J061--Automatic Transfer Switch (ATS) Testing and Imaging

Closed
36C24126Q0046Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

NAICS: 811310
New
Kubota M8200 Clutch Replacement
Solicitation # kubota-m8200-clutch-replacement
Management & Training Corporation is soliciting bids for the clutch replacement of a Kubota M8200 tractor with front wheel assist, no cab or loader, located at the Earle C. Clements Job Corps Center in Morganfield, Kentucky. The contractor is responsible for providing all transportation, labor, supervision, tools, and new manufacturer-specified parts to diagnose and repair the clutch assembly and power take-off system. Key technical requirements include replacing friction discs, bearings, oil seals, and O-rings, as well as resurfacing the flywheel and replacing hydraulic pipes and filters as necessary. Final acceptance is contingent upon the Facility Maintenance Department verifying proper clutch engagement and PTO operation under load. This is a fee-for-service contract awarded on a best-value basis, with a response deadline of November 3, 2026. The solicitation is set aside for small businesses, including VOSB, SDVOSB, WOSB, and HUBZone certifications. Applicants must submit a bid sheet, proof of insurance, a completed supplier packet including Form W-9, and a self-certification form. The contract is subject to various Federal Acquisition Regulations, including Service Contract Labor Standards under Wage Determination 2015-4687 Revision 31 for Kentucky, and strict requirements regarding the security of non-public information and the prevention of trafficking in persons.
Earle C. Clements Job Corps Center

POSTED

about 3 hours ago

DEADLINE

in 7 days
NAICS: 811310
New
SLED
ANNUAL ROTATING EQUIPMENT INSPECTION, TESTING, REPAIR, RECONDITIONING AND STORAGE SERVICES
Solicitation # 2026-RFP-130
Lakeland Electric is soliciting proposals under RFP 2026-RFP-130 to establish a pool of qualified contractors for the annual inspection, testing, repair, reconditioning, and storage of critical rotating equipment at the McIntosh and Larsen Power Plants. The scope of work covers a wide range of assets, including low- and medium-voltage AC/DC electric motors and circulating water and condensate pumps. Required services include clean inspection tests, troubleshooting, motor rewinding, dynamic field balancing, laser alignment, and vibration analysis. Additionally, the selected contractors must provide logistics support, including pickup, delivery, and secure indoor storage with ongoing preservation activities such as shaft rotation and lubrication. Proposals are due by 3:00 pm on October 30, 2026, via the OpenGov portal. Award decisions will be based on a 100-point scoring system evaluating pricing (30%), qualifications and experience (25%), technical and facility capabilities (25%), service approach and response (15%), and past performance (5%). Mandatory submittals include a signed W-9, Florida Sunbiz registration, a notarized Hold Harmless Indemnification Agreement, and a Human Trafficking Affidavit. Contractors must adhere to strict safety standards, including OSHA regulations for crane operations and powered industrial trucks, and must certify compliance with drug-free workplace and suspension and debarment regulations.
LE - Production - MPP

POSTED

about 10 hours ago

DEADLINE

in 3 days
NAICS: 811310
New
Federal
Combined Synopsis/Solicitation Notice: Maintenance of Commissary Refrigeration Systems and Repair of Refrigeration, Heating, Ventilation, and Air Conditioning Systems (HVAC) at Hario and Sasebo, Japan
Solicitation # W912HV26QA013
Solicitation W912HV26QA013 is a combined synopsis and request for quote for a firm-fixed-price contract to provide maintenance and repair services for commissary refrigeration systems, including Refrigeration Monitoring and Control Systems (RMCS), and heating, ventilation, and air conditioning (HVAC) systems. The work will be performed at the Hario Commissary (Building 5127), Sasebo Commissary (Building 1436), and Sasebo Storage Facility (Building 306) in Japan. The contract includes a base period from December 1, 2026, through November 30, 2027, with the option for four additional extension years. The contractor is required to provide monthly preventive maintenance and maintain 24/7 emergency service availability, with a two-hour response time and a 24-hour repair completion window. Replacement parts under 500,000 JPY are included in the base price, while those exceeding this amount are handled via reimbursable CLINs with a not-to-exceed limit of 3,000,000 JPY per period. Award will be based on the most advantageous quotation, evaluated in order of past performance (Acceptable/Unacceptable), technical capability (Good/Acceptable/Unacceptable), and price fairness and reasonableness. Quotations must be submitted electronically via the PIEE Solicitation Module by October 28, 2026. Required submissions include a technical narrative addressing emergency response and supply chain capabilities, financial documentation such as Standard Form 1407 and corporate tax returns, and at least three past performance questionnaires or CPARS evaluations. This acquisition is not set aside for small business concerns and requires compliance with OSHA and USACE safety standards.
W2SN Endist Japan

