The Department of Veterans Affairs has issued a presolicitation notice seeking a contractor to refurbish two hydraulic elevators, P-5 and P-6, located in the D Wing of the Fayetteville VA Medical Center in North Carolina. The project involves comprehensive modernization and refurbishment of these elevators, which serve critical hospital areas including the Emergency Room, Imaging, Laboratory, ICU, and Operating Rooms. The work encompasses demolition of existing systems, installation of non-proprietary modernization components, code upgrades for machine rooms and pits, cab and door refurbishments, as well as adherence to infection control requirements through phased barriers. The contractor is responsible for all labor, materials, equipment, tools, and transportation required to complete the project, ensuring reliable elevator operation while maintaining ongoing hospital activities and life safety. Completion is expected within 450 calendar days of the Notice to Proceed, with an estimated project cost ranging between $1 million and $5 million. This opportunity is set aside exclusively for Service-Disabled Veteran Owned Small Businesses (SDVOSB), requiring certification and registration with the Small Business Administration’s database prior to bid submission. The Department of Veterans Affairs plans to release an Invitation for Bid around February 5, 2026, and will award a firm fixed-price contract based on the bids received. Interested firms must be registered in the SAM system to access solicitation documents and submit proposals. A single site visit will be scheduled, with details to be provided in the solicitation. Communication regarding this project must be directed via email to the designated Contracting Officer, and no telephone requests for bid materials will be accepted. This notice serves informational purposes only and does not constitute a solicitation or invitation to bid.
General Info
Contract Value
$1,208,888Place of Performance
VA, USASet-Aside
Awardee
M2 FEDERAL INC.Award Issued Date
Timeline
Organization & Contact Information
Full Description
Scope of Work
Refurbish D wing Elevators
Fayetteville VA Medical Center Fayetteville, NC
Project No. 565-24-105
CONSTRUCTION SCOPE OF WORK
Contractor shall provide all labor, supervision, materials, equipment, tools, transportation, and incidentals necessary for modernization, refurbishment, installation, commissioning, and turnover of two existing D-Wing elevators P-5 and P-6 (hydraulic; 4,000 lb; 125 fpm; B/1/2 stops; duplex selective collective) serving the Emergency Room, Imaging, Laboratory, ICU, and Operating Rooms while maintaining hospital operations and life-safety. Work includes demolition of legacy systems, installation of non-proprietary modernization components, machine-room and pit code upgrades, cab and hoistway door refurbishments, ICRA-conforming phasing and barriers, commissioning, training, and full closeout. The finished elevators shall operate reliably and be executed in accordance with the final issued-for-construction documents, specifications, and applicable current VA, federal, state, and local codes and standards. This project does require a site safety and health officer (SSHO) separate from the site superintendent.
Contractor shall furnish, install, test, and commission work in full compliance with: ASME A17.1 (2022) Safety Code for Elevators and Escalators; acceptance test by QEI. NFPA 70 (NEC 2023), IBC 2021, IMC 2024, IPC 2024 and applicable NFPA provisions. OSHA (including asbestos and confined space standards, 29 CFR 1910/1926 as applicable). VA directives, design manuals, and Master Specifications (PG-18-1); comply with VA safety signage, ICRA guidance, and VA Elevator design guidance.
Base bid shall include all items listed on the drawings and in the specifications. Submit a detailed baseline schedule for VA approval, reflecting all phases of work, milestones, inspections, and commissioning activities.
Infection Control Risk Assessment (ICRA) & work restrictions: Mechanical room: ICRA Class III. Elevator lobbies (active work): ICRA Class III; predominantly night work; plastic barriers removed each morning and reinstated nightly. Elevator shafts: ICRA Class II with one car kept active during the other car s work scope. Provide negative air, HEPA filtration, dust-tight barriers, sticky mats, and debris management per approved ICRA plan. Schedule noisy/vibration work off-hours. Maintain egress, fire-life safety, and hospital security at all times.
Phasing & sequencing (contractor to detail means/methods):
Phase 1 (60 days): Engineer/vendor submittals for long-lead equipment. Phase 2 (120 days): Material acquisition; establish ICRA barriers. Phase 3 (14 days): Demolish old equipment; begin pit work/sump base. Phase 4 (21 days): Paint half the mechanical room floor at P-5; 7-day cure; route/rough-in sump discharge to mech room; defer mech room wall paint to Phase 10. Phase 5 (60 days): Install P-5 modernization equipment (incl. lobby call stations). Phase 6 (30 days): Paint P-5 pit walls/floor; test and turnover P-5. Phase 7 (7 days): Re-set ICRA barriers; prep P-6 for work (COR inspection/approval).
Phase 8 (28 days): Demolish P-6 equipment; pit work and floor paint with 7-day cure. Phase 9 (45 days): Install P-6 modernization equipment. Phase 10 (30 days): Paint mechanical room walls and pits; test and turnover P-6; complete BMS/EMCS connections and testing. Phase 11 (30 days): Project closeout, O&M/Training; commissioning completed.
