NOTICE OF INTENT TO SOLE SOURCE-KY7A LOAD TAP CHANGER RETROFIT SERVCIES

Closed
26WA159390Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 811310
New
SLED
The State of New Hampshire, Department of Natural and Cultural Resources, Division of Parks and Recreation (the "State" and "Division"), is seeking written proposals from qualified vendors to provide industrial motor and electrical control mainten...
Solicitation # 656bdc64-f1c6-40c6-85f2-429f59c01a75
The State of New Hampshire, Department of Natural and Cultural Resources, Division of Parks and Recreation, is seeking a qualified vendor to provide comprehensive industrial motor and electrical control maintenance for the snowmaking system at Cannon Mountain Ski Area. The scope of work includes preventive maintenance, inspection, diagnostic testing, repair, overhaul, and emergency response for industrial electric motors ranging from 50 HP to 1,250 HP from manufacturers such as GE, US Motors, Siemens, TECO, and Marathon. The selected vendor must provide all necessary labor, supervision, tools, and materials, ensuring all work adheres to manufacturer recommendations, industry standards, and applicable safety regulations. The contract is envisioned as a three-year agreement starting November 15, 2026, with the state holding an option for two additional one-year extensions, pending approval from the NH Governor and Executive Council. Award decisions will be based on the best overall value, with evaluation weighted toward pricing (50%), experience and qualifications (25%), technical approach (15%), and references (10%). Vendors must provide proof of Commercial General Liability and Workers' Compensation insurance and submit a detailed proposal including a pricing sheet for labor rates, shop services, and parts markups. The final agreement will be based on the State of New Hampshire Form P-37.
Department Of Natural & Cultural Resources

POSTED

about 22 hours ago

DEADLINE

in 4 days

AI Contract Overview

Show more

The Department of Energy’s Western Area Power Administration plans to award a sole source contract to Reinhausen Manufacturing, Inc. for the retrofit of a KY7A load tap changer at the Headgate Rock Substation in Parker, Arizona. Reinhausen is the only vendor capable of providing the specialized vacuum-operated load tap changer replacement parts and technical expertise required for this critical transformer component, ensuring continued operational reliability and reducing long-term maintenance costs. The scope of work involves comprehensive on-site services including mobilization, pre-testing of electrical and oil parameters, removal of the existing load tap changer, installation of a new RMV-II unit with welded transition throat, relocation of the control cabinet, re-gasketing, pressure testing, vacuum drying, and final oil filling under strict technical specifications. All activities must comply with precise safety, environmental, and performance standards, including dew point limits not to exceed 1% and a 48-hour vacuum hold at 1 Torr or less. The project requires full documentation including as-built drawings, test reports, and revised schematics upon completion, along with thorough cleanup and demobilization. The contract is governed under FAR Part 12 simplified procedures for commercial items, with a NAICS code of 811310 and a $12.5 million small business size standard. The solicitation number is 26WA159390, with a response deadline of June 6, 2026. Only capability statements submitted via email to Georgette Reyes-Wiltz will be considered, and any costs incurred by respondents in preparing submissions are borne solely by them. No competitive bidding will be conducted, and the government retains full discretion in determining the award based on the vendor’s demonstrated ability to meet the technical and operational requirements outlined in the notice.

General Info

WAPA to sole source retrofit KY7A load tap changer at Headgate Rock Substation.

Agency

Department Of Energy → Western-Desert Southwest RegionView Agency

NAICS

811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and MaintenanceView NAICS

Place of Performance

Parker, AZ, 85344, USA

Set-Aside

NONE

Documents

(0)

No documents available

AI Contract Breakdown

Uniform Contract Format

No contract breakdown available.

Cannot generate Contract Breakdown because no documents were found from this contract's source.

Timeline

PhaseClosed
Posted

special-notice

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Start your free trial to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Energy → Western-Desert Southwest Region
Contacts1 person available
OfficePHOENIX, AZ, 85009, USA
Organization / Agency
Department Of Energy → Western-Desert Southwest Region
View Agency Profile
Office AddressPHOENIX, AZ, 85009, USA
Contacts
Reyes-Wiltz Georgette Flores

Full Description

Show more

Notice of Intent to Sole Source: Headgate Rock KY7A Load Tap Changer Retrofit Services – Reinhausen Manufacturing, Inc.


The Department of Energy (DOE) / Western Area Power Administration (WAPA) intends to issue a sole source award, under the authority of RFO FAR 12.201-1 Simplified Procedures for Certain Commercial Items Certain Commercial Items (IAW 41 U.S.C.1901 Simplified Acquisition Procedures), to Reinhausen Manufacturing, Inc. of Humboldt, TN.