POSTED

about 14 hours ago

DEADLINE

in about 16 hours
NAICS: 811310
New
Federal
Equipment Operations, Maintenance, and Repair Services at Joint Base Pearl harbor Hickam, Hawaii (JBPHH).
Solicitation # N6247827R2535
Solicitation N6247827R2535 is a Request for Proposal issued by NAVFAC Systems Command Hawaii for equipment operations, maintenance, and repair services at Joint Base Pearl Harbor Hickam, Hawaii. This Indefinite Delivery Indefinite Quantity (IDIQ) contract is a total small business set-aside, specifically open to HUBZone and Economically Disadvantaged Women-Owned Small Business entities under NAICS code 811310. The scope of work involves the calibration, maintenance, and repair of various systems, including boilers, unfired pressure vessels, wastewater instrumentation, autoclaves, and auxiliary generators. The contract is structured with a base period and four option periods, running from March 1, 2027, to September 1, 2032, and consists of both recurring preventive maintenance and non-recurring unit priced labor. The government will utilize the Lowest Price Technically Acceptable (LPTA) process for award, evaluating proposals based on total price and non-price factors including corporate experience, qualifications, safety, and past performance. To be eligible, offerors must achieve an acceptable rating in all non-price factors. Key requirements include the provision of a Project Manager with at least three years of relevant experience, a Site Safety and Health Officer, and an Environmental/Energy Manager. All technical work must be performed by personnel trained and certified by the Original Equipment Manufacturer. Proposals must be submitted via the Procurement Integrated Enterprise Environment (PIEE) by December 8, 2026, and must include a comprehensive Quality Management Plan and specific safety data, including DART and TCR rates from 2020 to 2024.
Navfacsyscom Hawaii

POSTED

about 14 hours ago

DEADLINE

in about 1 month

General Info

NAICS

811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance

Place of Performance

ME

Set-Aside

NONE

Documents

1

Solicitation 36C24126Q0046 - Automatic Transfer Switch Testing and Imaging

DOCX, High priority: read this first5 pages · rfq
High

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

PhaseClosed
Posted

special-notice

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Start your free trial to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → 241-NETWORK Contract Office 01 (36C241)
Contacts1 person available
OfficeTOGUS, ME, 04330, USA
Office AddressTOGUS, ME, 04330, USA
Contacts
Rosangela PereiraContract Specialist