Total of 445 days.
Protect adjacent finishes; cap/terminate abandoned utilities; manage, containerize, and dispose of waste per VA environmental procedures (recycle where practicable).
If ACM is confirmed, perform abatement under the approved plan before disturbance.
Controls & operation:
Replace relay logic with a microprocessor controller (BoD Smartrise or equivalent), providing: simplex/duplex operation as required, emergency power capability, onboard diagnostics, landing control system, FF Service Phases 1 & 2, independent service, hoistway access, car-top operation, timed lighting/fan control, and emergency-power pre-transfer signal integration (two-wire from building switchgear).
Hydraulic package:
Replace/upgrade hydraulic machines and associated components (BoD EECO or equivalent): dry tanks, (Maxton/EECO or equivalent) control valves, motors, pumps, pit shut-off valves, and new Victaulic gaskets, complete with new wiring.
Door equipment:
Replace hall door equipment, car door operators, and car door equipment (BoD GAL or equivalent). Provide new hoistway doors with stainless steel skins; polish/renew existing stainless hall frames.
Fixtures & signaling:
Replace hall pushbuttons, main COP, auxiliary COP, combination hall direction/car position indicators, and emergency power jewel; integrate jewel pre-transfer signal (two-wire from switchgear to controller). (BoD Innovation for fixtures.)
Cab interiors:
New cab interiors, new flooring, new covers for the existing stainless side lighting (retain system, replace covers), new car doors; polish interior stainless steel. Elevators P-5/P-6 to match the new car scheme already deployed in D-Wing.
Machine Room:
Dedicated 110V car-light disconnect; car lights on a dedicated circuit (panel AB-2 has spares).
Illumination: provide 200 lux measured at floor.
GFCI outlet on a dedicated source.
Environmental: Provide exhaust/heat to maintain 45 90°F, 95% RH.
Sprinklers/detectors: If sprinklers present, install heat detector within 2' of each head and a smoke detector within 2' of each heat detector per NFPA 72 coordination.
Pits:
Lighting: provide 100 lux.
GFCI outlet on a dedicated circuit.
Sump pump: Install new sump pump at 3,000 gph capacity with single dedicated receptacle and discharge tank/piping per drawings. Paint pit walls to finished floor level with epoxy.
Elevator recall & FA interfaces:
Provide addressable devices and relay logic for primary/secondary recall and flashing hat function; integrate with the building s addressable system in accordance with current code.
Architectural & lobby scope:
Clean, prep, and finish existing stainless elevator jambs to receive new coating.
Vestibules (B, 1, 2): remove corner guards/bumper rails/base; prep and install new corner guards, bumper rails, base, and paint to Level 4 finish; match D-Wing standards.
Machine room walls: epoxy paint per phasing (Phase 10).
Mechanical scope:
Demo existing terminal unit/duct as indicated; install new constant-volume terminal unit and ductwork; coordinate clearances, access, and EMCS points.
Plumbing/sanitary scope:
Cap existing sump pit and add the new sump and discharge tank/piping per drawings; coordinate penetrations and firestopping.
Electrical/communications scope:
Provide all new elevator power/control wiring in conduit; no exposed cabling.
Coordinate normal/emergency power feeds, car-light circuit, GFCIs, FA interfaces, EMCS tie-ins, and signaling. Provide panel schedules and as-built risers.
Testing, commissioning, training:
Pre-functional checklists and functional testing for each elevator; integrate controls, FA/recall, emergency power, door protection, and ride quality.
Conduct A17.1-2022 Acceptance Test witnessed by licensed QEI; Contractor to schedule, provide load, and correct deficiencies.
Coordinate with VA-hired CxA for plan review, point-to-point verification, performance testing, and issue resolution through turnover.
Provide staff training (operator and maintenance) and furnish all manuals/tools.
Deliverables & closeout:
As-builts: Revit/CAD + PDF; record risers and device addresses.
O&M manuals: indexed, bound hard copies + editable digital (Word/Excel) and PDFs.
Warranties: per spec; include controller, drives, hydraulics, doors/operators, fixtures.
Spare parts/special tools: per manufacturer requirements.
Punch list: Correct all items within 15 working days of issuance; provide re-inspection; achieve COR acceptance.
Similar Contracts
Same NAICS industry code
More opportunities from Department Of Veterans Affairs → 246-NETWORK Contracting Office 6 (36C246)
Same awarding agency
Earlier notices in this NAICS code
Posted before this notice, open and closed
Ready to Pursue This Opportunity?
Get AI-powered intelligence on this solicitation and the ones like it
Every page of the solicitation package shredded into a compliance breakdown
AI-powered matching based on your capabilities and past performance
Competitor and incumbent history on the requirement
Automated alerts on amendments, Q&A deadlines, and award
Join 750+ contractors already using CLEATUS