Z2DA--Replace Dual Duct Boxes on Second Floor - 539-21-201

Closed
36C25026B0042Federal

Contract Overview

Solicitation details, issuing organization, response deadlines, documents, and interested companies for this government contract opportunity.

Active Opportunities Like This One

AI Contract Overview

Show more

This contract involves the replacement of dual duct mixing boxes located on the second floor of a facility, identified by solicitation number 36C25026B0042. The work falls under the NAICS code 238220, indicating it pertains to plumbing, heating, and air-conditioning contractors. The Department of Veterans Affairs, through its 250-NETWORK Contract Office 10 in Dayton, Ohio, is overseeing the solicitation. Interested parties must submit their responses by the deadline on June 11, 2026. The contract is managed by Contracting Officer Ronald T Heidemann, who serves as the primary point of contact. While the exact location for the place of performance is unspecified, the solicitation is publicly posted and detailed information can be accessed online through the SAM.gov workspace link. The contract is categorized as a solicitation without any specified set-aside, meaning it is open to all qualified bidders. The project primarily focuses on mechanical system maintenance and improvements within a government facility, ensuring proper air distribution and ventilation through the upgraded mixing boxes.

General Info

Replacement of second-floor dual duct mixing boxes for VA facility; bids due June 11, 2026.

Agency

Department Of Veterans Affairs → 250-NETWORK Contract Office 10 (36C250)

NAICS

238220 - Plumbing, Heating, and Air-Conditioning Contractors View NAICS

Place of Performance

OH

Set-Aside

NONE

Documents

(20)

Justification and Approval for Tridium Niagara System Building Management Controls System

PDFjustification-and-authorization

Lead Paint Report for CVAMC 2nd Floor Duct Boxes Renovation

PDFreport

Amendment 0002 to IFB 36C25026B0042 for VAMC Cincinnati Duct Replacement

DOCXamendment

Solicitation 36C25026B0042 - Replace Dual Duct Mixing Boxes on Second Floor

DOCXifb

Pre-Award Contractor Safety and Environmental Record Evaluation Form for Project 539-21-201

DOCXpre-award-safety-evaluation

Attachment 4 - Drawings

PDFdrawings

RFI 36C25026B0042 Replace Dual Duct Mixing Boxes on Second Floor

DOCXrfi

ICRA Construction Health and Safety Form for Replace Dual Duct Boxes Project 539-21-201

PDFconstruction-health-safety-form

VHA Pre-Construction Risk Assessment (PCRA) for Project 539-21-201

PDFpcra

VHA Directive 1192.01 Seasonal Influenza Vaccination Program for VHA Health Care Personnel

PDFdirective

VAAR 852.219-75 Certificate of Compliance for Services and Construction

DOCXcertificate-of-compliance

Atch+RFI+6+life+safety+plan.pdf

PDF

IFB 36C25026B0042 Replace Dual Duct Mixing Boxes Project

PDFifb

Justification and Approval for Tridium Facility Explorer BAS Controllers at Cincinnati VAMC

PDFjustification-and-authorization

Amendment 0001 to Solicitation 36C25026B0042

DOCXamendment

Technical Specifications for Replace Dual Duct Boxes on 2nd Floor VA Project 539-21-201

PDFspecifications

Asbestos Survey Report for Replace Dual Duct Boxes on 2nd Floor - Cincinnati VA Medical Center

PDFsurvey-report

Presolicitation 36C25026B0042 Replace Dual Duct Boxes on Second Floor

DOCXpresolicitation

Justification and Approval for Honeywell/Siemens/Johnson Controls Controllers

PDFjustification-and-authorization

OH20260082 Ohio Hamilton County Building Construction Wage Determination

PDFwage-determination

AI Contract Breakdown

Uniform Contract Format

Sign up to view the full breakdown with detailed analysis of each section.

Timeline

2 updates
PhaseClosed
Posted

Solicitation

Amendment 0

Contract was updated

Amendment 2

Contract was updated

Response Deadline

Deadline has passed

Submission Closed

Find active opportunities like this

Start your free trial to discover similar active contracts, track opportunities, and build proposals with AI assistance.