Full Description

Show more
The Department of Veterans Affairs, Networking Contracting Office (NCO 01) located in VAMC Boston, West Roxbury intends to enter into a sole source procurement, pursuant to the authority of FAR 6.302-1, with Russelectric, a Siemens Business for the following requirement:
Statement of Work
1.0 Scope of Work The contractor will perform annual Automatic Transfer Switch (ATS) testing and imaging at the Boston Healthcare System, West Roxbury Division.
Contractor is responsible for all labor, materials, tools and special equipment required to perform the work.
All Transfer Switch Testing shall occur during off hours (10:00 PM 7:00 AM).
Period of Performance The anticipated period of performance will be a one-base year with four (one) year options.
2.0 Performance Requirements INFRARED THERMAL IMAGING
Thermal infrared imaging of both the normal and emergency power poles shall be done during annual testing. The transfer/bypass switch shall be in the emergency position for 30 minutes, prior to the imaging pictures taken to allow for any temperature rise. Reports of anomalies shall include a color photograph of the switch being tested & a color thermal imaging print. The report information shall be similar to test report a attached and made part of this standard. Both the transfer switch & bypass contacts shall be scanned.
The following standards, as applicable, shall be part of the testing requirements:
NFPA-70 (national electric code) NFPA-70B (electrical equipment maintenance) nfpa-70e (electrical safety in the workplace) nfpa-99 (health care facilities) NFPA-101 (life safety code) NFPA-110 (emergency and standby power systems) nfpa-20 (stationary pumps for fire protection) ansi/neta-mts (maintenance testing specifications) ma elevator regulations (524 cmr) TESTING REQUIREMENTS In-phase monitors (sync check relays)
In-phase monitors shall be checked for calibration and shall be set for + or 7 degrees maximum. Relay output contacts shall be tested, Dead bus relay outputs shall be confirmed and maximum slip rate shall be noted on the test reports.
VOLTAGE & FREQUENCY SENSORS All voltage and frequency sensors for both normal and emergency shall be calibrated with a three-phase test set, using calibrated meters for all pickup & dropout values. All results, including as found and as left settings shall be noted on the test reports.
AUXILIARY CONTACTS & SPECIAL TIMED CONTACTS All auxiliary position contacts shall be tested in both positions and so noted in the test reports. All auxiliary contact functions such as Normal Power Available , Emergency Power Available , ETC. Shall be verified and noted in the test reports.
TIMER CALIBRATION AND OPERATION CHECKS The following timers shall be checked for accuracy and so noted in the test reports: Time delay, engine start. Time Delay, transfer to Emergency. UMD Timer for Pre, Post, or Both. T3/W3 elevator presignal time delay w/ bypass. Time delay, retransfer to normal. (set at 30 minutes) Time delay, engine cool down. (set at 300 seconds) Time delay neutral position on Delayed transition switches.
LOAD SHED, BLOCK TRANSFER & RE-ADD CRKTS. Special custom Load shed, Block Transfer & Re-add circuits shall be verified to be operational and be noted on the test reports. (If applicable) VERIFY TOTAL POWER FAILURE TO RESTORATION OF LOAD FROM EMERGENCY GENERATOR Time delay, engine start = 1 or 3 seconds (Engineering Dept to specify actual time) Time delay, transfer to emergency = .1-15 seconds (Engineering Dept to specify actual time) Time delay, presignal = 10-20 seconds (Elevator contractor to specify actual required time) Time delay, load shed = 1-30 seconds (Engineering Dept to specify actual required time delay) Engine up to speed time = typical 4.5-6 seconds Retransfer to normal position = 5 minutes Insure total transfer time on Critical or Life Safety switches do not exceed 10 seconds. Insure that Elevator transfer switches transfer within 10 seconds, or as allowed by Mass Elevator Regulations (524 CMR) which is typically 25 seconds.
BYPASS/ISOLATION SWITCH TESTS Provide bypass to normal and bypass to emergency operations with Isolation option for each. Ensure no load-break condition exists. (Switch must be a make-before-break arrangement) If switches are of the Load-break design, Engineering will establish the time & date for these tests. Verify Manual Transfer switch function of Bypass switch. (Manual Transfer Switch Operation) Ensure engine start contacts stay closed with ATS module out in Isolate position After switch is isolated, rack ATS module back into the TEST position and cycle the switch through a complete sequence. Follow manufacturer s instructions for returning switch to normal operating position Verify B/I module relays are properly energized and that all blocking interlocks are operating correctly. Verify all auxiliary and B/I engine start contacts.