This is a sole source acquisition to Reinhausen Manufacturing Inc. as they are the only vendor that can provide the required parts and service needed to repair a KY7A load tap changer (LTC)- serial number C-05324-5-1 located at WAPA Desert Southwest Region’s Headgate Rock Substation located in Parker, AZ. Reinhausen Manufacturing is uniquely qualified to provide the technologically advanced vacuum operated load tap changer (VLTC) bolt on replacement, increasing availability for future original equipment manufacturer (OEM) parts and services to WAPA while reducing maintenance costs and service intervals.


Scope of Services shall include:


  1. Mobilize crew and equipment to Headgate Rock Substation.
  2. Perform pre-job brief to identify hazards and proper isolation, switching and grounding
  3. Stage Equipment.
    1. Arrester stand-offs above the “load tap changer (LTC)” may need to be temporarily removed for the retrofit.
  4. Perform pre-testing in as found tap position for baseline
    1. Doble power factor overall, bushings, C1 and C2
    2. TTR in all OLTC taps
    3. Winding Resistance in all OLTC taps
    4. Insulation Resistance (Megger)
    5. Main and Core
    6. Oil Analysis (Dielectric (D1816), Acid (D974), IFT (D971 or D2285), Color (D1500), Visual (D1524), Water (D1533), PF (D924), and Dissolved Gas Analysis)
  5. Perform Inspection of Unit
  6. Identify Leaks
  7. Drain main tank oil into the contractor’s supplied oil storage
  8. Drain LTC oil into customer supplied drums or totes
    1. Customer to dispose of waste oil and drums/totes
  9. Perform an initial dew point (12hr, minimum measurement. Review results with WAPA’s technical representative.
  10. Perform an internal inspection of the transformer and LTC leads to determine “as is” condition and to identify any potential problems or issues.
  11. Retrofit new LTC to transformer:
    1. Identify, label, and disconnect all leads at LTC board
    2. Remove existing LTC from main tank
      1. WAPA to dispose of LTC mechanism, compartment, etc.
    3. Install New RMV-II with transition throat to main tank via welding
    4. Make lead extension connections from windings to LTC board as necessary.  Install any supports, clamps, spacers as necessary to maintain clearance.
    5. Wrap Connections and verify clearances for required voltage level modification of existing leads, terminals, or flange.
  12. Re-gasket all manholes accessed during project.
  13. Relocation of control cabinet:
    1. Determinate and remove items in the existing control cabinet
    2. Label wiring for reconnection
    3. Transfer components to new cabinet and terminate wiring
      1. Customer to dispose of original cabinet
  14. Clean up welds and repaint as needed
  15. Seal unit and pressure test for leaks.  All accessed manholes will be re-gasketed.
  16. Perform dew point test to determine dryness of insulation
    1. Max acceptable limit is 1%
    2. If dewpoint exceed 1%, field dry out will be required
      1. Associated cost of field dry-out will be at the expense of WAPA based on initial baseline dewpoint reading and final
  17. Perform final vacuum and oil filling:
    1. Vacuum 48 hours at 1 Torr or less
    2. Perform Vacuum leak test
    3. Fill unit with de-gas oil at 60deg C +/-5”, without exceeding 5Torr
    4. Break Vacuum with dry air
  18. Bleed all areas required
  19. Perform final testing:
    1. Doble power factor overall, bushings, C1 and C2
    2. TTR in all OLTC taps
    3. Winding Resistance in all OLTC taps
    4. Insulation Resistance (Megger)
    5. Main and Core
    6. Oil Analysis (Dielectric (D1816), Acid (D974), IFT (D971 or D2285), Color (D1500), Visual (D1524), Water (D1533), PF (D924), and Dissolved Gas Analysis)
    7. Operational check of LTC controls
  20. Review results with WAPA
  21. Provide report, test results, as-built drawings and revised existing drawings
  22. Clean area and prepare for demobilization of crew and equipment

The resulting procurement will be conducted in accordance with RFO FAR Part 12. The North American Industry Classification System (NAICS) code for this acquisition is 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance with a small business size standard of $12.5 million.


This synopsis of the proposed contract action/notice of intent is for information and market research purposes only. THIS IS NOT A REQUEST FOR COMPETITIVE QUOTES. No solicitation package will be publicly issued. Responsible sources may submit a capability statement in response to this requirement, which shall be considered by the Agency. Capability statements must be received no later than the due date and time specified on this notice. Responses must be supported with clear and convincing evidence that clearly articulate the company's ability to satisfy the Government's requirements. A determination by the Government not to compete based upon responses to this notice is solely within the discretion of the Government. Inquiries will only be accepted via e-mail to Georgette Reyes-Wiltz at reyeswiltz@wapa.gov. No telephone requests will be honored.


If parties choose to respond, any cost associated with preparation and submission of data or any other cost incurred in response to this announcement are the sole responsibility of the respondent and will not be reimbursed by the Government.


Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 650+ contractors already using CLEATUS