon request, documentation of certification/training on the specific equipment under the terms of this contract.
The Bidders shall be qualified to perform work on steam distribution systems to include industrial boiler plant equipment and have completed prior steam distribution work and/or inspection projects for VA Connecticut Healthcare System.
The Service Provider shall have a minimum of three (3) years of related scope and work experience with commercial and industrial steam boiler and steam boiler component installation and repairs as well as all aspects of inspections, cleaning, calibration, and testing in compliance with and clear understanding of relevant codes and regulations.
The Service Provider and/or assigned project staff members shall have industry standard certifications and qualifications to include but not limited to current OSHA certification (10 hours minimum/ 30 hours preferred) and equivalent qualifications associated with requirements herein.
The Service Provider shall submit documentation of technical training and certifications for personnel performing all work under the terms of this contract for review and acceptance prior to the start of work on site.
The Service Provider/ welders shall be certified and possess R-stamp certification.
The Service Provider will be responsible for complying with the VA Connecticut Healthcare System policies for confined space, Lock Out Tag Out, all equipment, supplies, and external support to safely enter the confined space to document and investigate existing conditions, determine quantities, and confirm scope of work.
The Service Provider shall submit documentation on technical training and certifications for personnel performing all work. The Contracting Officer (CO) and/or Contracting Officer s Representative (COR) specifically reserve the right to reject any of the Service Provider s personnel and refuse permission to work on the equipment outlined herein, based upon credentials provided.
SCOPE OF WORK The Service Provider shall furnish all labor, materials, equipment, tools, supervision, Safety considerations, LOTO procedures, clean up (daily and at the end of work with proper disposal of waste) and all incidentals to complete work for the services described in this document.
The Service Provider shall submit a project schedule, work procedures, inspection procedures, testing procedures, all safety documentation, weld procedures, welders certifications, etc. for review and approval by VA Contracting Officer Representative (COR) and Safety Office before the start of work on site.
If applicable, the Service Provider shall develop and submit an abatement plan including all personnel certifications and training records before the start of work on site.
Normal scheduled work shall occur between the hours of; 7:00 a.m. and 5:00 p.m. Monday Friday as coordinated with COR. All off-normal scheduled work shall be communicated and coordinated with CO and COR a minimum of ten (10) working days prior to need. No work shall be performed on Federal Holidays unless an emergency status has been indicated and/or authorized by the Contracting Officer.
US Federal Holidays:
New Year s Day Martin Luther King Jr. Day President s Day Memorial Day Juneteenth Independence Day Labor Day Columbus Day Veterans Day Thanksgiving Day Christmas Day
Description of Services: The project will include but not be limited to the following:
Boiler #1
Low Fuel Gas Pressure Cutoff Switch (LFGPCS): Replace switch and make isolation valves lockable only in open position. The Contractor shall replace switch and retest.
High Fuel Gas Pressure Cutoff Switch (HFGPCS): Replace switch and make isolation valve lockable only in open position. The Contractor shall replace switch and retest.
Combustion Air Proving Switch (CAPS): Switch setpoint is too low. The Contractor shall adjust switch to trip at 6.4 in wc or higher. The Contractor shall adjust the setpoint and retest. The Contractor shall adjust switch. Expected to be corrected within April 22 services. Verify in field task has been completed.
Purge Airflow Proving Switch (PAPS): Not plumbed properly. Switch must be plumbed from the wind box to the stack with proper test ports and isolation valves. Refer to testing manual 5th edition. Once properly plumbed switch must be properly set. The Contractor shall replumb switch and retest.
Low Fire Proving Switch (LFPS): Setpoint too high (x2 devices). The Contractor shall adjust position switch so that the switch is open at 10% firing rate or less for both devices and retest. The Contractor shall adjust the switch. Expected to be corrected within April 22 services. Verify in field task has been completed.
Replace the control panel mounted draft gauges for furnace pressure, draft, and flue gas outlet pressure.
Boiler #2
Low Fuel Gas Pressure Cutoff Switch (LFGPCS): Replace switch and make isolation valves lockable only in open position. The Contractor shall replace switch and retest.
Automatic Pilot Fuel Gas Shutoff Valve and Solenoid Vent Valve Seat Leakage (APFGSOV & APFGSVV): Both upstream and downstream APFGSOVs are leaking. The Contractor shall replace valves and retest.
Combustion Air Proving Switch (CAPS): Switch setpoint is too low. The Contractor shall adjust switch to trip at 6.4 in wc or higher. The Contractor shall adjust the setpoint and retest. The Contractor shall adjust switch. Expected to be corrected within April 22 services. Verify in field task has been completed.
Purge Airflow Proving Switch (PAPS): Not plumbed properly. Switch must be plumbed from the wind box to stack with proper test ports and isolation valves. Refer to testing manual 5th edition. Once properly plumbed switch must be properly set. The Contractor shall replumb switch and retest.
Furnace Pressure Interlock (FPI): The manual isolation valve for this switch needs to be locked in the open position. The Contractor shall make adjustment or replace interlock and retest.