QUALIFICATIONS FOR BIDDERS: Qualified Bidders Shall be NETA certified Company and either Factory Trained & Authorized or Factory Trained on the Equipment to be tested. (General Electric, Zenith Controls, Russelectric, Pace, Asco, Westinghouse, Kohler, and Generac) and have a minimum of 20 years of experience, as many of the VA sites have older gear operating on site in excess of 15 years. Submit qualifications for technical review.
The Field Engineer/Technician shall also be a Certified Level 2 or greater Thermographer.
SUBCONTRACTORS If Prime vendor determines to utilize subcontractors, Prime vendor must be physically present at all times there are sub-contractors present, work activities are ongoing, materials are being delivered, etc. In addition, Prime vendor to submit in technical proposal the delineation of work from prime and subcontractors to include percentage (%) of work breakdown and description of work activities.
TEST REPORT REQUIREMENTS: Test Reports are required to document results of each switch.
PREMIUM TIME WORK:
Bidders are reminded that all work must be done on premium time as designated by the contract.
PLEASE NOTE: TESTING OF BYPASS/ISOLATION SWITCHES REQUIRES ADDITIONAL TESTING CRITERIA DIFFERENT AND IN ADDITION TO A STANDARD ATS. Bid prices shall be per unit and Campus may add or delete units from their BOM. All services & inspections shall be scheduled thru COR. No additional work can be performed under this contract, and no changes to this Scope of Work can be made without the authority and prior approval of the Contracting Officer. 3.0 Equipment to be serviced: ATS Inventory   Designation Make Model Serial Controller Location EE# 1 B1-1 Russelectric RTBD-4004CEF 30535-1 A/8 2000 B1 82503 2 B1-2 Russelectric RTBD-4004CEF 30535-2 C/D 2000 B1 82502 3 B1-3 Russelectric RTBD-6004CEF 30535-2 A/8 2000 B1 82495 4 B1-4 Russelectric RTBD-6004CEF 30535-2 C/D 2000 B1 82498 5 B1-5 Russelectric RTBD-4004CEF 30535-1 E/F 2000 MCC431-01-WR 82501 6 B1-6 (Fire pump) Zenith       GD130-01-WR 56611 7 B1-7 Russelectric RTBD-6004CEF 30535-2 E/F 2000 A3E-06 (B1) 82497 8 B1-8 Russelectric RTBD-6004CEF 30535-2G/H 2000 A3 061 (B1) 82504 9 B1-10 Russelectric RTBDLBCT-8004CEF 35621-2A/B 2000 B1 136551 10 B1-11 Russelectric RTS03-ABLB6004AMF1 36512-1A/B RPTCS B1 147444 11 Emg Light Relays         Auditorium   12 A3C-1 (ATS-2) Russelectric RTB-4004CEF 24509-3A/B 2000 B2 62947 13 A3C-2 (ATS-1) Russelectric RTB-2604CEF 24509-1A/B 2000 B2 62948 14 A3C-3 (ATS-8) Russelectric RTB-4004CEF 35621-1A/B 2000 B2 136550 15 A3C-4 (ATS-11) Russelectric RTS03-ABLB4004AMF1 39016 -1A/B RPTCS     16 A3S-1 (ATS 5) Russelectric RTB-2604CEF 24509-1C/D 2000 B2 62945 17 A4E-1 (ATS 4) Russelectric RTB-4004CEF 24509-2A/B   B2 62946 18 A4E-2 (ATS 6) Russelectric RTB-4004CEF 29772-1A/B 2000 B2 73136 19 A4E-3 (ATS 10) (Fire pump) Zenith       B2 72469 20 A4E-4 (ATS-3) Russelectric RTB-4004CEF 31010-1 A/B   B2 83279 21 A4E-5 (ATS-9) Russelectric RTBDLB-6004CEF 35145-1 A/B 2000 B2 136549 22 A4E-7 (ATS-7) Russelectric RTS03-ABLB8004AMF1 36466-1A/B RPTCS B2 168928 23 ATS- (Mobile OR) GE       B2 73137 25 B8-Boiler Russelectric RTS03-ABLA4004AMF1 36608-1A/B RPTCS B8 140803 26 B20-Research Russelectric RTS03-ABLB8004AMF1 38472-1A/B RPTCS B20   27 B21-Research Russelectric RTBDNB-6004CEF 35273-1A/B 2000 B21 136548 28 B3-1 Russelectric RTBD-1004CEF 29772-2A/B 2000 B3 71293 29 B3-2 Russelectric RTBDLB-4004CEF 33859-2C/D 2000 B3 104155 30 B3-3 Russelectric RTBDLB-4004CEF 33859-2A/B 2000 B3 104153 31 B3-4 Russelectric RTBDLB-6004CEF 33859-1A/B 2000 B3 104154 32 B3-5 Russelectric RTBDLB-4004CEF 37890-1A/B RPTCS B3 167460 33 Garage Russelectric     RPTCS Garage   34 Garage Russelectric     RPTCS Garage  
The NAICS code for this requirement is 811310.
Russelectric, a Siemens Business is the OEM for 34 automatic transfer switches at the West Roxbury Campus. Russelectric, a Siemens Business, is the only company that can interface with the PLC controller on the ATS to diagnosis issues and perform maintenance as required per manufacture and maintain required UL equipment rating/approval of all equipment.
This notice of intent is not a solicitation nor is it a request for proposal. However, all responsible sources may submit a capability statement demonstrating the ability to provide the requested services, in writing by Thursday, October 30, 2025 at 3PM EST time. Responses should be sent to Rosangela Pereira at contact@example.gov. Information submitted in response to this notice will be used solely to determine whether competitive procedures could be used for this acquisition. A determination not to open the requirement to competition based upon responses to this notice is solely within the discretion of the Government.