Organization & Contact Information

Show more
AgencyDepartment Of Veterans Affairs → 250-NETWORK Contract Office 10 (36C250)
Contacts1 person available
OfficeDAYTON, OH, 45428, USA
Organization / Agency
Department Of Veterans Affairs → 250-NETWORK Contract Office 10 (36C250)
Office AddressDAYTON, OH, 45428, USA
Contacts
Ronald T HeidemannContracting Officer

Full Description

Show more
REPLACE DUAL DUCT BOXES ON THE SECOND FLOOR FOR THE VETERANS AFFAIRS MEDICAL CENTER (VAMC) CINCINNATI, OH PROJECT NUMBER: 539-21-201 QUESTIONS AND ANSWERS (RFIs) TO REQUEST FOR INVITATION FOR BID (IFB) NUMBER: 36C25026B0042
QUESTIONS AND ANSWERS : RFI #1 Question: spec 01 00 00 lay down and dumpster area: Where will the laydown and dumpsters area be located?
Answer: There is no guarantee of laydown space, contractors shall plan accordingly to support their material. Yes, power is available. Dumpster location will be coordinated with COR. RFI #2 Question: Parking: How many parking spaces will be provided?
Answer: Per specification 010000 section: 1.5F2. There will be no parking by any contractors on the VA campus
RFI #3 Question: spec 01 35 26 SSHO: Can the superintendent be dual-hatted and fulfill the role of SSHO?
Answer: Yes, the superintendent and SSHO can perform both roles
RFI #4 Question: spec 02 83 33.13 LBP: Can the government please identify the location and quantities of LBP (lead-based paint) remediation?
Answer: The samples tested pertained to painted plaster (white) walls. The analytical results indicated that the white-painted plaster walls contain 480 parts per million (ppm) of lead. If white painted plaster walls are Impacted by the project, contractors should be aware and take the appropriate precautions to comply with OSHA regulations and VA project specifications see lead paint report attached.
RFI #5 Question: Procore software: Will the government accept the use of Procore construction management software?
Answer: Yes.
RFI #6 Question: Life safety drawings: Can the government please provide life safety drawing showing existing smoke and fire walls within the project boundaries?
Answer: Existing smoke and fire walls are shown on the drawings. No changes in the safety plan see attached life safety plan.
RFI #7 Question: spec 02 82 11 asbestos abatement 1.1.2 extent of work: Is all the ACM removal associated with the mechanical demo? I.E. no abatement is expected to remove mastic etc. on duct, pipe boxes that are not shown for removal.
Answer: Yes, the abatement scope is associated with the mechanical demo- see mechanical drawings - see attachment.
RFI #8 Question: spec 02 82 11 asbestos abatement 1.1.2 extent of work material locations table: Where is Corridor A-2-15 located?
Answer: Contractor to bid quantities for removal. Corridor is C*2*3. Also, corridor A-2-15 is to the north. RFI #9 Question: spec 02 82 11 3.2 removal of ACM/phasing: As the specs call for critical barriers, an attached 3-stage decontamination unit, drop cloths beneath the work, and negative pressure requirements of this specification for any level of abatement. Would the Government allow the phasing for the abatement to include "owning" both sides of the corridors (closed to traffic) for the abatement in the corridors?
Answer: All work within corridors shall occur during weekends, between 8PM Friday and 6AM Monday. The corridors shall be opened for normal operations outside of these hours. It is permissible to own both sides (closing traffic) during weekend work. Coordinate with COR.
RFI #10 Question: Drawing 1-A001 detail 16 and note 2: 1) Note 2 calls for new wall covering. Does the VA have attic stock to match? If not, can we paint, or please provide the wallpaper manufacturer series and color? 2) detail 16 labels room as C242 is this mislabeled and should be A242?
Answer: Paint is an acceptable finish coordinate with COR to match attic stock; the contractor is to provide a level 5 finish from corner to corner. Detail 16 label is mislabeled and should be A242.