High Fuel Gas Pressure Cutoff Switch (HFGPCS): Replace switch and make isolation valve lockable only in open position. The contractor shall replace the switch and retest.
Replace the control panel mounted draft gauges for furnace pressure, draft, and flue gas outlet pressure.
Boiler 3
Boiler is considered as being out-of-service and requires no corrections.
General Site Corrections:
Test and verify that existing water relays are operational (replace if required or provide as spares), remove the existing transmitter-actuated condensate tank high-water-level alarm, and provide a new replacement unit. Remove the existing probe-actuated high-level alarm and supply a new probe assembly. All installation, testing, and commissioning shall be included.
Provide and install Cross Boiler SCADA HMI with functions and plant trends per review with Plant Supervisor and COR.
Replace the control panel mounted draft gauges for furnace pressure, draft, and flue gas outlet pressure.
In addition, the contractor shall:
Check-in with the VACT Boiler Plant Supervisor at the start of each workday.
Provide a final comprehensive report on repairs and testing of deficient devices.
Performed and complete work per schedule that is approved in advance. Dates and times of work shall be coordinated between the Contractor and VA Contracting Officer to minimize impact on boiler plant operations. The Contract shall be completed within indicated days of the award. If any portion of the Contract cannot be completed within this period, the Contractor and VA Contracting Officer shall determine a reasonable period of performance for the specified portion within ten (10) Calander Days of award to modify for full compliance.
The Service Provider shall schedule and coordinate all work with VA COR, Utilities Supervisor, and Boiler Plant Supervisor.
All LOTO requests and procedures shall follow the VA Connecticut Healthcare System Medical Center Policy 138-075.
Coordinate Hot Work permit requests with VA Connecticut Healthcare System Safety Office.
Coordinate all placement and removal of Lock Out Tag Out devices for any energy sources with the VA COR/Maintenance & Operations.
All Confined Space entries shall follow the VA Connecticut Healthcare System Standard Operating Procedure Confined Space SOP-SO-010.
The VACHS confined space acknowledgement and permit is required to be completed by qualified individuals identified to perform entry into any confined space and will be coordinated with the VACHS Safety & Outage Coordinator and VACHS Safety Representative on site.
Protect all equipment in place during replacement activities.
Equipment considered necessary to accomplish all the work required by this contract includes but is not limited to equipment required for metal work, welding, inspection, testing, rigging & handling, de-watering, containment, and cleaning of any debris resulting from this work.
In accordance with VHA Operational Alert and Guidance, NO cast iron fittings and pipe components (valves, steam traps, etc.) shall be used. Reference VHA Directive 1810(1) as amended on September 11, 2018: 5.a(1) and 5.b(1).
ASTM A193 bolts shall be utilized and replace any ASTM A307 Bolts at locations of steam piping, flanges, gaskets, and other hardware where piping replacements are included within this scope of work. Reference Veterans Health Administration (VHA) Master Specifications for Hydronic Piping (Specification 23 22 13) and Steam and Condensate Heating Piping (Specification 23 22 13) where applicable.
Repair of existing cast iron fittings or pipe components is permissible in specific instances but must be reported and coordinated with the CO and COR for approval before starting the work through submittal process with justification as necessary.
All new steam and condensate lines shall be Schedule 80. All new steam and condensate lines that utilize valves to isolate or divert a medium shall be installed new as a double in series valve system (except for a drain line valve). Where the option exists to utilize welded vs threaded distribution, welded is the required option with connection to weld neck flanges and per use of metal jacketed gaskets. Alternate may be considered but not allowed unless authorized by the COR.
Repairs and any modifications shall be in full compliance with American Society of Mechanical Engineers (ASME) and National Board Inspection Code (NBIC).
The Service Provider shall perform an inspection report of all repairs, corrections, and testing with photographs and other documentation necessary to confirm information within the report.
All welding work shall be completed by certified welders (submit certifications for review and acceptance to the COR prior to any work) and must possess R-stamp certification. All weld tests shall meet standard per code specifications ASME Section V requirements for nondestructive examination and ASME Section VIIII rules for construction of pressure vessel.
Finish work shall include new insulation with R-factor and type to match existing, fiberglass with white paper wrap on lines, removable Velcro type fitting booths, color coded for medium, brass tags valves, medium labels on insulation and flow indicators as required.
SUBMITTALS/DELIVERABLES
The Service Provider shall furnish all submittal item documentations (with final dispositions) and final documentation report with all tests, photos, corrections made within fourteen (14) business days after work is completed. All submittals shall be provided to the VA O&M Section for Information Sharing Only and courtesy review. Proper equipment selection and timely procurement shall remain the responsibility of the Service Provider.
The Service Provider shall furnish all material certifications for any replacement parts used.
The Service Provider shall furnish a waste manifest as required.