More opportunities from Department Of Veterans Affairs → 241-NETWORK Contract Office 01 (36C241)

Same awarding agency

NAICS: 532490
New
Federal
W038--Wheeled Rental Loader - Winter FY27
Solicitation # 36C24126Q0815
The VA Maine Healthcare System Togus is seeking a qualified vendor under a total set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) to provide month-to-month rental and support services for two wheeled loaders and snow removal attachments. The equipment, specified as CAT 926 or CAT 930 models weighing between 27,972 and 31,124 lbs, will be used for snow removal at the Togus VAMC campus in Augusta, Maine. Requirements include a 3-yard bucket with a Fusion coupler, 160 to 170 hp Tier 4 Final engines, ROPS/FOPS certified cabs, and liquid-filled tires. The contractor must provide 24/7 service and support, with repairs initiated within 24 hours of notification or the provision of a replacement loader at no additional cost. All preventive maintenance, repairs, and delivery/pickup charges must be included in the firm fixed price quote. The procurement is governed by NAICS code 532490 and follows FAR subpart 12.6 streamlined procedures. Award will be based on a comparative evaluation of technical capability, past performance, and price, with the contract awarded to the responsible vendor who is technically acceptable and offers the lowest evaluated price. Vendors must submit a firm fixed price quote, a technical capability statement, and a signed Limitation of Subcontracting certificate. Strict security and health protocols apply, including mandatory security badging, adherence to VA non-smoking policies, and proof of vaccinations for influenza, COVID-19, and tuberculosis testing for all personnel accessing the station. All quotes must be submitted to the designated contact by November 2, 2026, at 5:00 PM EST.
Other Commercial and Industrial Machinery and Equipment Rental and Leasing

POSTED

about 14 hours ago

DEADLINE

in 6 days
View Details
NAICS: 561210
New
Federal
F109--Water Management Program and Chemical Testing Amendment 001- Q&A
Solicitation # 36C24127Q0016
The Department of Veterans Affairs Network Contracting Office 01 is soliciting quotes for a new Water Management Program and Chemical Testing contract to support three VAMC Boston Healthcare System campuses in Jamaica Plain, West Roxbury, and Brockton. This procurement is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) and Veteran-Owned Small Businesses (VOSB) under NAICS code 561210. The contractor will be responsible for developing, testing, and maintaining a comprehensive Water Management Program, including monthly and quarterly water testing and the implementation of a web-based data management system. All services and reporting must align with AAMI ST-108:2023 standards. The anticipated period of performance consists of a base year from March 1, 2027, to February 29, 2028, with four one-year option renewals. Amendment 0001 updated the Statement of Work, added a Questions and Answers document, and extended the response deadline to November 6, 2026, at 12:00 PM EST. Award will be based on a comparative evaluation of technical quality, qualifications, past performance, veterans involvement, and price. Key technical requirements include the use of an accredited laboratory located within the contiguous United States (east of or within MN, IA, MO, AR, and LA), the assignment of dedicated on-site personnel for monthly testing, and a demonstration of independence with no conflict of interest regarding the sale of treatment chemicals. Prospective offerors must be registered in SAM and the SBA VetCert database and must complete VA vendorization via Form 10091 to be eligible for award.
Facilities Support Services

