J041--RFQ Amendment (Questions) 13 MAR 26 Repair Services - Chiller Plant Skid 1 & 2 Pump
Contract Overview
Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.
Active Opportunities Like This One
AI Contract Overview
Solicitation Number 36C25626Q0449 is a Request for Quotation issued by the Department of Veterans Affairs Network Contracting Office 16 for repair services at the Alexandria VA Medical Center in Pineville, Louisiana. This total SDVOSB set-aside project requires the replacement of two Taco pumps, two 125 HP premium efficiency electric motors, and two Taco triple duty valves for Chiller Plant Skids 1 and 2. The scope of work encompasses the complete removal of old equipment, installation, welding, laser alignment, electrical reconnection, and the replacement of two-inch thick wrapped fiberglass insulation. The contractor is responsible for ensuring the new components meet DOE and ASHRAE 90.1 standards, performing hydrostatic testing, and providing a final commissioning report to VA Engineering. The contract will be awarded based on the Lowest Price Technically Acceptable (LPTA) method, evaluating offerors on technical acceptability and past performance. The period of performance is 120 calendar days from the Notice to Proceed. Amendment 00001 clarified that while VFDs are required, they are not being replaced, and no BAS connections are needed. Piping sizes for the triple duty valves are specified as 12 inches for Chiller 1 and 10 inches for Chiller 2. Proposals must be submitted in two volumes, technical and pricing, via email to the contract specialist. All payments will be processed electronically through the VA Electronic Invoice Presentment and Payment System.
General Info
Contract Value
$169,000Place of Performance
Alexandria, VA Medical Center 2495 Shreveport Hwy, Pineville,, MS, 71360, USASet-Aside
Awardee
STERILECO LLCAward Issued Date
Timeline
Submission Closed
Organization & Contact Information
Full Description
1. Photos of the pumps/motors showing piping arrangement, electrical connection, and nameplate data. Are VFDs required? Is there any BAS connections or interlocks for the pumping system? ANS: The pics are attached to the email for this project. VFD's are required but not being replaced. No BAS connections needed. 2. Electrical for the Motors: HP, Voltage, Amperage and disconnecting means and locations. ANS: The information are located in the pics attached to the email. Electrical is all on name plate of pumps in pics 3. Pump capacity information: Flow Rate in GPM, & Pumping Head. ANS: The information are located in the pics attached to the email. Flow rate and GPM are on name plates in pics 4. What type of insulation is installed and thickness? ANS: The insulation is wrapped fiberglass insulation 2" thick 5. Is pump an End Suction, Double Suction, or In Line type Pump. ANS: See pics of pumps for the alignment for inlet and outlet 6. What is the pipe size for the Taco Triple Duty Valves to be installed. ANS: The piping is 12" for chiller 1 and 10" for chiller 2 Clarify the questions come from the scope: "The Contractor shall provide all tools, shipping, delivery, personnel, transportation, demolition, removal of old equipment, installation of new equipment, modifications to existing piping, to deliver and install the necessary equipment for repairing Chillers 1, and 2 ANS: The contractor must install both pump/motor for each chiller 1&2 and triple duty valve for both chillers. 2. The scope is to provide regular system health checks, preventative/routine maintenance, repairs, onsite training, and access to a technical support team in support of two industrial chillers and their subcomponents which consist of, but not limited to: magnetic drive pumps, piping, electrical connections, regulator valves, pneumatic actuators, gauges and indicators, heat exchangers, AC drives, and input modules. " ANS: The contractor after installation must verify the installation correct with functional for the 2 chillers pump/motors and triple duty valve.
More opportunities from Department Of Veterans Affairs → 256-NETWORK Contract Office 16 (36C256)
Same awarding agency
Earlier notices in this NAICS code
Posted before this notice, open and closed
Find Active Opportunities Like This
Get AI-powered intelligence on the opportunities still open
Every page of the solicitation package shredded into a compliance breakdown
AI-powered matching based on your capabilities and past performance
Competitor and incumbent history on the requirement
Automated alerts on amendments, Q&A deadlines, and award
Join 750+ contractors already using CLEATUS