SPECIAL INSTRUCTIONS Service Provider Check-in: All employees of the Service Provider shall comply with VA Security Management Program and obtain permission from the VA Police for access to restricted and unauthorized access areas. Upon arrival, the Service Provider shall sign-in at FMS Office and receive a temporary identification badge prior to performing services at VA Connecticut Healthcare System. The Service Provider shall wear visible identification always displaying the name and company ID while on site. All site visits shall be coordinated with the VA COR or assigned POC.
Per Directive 1805, smoking, vaping, and smokeless tobacco are prohibited on the grounds of VA facilities, including in vehicles. This Directive applies to all Service providers and their employees.
No photography of VA premises is allowed without the written permission of the contracting officer. Patients and staff are not to be photographed at any time.
Parking for Service Provider and employees shall be in designated areas only. The Service Provider shall coordinate with VA COR.
The Service Provider shall confine all operations (including storage of materials) on government premises to areas authorized or approved by the VA Contracting Officer. The Service provider shall confine all operations (including storage of materials) on government premises to areas authorized or approved by the VA Contracting Officer. The Service provider shall hold and save the government, its officers, and agents, free and harmless from liability of any nature occasioned by the Service provider s performance. Working space and space available for storing materials shall be as determined by the COR. Workers are subject to the rules of the Medical Center applicable to their conduct. Execute work in such a manner as to reduce impacts with work being done by others.
Billing: Provide COR with a report or statement of work completed and include statements with request for payment. The statement should include service completed and the date each service item was completed. Labor charges shall be billed hurly, and any unused labor totals will be credited back to the VA Medical Center on the next billing cycle, upon receipt of the service report.
Safety Codes / Certification / Licensing: Environmental abatement work, if necessary and required per SOW, is to be performed by Service Provider under supervision and monitoring for the VA by a Certified Industrial Hygienist. If suspected ACM is discovered, reach out immediately to the VA Contracting Officer and Contracting Officer Representative.
The Service Provider shall comply with all codes as described above, as well as codes customarily applied in VA construction jobs such as NFPA fire code, OSHA, VA Design Guides, etc. Labs used by the Service Provider shall be licensed as required by any applicable governing agencies, and their certifications and licenses shall be included in the reports.
Travel: Service Provider and/or subcontractors will travel from their place of business to the VA Connecticut Healthcare System and park, access and/or work in authorized areas only.
NARA Records Management Requirements The following standard items relate to records generated in executing this contract:
Citations to pertinent laws, codes and regulations such as 44 U.S.C. Chapter 21, 29, 31, and 33; Freedom of Information Act (5 U.S.C. 552); Privacy Act (5 U.S.C. 552a); 36 CFR Part 1222 and Part 1228.
The Contractor shall treat all deliverables under the contract as the property of the U.S. Government for which the Government Agency shall have unlimited rights to use, dispose of, or disclose such data contained therein as it determines to be in the public interest.
The Contractor shall not create or maintain any records that are not specifically tied to or authorized by the contract using Government IT equipment and/or Government records.
The Contractor shall not retain, use, sell, or disseminate copies of any deliverable that contains information covered by the Privacy Act of 1974 or that which is generally protected by the Freedom of Information Act.
The Contractor shall not create or maintain any records containing any Government Agency records that are not specifically tied to or authorized by the contract.
The Government Agency owns the rights to all data/records produced as part of this contract.
The Government Agency owns the rights to all electronic information (electronic data, electronic information systems, electronic databases, etc.) and all supporting documentation created as part of this contract. The Contractor must deliver sufficient technical documentation with all data deliverables to permit the agency to use the data.
The Contractor agrees to comply with Federal and Agency records management policies, including those policies associated with the safeguarding of records covered by the Privacy Act of 1974. These policies include the preservation of all records created or received regardless of format [paper, electronic, etc.] or mode of transmission [e-mail, fax, etc.] or state of completion [draft, final, etc.].
No disposition of documents will be allowed without the prior written consent of the Contracting Officer. The Agency and its contractors are responsible for preventing the alienation or unauthorized destruction of records, including all forms of mutilation. Willful and unlawful destruction, damage, or alienation of Federal records is subject to the fines and penalties imposed by 18 U.S.C. 2701. Records may not be removed from the legal custody of the Agency or destroyed without regard to the provisions of the agency records schedules.
The Contractor is required to obtain the Contracting Officer s approval prior to engaging in any contractual relationship (sub-contractor) in support of this contract requiring the disclosure of information, documentary material and/or records generated under or relating to this contract. The Contractor (and any sub-contractor) is required to abide by Government and Agency guidance for protecting sensitive and proprietary information.