POSTED

about 14 hours ago

DEADLINE

in 10 days
View Details
NAICS: 532490
New
Federal
W065--Karl Storz Brand Name or Equal Equipment Lease
Solicitation # 36C24127Q0039
The VA Boston Healthcare System is soliciting quotes for a 36-month Fair Market Value lease of endoscopy video systems, insufflators, wireless systems, and related components for the VA Maine Healthcare System in Togus. This unrestricted procurement, under NAICS code 532490, seeks Karl Storz brand name or equal equipment to support clinical workflows across general surgery, urology, gynecology, ENT, and arthroscopy. The comprehensive solution must include the equipment, OEM installation, configuration, on-site training for clinical and SPS staff, and full-service maintenance. Key technical requirements include high-resolution 2D, 3D, and NIR/ICG fluorescence imaging, as well as a diverse portfolio of rigid and flexible optics. The contract consists of a base year and two option years, with a requirement that all new equipment be delivered within 45 days of award. Award will be based on a comparative evaluation of technical quality, past performance, price, speed of delivery, and veterans involvement, with specific evaluation credit given to SDVOSB and VOSB entities. Offerors proposing equal products must provide detailed documentation of compliance with all salient characteristics. All quotes must be submitted via email to the contracting officer by November 1, 2026, and must include a formal statement of acceptance regarding the solicitation terms and conditions.
Other Commercial and Industrial Machinery and Equipment Rental and Leasing

POSTED

about 14 hours ago

DEADLINE

in 5 days
View Details
NAICS: 713940
New
Federal
G003--Gym Rental Services
Solicitation # 36C24127Q0040
The Department of Veterans Affairs intends to award a sole source contract for gym rental services to support the Gerofit Program at the VA Medical Center Northampton. Under NAICS code 713940 and PSC G003, the agency seeks a facility within a 15-minute drive of the Edward P. Boland Department of Veterans Affairs Medical Center to temporarily relocate the program due to renovations and safety issues. The required space must be between 2,000 and 3,000 square feet of enclosed multi-purpose area, accessible three times per week for 2.5 hours to accommodate classes of 20 to 25 people. Key facility requirements include strong WIFI for livestreaming classes via WebEx and on-site storage for VA equipment, such as projector screens and gym items. The period of performance is scheduled to begin on November 15, 2026, consisting of a firm six-month term with an additional six-month option. This action is being conducted under the authority of FAR 12.102 and FAR Part 5. To be eligible for award, prospective firms must be registered in SAM.gov and VetCert, and those claiming small business status must be verified by the Small Business Administration. Additionally, vendors must be vendorized by completing Form 10091. Interested parties should register via the SAM.gov interested vendors list, and any inquiries should be directed to the Contracting Officer, Tara Dossiema.
Fitness and Recreational Sports Centers

POSTED

about 14 hours ago

DEADLINE

in 14 days
View Details

Earlier notices in this NAICS code

Posted before this notice, open and closed

Find Active Opportunities Like This

Get AI-powered intelligence on the opportunities still open

Every page of the solicitation package shredded into a compliance breakdown

AI-powered matching based on your capabilities and past performance

Competitor and incumbent history on the requirement

Automated alerts on amendments, Q&A deadlines, and award

Miguel
Hillary
Keith Deutsch
Christine

Join 750+ contractors already using CLEATUS