More opportunities from Department Of Veterans Affairs → 241-NETWORK Contract Office 01 (36C241)

Same awarding agency

NAICS: 541330
New
Federal
C221--402-27-001 Repair Chiller 3 (AE)
Solicitation # 36C24127R0009
Network Contracting Office 1, supporting the VA New England Healthcare System, is conducting market research to identify potential sources for Architect and Engineering (AE) services at the VA Maine Health Care System in Togus. The project focuses on evaluating existing conditions and designing corrective measures to repair Chiller 3, specifically addressing low voltage faults and refrigerant and oil leaks. The scope is limited to Type A services, concluding with a 35 percent design submission, and includes investigative services such as site visits, field studies, and user interviews. The period of performance for this work is 90 calendar days. This notice is a sources-sought tool used to determine the appropriate socio-economic set-aside for the eventual procurement under NAICS 541330, which has an SBA size standard of 22.5 million dollars in average revenue. Interested firms must submit a letter of interest by November 20, 2026, to Diane C. Davis, including their UEI number, socio-economic status, a narrative of similar experience, and proposed team composition. The government requires that if a set-aside is implemented, at least 50 percent of the work must be performed by the prime contractor or similarly situated subcontractors. All design work must adhere to the VA Technical Information Library standards, and sensitive infrastructure data must be marked as For Official Use Only.
Engineering Services

POSTED

1 day ago

DEADLINE

in 29 days
View Details
NAICS: 811310
New
Federal
H146--Hach Water Quality Monitoring Service
Solicitation # 36C24127Q0031
The Department of Veterans Affairs Networking Contracting Office intends to enter into a sole source procurement with Hach Company under FAR 6.302-1 for water quality monitoring services at the VA Medical Center in White River Junction, Vermont. This requirement is designated under NAICS code 811310. The scope of work involves the inspection, maintenance, repair, and annual calibration of ten Hach water quality monitoring instruments located across several facility buildings, as well as the annual calibration of one colorimeter. The contract includes two scheduled visits per 12-month period, 24/7 emergency service, and monthly reagent refills. These services are critical for ensuring the supply of safe drinking water and generating the daily data reports required by the State of Vermont Drinking Water Protection Division. The procurement is awarded to Hach Company because the equipment and services are proprietary, and the manufacturer does not authorize other organizations to perform repairs or recalibrations. Because the work is performed within a functioning hospital, the contractor must adhere to strict infection control practices and submit an Infection Control Plan, Activity Hazard Analysis, and Material Safety Data Sheets for approval. All work must comply with NFPA, OSHA, EPA, and specific VA specifications and handbooks. The government retains all rights to data and electronic records produced under the contract, and the contractor must comply with the Privacy Act of 1974 and the Freedom of Information Act. Interested parties must submit their capabilities to Kenya Mitchell by the specified deadline to determine if competitive procedures are feasible.
Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance

POSTED

2 days ago

DEADLINE

in about 22 hours
View Details
NAICS: 561730
New
Federal
S208--West Haven Grounds and Maintenance
Solicitation # 36C24127Q0004
The Department of Veterans Affairs, Network Contracting Office 1, is soliciting proposals for a firm-fixed-price contract to provide comprehensive grounds maintenance, snow and ice removal, and storm drain cleaning services at the West Haven VA Medical Center in Connecticut. This total small business set-aside under NAICS 561730 includes a base year and four option years, with a total duration not to exceed five years. The scope of work requires 24/7 availability for snow and ice events, with a mandatory response time of one hour and the requirement for a field service representative located within 200 miles of the campus. Key services include mowing 30 acres of improved grounds, fall leaf removal, bi-annual storm drain cleaning for both West Haven and Newington campuses, and specialized snow removal for parking garages. Fertilization, pest control, and soil aeration are expressly excluded from the contract. Award will be granted to the Lowest Priced Technically Acceptable (LPTA) offeror. Technical acceptability is based on the capability to perform all services, equipment inventory, and personnel qualifications, while past performance is evaluated on a go/no-go basis requiring at least three references from the last five years. Proposals must be submitted in two volumes, consisting of a technical capability statement and a completed CLIN pricing schedule, by October 29, 2026, at 10:00 AM Eastern Time. Performance is monitored via specific acceptable quality levels based on customer complaints, and the contractor must adhere to Service Contract Labor Standards for the West Haven and Newington areas.
Landscaping Services

POSTED

2 days ago

DEADLINE

in 7 days
View Details

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS